Full Text Searchable PDF User Manual
361819-YIM-A-0208
R-410A
OUTDOOR SPLIT-SYSTEM
HEAT PUMP
MODELS: 18 SEER - YZE03811 SERIES
3 TON
INSTALLATION MANUAL
ISO 9001
Certified Quality
Management System
LISTED
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for the smallest rated indoor coil plus 15 feet of field
supplied lines.
Matching indoor coils are available with a thermal expansion valve or
an orifice liquid feed sized for the most common usage. The orifice size
and/or refrigerant charge may need to be changed for some indoor-out-
door unit combinations, elevation differences or total line lengths. Refer
to Application Data covering “General Piping Recommendations and
Refrigerant Line Length” (Part Number 036-61920-001).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words
DANGER
,
WARNING
, or
CAUTION
.
DANGER
indicates an
imminently
hazardous situation, which, if not
avoided,
will result in death or serious injury
.
WARNING
indicates a
potentially
hazardous situation, which, if not
avoided,
could result in death or serious injury
.
CAUTION
indicates a potentially hazardous situation, which, if not
avoided
may result in minor or moderate injury
. It is also used to
alert against unsafe practices and hazards involving only property dam-
age
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.
R-410A systems operate at higher pressures than R-22 systems.
Do not use R-22 service equipment or components on R-410A
equipment. Service equipment
Must Be Rated
for R-410A.
TABLE OF CONTENTS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATIONS REQUIRING TXV . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
LIST OF FIGURES
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Typical Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CFM Selection Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Thermostat Wiring – Two-Stage Heat Pumps -
Two-Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . 7
Thermostat Wiring – Two-Stage Heat Pump -
Two-Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . 8
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Modulating Furnace . . . . . . . . . . . . . . . . . . . . . . . . .11
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Modulating Furnace . . . . . . . . . . . . . . . . . . . . . . . . .12
Heat Pump Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
LIST OF TABLES
Defrost Initiate Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
361819-YIM-A-0208
2
Unitary Products Group
INSPECTION
As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information.
Requirements For Installing/Servicing R-410A Equipment
•
Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle POE oils, and the higher pressures
of R-410A.
•
Manifold sets should be 800 PSIG high side and 250 PSIG low
side with 550 PSIG low side restart.
•
All hoses must have a 700 PSIG service pressure rating.
•
Leak detectors should be designed to detect HFC refrigerant.
•
Recovery equipment (including refrigerant recovery containers)
must be specifically designed to handle R-410A.
•
Do not use an R-22 TXV.
•
A liquid-line filter drier is required on every unit.
LIMITATIONS
The unit should be installed in accordance with all National, State and
Local Safety Codes and the limitations listed below:
1.
Limitations for the indoor unit, coil and appropriate accessories
must also be observed.
2.
The outdoor unit must not be installed with any duct work in the air
stream. The outdoor fan is the propeller type and is not designed
to operate against any additional external static pressure.
3.
The maximum and minimum conditions for operation must be
observed to assure a system that will give maximum performance
with minimum service.
4.
This unit is not designed to operate with a low ambient kit. Do not
modify the control system to operate with any kind of low ambient
kit.
5.
The maximum allowable line length for this product is 75 feet.
SECTION III: UNIT INSTALLATION
LOCATION
Before starting the installation, select and check the suitability of the
location for both the indoor and outdoor unit. Observe all limitations and
clearance requirements.
The outdoor unit must have sufficient clearance for air entrance to the
condenser coil, for air discharge and for service access. See Figure 1.
NOTE:
For multiple unit installations, units must be spaced a minimum
of 18 inches apart. (Coil face to coil face.)
If the unit is to be installed on a hot sun exposed roof or a black-topped
ground area, the unit should be raised sufficiently above the roof or
ground to avoid taking the accumulated layer of hot air into the outdoor
unit.
Provide an adequate structural support.
ADD-ON REPLACEMENT/RETROFIT
When this unit is being used as a replacement for an R-22 unit, it is
required that the outdoor unit, indoor coil, and metering device all be
replaced. The following steps should be performed in order to insure
proper system operation and performance. Line-set change out is also
recommended.
1.
Change-out of the indoor coil to an approved R-410A coil/ con-
densing unit combination with the appropriate metering device.
2.
Change-out of the line-set when replacing an R-22 unit with an
R410-A unit is highly recommended to reduce cross-contamina-
tion of oils and refrigerants.
3.
If change-out of the line set is not practical, then the following pre-
cautions should be taken.
•
Inspect the line set for kinks, sharp bends, or other restrictions,
and for corrosion.
•
Determine if there are any low spots which might be serving as oil
traps.
•
Flush the line set with a commercially available flush kit to
remove as much of the existing oil and contaminants as possible.
•
Install a suction line filter-drier to trap any remaining contami-
nants, and remove after 50 hours of operation.
4.
If the outdoor unit is being replaced due to a compressor burnout,
then installation of a 100% activated alumina suction-line filter
drier in the suction-line is required, in addition to the factory
installed liquid-line drier. Operate the system for 10 hours. Monitor
the suction drier pressure drop. If the pressure drop exceeds 3
psig, replace both the suction-line and liquid-line driers. After a
total of 10 hours run time where the suction-line pressure drop has
not exceeded 3 psig, replace the liquid line drier, and remove the
suction-line drier. Never leave a suction-line drier in the system
longer than 50 hours of run time.
AIR TEMPERATURE DB AT
OUTDOOR COIL, °F
AIR TEMPERATURE AT
INDOOR COIL, °F
Min.
Max.
Min.
Max.
Cool
Heat
Cool
Heat
°
WB
Cool
°
DB
Heat
°
WB
Cool
°
DB
Heat
50
-10
115
75
57
50
1
1. Operation below this temperature is permissible for a short period of
time, during morning warm-up.
72
80
FIGURE 1:
Typical Installation
THERMOSTAT
NEC CLASS 1
WIRING
TO INDOOR
BLOWER
NEC CLASS 2
WIRING
TO COIL
WEATHERPROOF
DISCONNECT SWITCH
48” OVERHEAD
CLEARANCE
24” SERVICE
ACCESS
CLEARANCE
18” FRONT
& SIDES
NOTE:
ALL OUTDOOR WIRING MUST BE WEATHERPROOF
SEAL OPENINGS WITH
PERMAGUM OR EQUIVALENT
361819-YIM-A-0208
Unitary Products Group
3
GROUND INSTALLATION
The unit may be installed at ground level on a solid base that will not
shift or settle, causing strain on the refrigerant lines and possible leaks.
Maintain the clearances shown in Figure 1 and install the unit in a level
position.
Normal operating sound levels may be objectionable if the unit is placed
directly under windows of certain rooms (bedrooms, study, etc.).
Condensate will drain from beneath the coil of the outdoor unit during
the defrost cycle. Normally this condensate may be allowed to drain
directly on the ground.
Elevate the unit sufficiently to prevent any blockage of the air entrances
by snow in areas where there will be snow accumulation. Check the
local weather bureau for the expected snow accumulation in your area.
Isolate the unit from rain gutters to avoid any possible wash out of the
foundation.
ROOF INSTALLATION
When installing units on a roof, the structure must be capable of sup-
porting the total weight of the unit, including a pad, lintels, rails, etc.,
which should be used to minimize the transmission of sound or vibra-
tion into the conditioned space.
UNIT PLACEMENT
1.
Provide a base in the pre-determined location.
2.
Remove the shipping carton and inspect for possible damage.
3.
Compressor tie-down bolts should remain tightened.
4.
Position the unit on the base provided.
NOTE:
Heat pumps will defrost periodically resulting in water drainage.
The unit should not be located where water drainage may freeze
and create a hazardous condition - such as sidewalks and
steps.
LIQUID LINE FILTER-DRIER
The heat pumps have a solid core bi-flow filter/dryer located on the liq-
uid line.
NOTE: Replacements for the liquid line drier must be exactly the same
as marked on the original factory drier. See
Source 1 for O.E.M.
replacement driers.
PIPING CONNECTIONS
The outdoor unit must be connected to the indoor coil using field sup-
plied refrigerant grade copper tubing that is internally clean and dry.
Units should be installed only with the tubing sizes for approved system
combinations as specified in Tabular Data Sheet. The charge given is
applicable for total tubing lengths up to 15 feet. See Application Data
Part Number 036-61920-001 for installing tubing of longer lengths and
elevation differences.
NOTE:
Using a larger than specified line size could result in oil return
problems. Using too small a line will result in loss of capacity
and other problems caused by insufficient refrigerant flow. Slope
horizontal vapor lines at least 1" every 20 feet toward the out-
door unit to facilitate proper oil return.
PRECAUTIONS DURING LINE INSTALLATION
1.
Install the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.
2.
The lines should be installed so that they will not obstruct service
access to the coil, air handling system or filter.
3.
Care must also be taken to isolate the refrigerant lines to minimize
noise transmission from the equipment to the structure.
4.
The vapor line must be insulated with a minimum of 1/2" foam rub-
ber insulation (Armaflex or equivalent). Liquid lines that will be
exposed to direct sunlight and/or high temperatures must also be
insulated.
Tape and suspend the refrigerant lines as shown. DO NOT allow tube
metal-to-metal contact. See Figure 2.
5.
Use PVC piping as a conduit for all underground installations as
shown in Figure 3. Buried lines should be kept as short as possible
to minimize the build up of liquid refrigerant in the vapor line during
long periods of shutdown
6.
Pack fiberglass insulation and a sealing material such as perma-
gum around refrigerant lines where they penetrate a wall to reduce
vibration and to retain some flexibility.
7.
See Form 690.01-AD1V for additional piping information.
The outdoor unit should not be installed in an area where mud or
ice could cause personal injury. Remember that condensate will
drip from the unit coil during heat and defrost cycles and that this
condensate will freeze when the temperature of the outdoor air is
below 32°F.
Failure to do so or using a substitute drier or a granular type may
result in damage to the equipment.
R-410A / R-22
Filter-Drier
Source 1 Part No.
Apply with Models
YZE
026 - 25512 - 000
All Sizes
This system uses R-410A refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle R-410A. If you are unsure, consult the
equipment manufacturer.
Never install a suction-line filter drier in the liquid line of an R-410A
system. Failure to follow this warning can cause a fire, injury or
death.
FIGURE 2:
Tubing Hanger
Liquid
Line
Incorrect
Correct
Tape
Sheet Metal Hanger
Insulated Vapor Line
361819-YIM-A-0208
4
Unitary Products Group
PRECAUTIONS DURING BRAZING OF LINES
All outdoor unit and evaporator coil connections are copper-to-copper
and should be brazed with a phosphorous-copper alloy material such
as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units
have reusable service valves on both the liquid and vapor connections.
The total system refrigerant charge is retained within the outdoor unit
during shipping and installation. The reusable service valves are pro-
vided to evacuate and charge per this instruction.
Serious service problems can be avoided by taking adequate precau-
tions to assure an internally clean and dry system.
PRECAUTIONS DURING BRAZING SERVICE VALVE
Wrap a wet rag around the service valve as shown in Figure 4 to pre-
vent heat damage. Also, protect all painted surfaces, insulation, and
plastic base during brazing. After brazing cool joint with wet rag.
Valve can be opened by removing the plunger cap and fully inserting a
hex wrench into the stem and backing out counter-clockwise until valve
stem just touches the chamfered retaining wall.
Connect the refrigerant lines using the following procedure:
1.
Remove the cap and Schrader core from both the liquid and vapor
service valve service ports at the outdoor unit. Connect low pres-
sure nitrogen to the liquid line service port.
2.
Braze the liquid line to the liquid valve at the outdoor unit. Be sure
to wrap the valve body with a wet rag. Allow the nitrogen to con-
tinue flowing. Refer to the Tabular Data Sheet for proper liquid line
sizing.
3.
Carefully remove the rubber plugs from the evaporator liquid and
vapor connections at the indoor coil.
4.
Braze the liquid line to the evaporator liquid connection. Nitrogen
should be flowing through the evaporator coil.
5.
Slide the grommet away from the vapor connection at the indoor
coil. Braze the vapor line to the evaporator vapor connection. After
the connection has cooled, slide the grommet back into original
position. Refer to the Tabular Data Sheet for proper vapor line siz-
ing.
6.
Protect the vapor valve with a wet rag and braze the vapor line
connection to the outdoor unit. The nitrogen flow should be exiting
the system from the vapor service port connection. After this con-
nection has cooled, remove the nitrogen source from the liquid fit-
ting service port.
7.
Replace the Schrader core in the liquid and vapor valves.
8.
Go to “SECTION IV” for TXV installation.
9.
Leak test all refrigerant piping connections including the service
port flare caps to be sure they are leak tight. DO NOT OVER-
TIGHTEN (between 40 and 60 inch - lbs. maximum).
10. Evacuate the vapor line, evaporator and the liquid line, to 500
microns or less.
NOTE:
Line set and indoor coil can be pressurized to 250 psig with dry
nitrogen and leak tested with a bubble type leak detector. Than
release the nitrogen charge.
NOTE:
Do not use the system refrigerant in the outdoor unit to purge or
leak test.
11.
Replace cap on service ports. Do not remove the flare caps from
the service ports except when necessary for servicing the system.
12. Release the refrigerant charge into the system. Open both the liq-
uid and vapor valves by removing the plunger cap and with an
allen wrench back out counter-clockwise until valve stem just
touches the chamfered retaining wall. See Page 4 "PRECAU-
TIONS DURING BRAZING SERVICE VALVE".
13. Replace plunger cap finger tight, then tighten an additional 1/12
turn (1/2 hex flat). Cap must be replaced to prevent leaks.
FIGURE 3:
Underground Installation
Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature required is high enough
to cause oxidation of the copper unless an inert atmosphere is pro-
vided. The flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety valve to insure
that only low pressure dry nitrogen is introduced into the tubing.
Only a small flow is necessary to displace air and prevent oxidation.
This is not a backseating valve. The service access port has a
valve core. Opening or closing valve does not close service access
port.
If the valve stem is backed out past the chamfered retaining wall,
the O-ring can be damaged causing leakage or system pressure
could force the valve stem out of the valve body possibly causing
personal injury.
TO INDOOR COIL
TO O UTDOOR UNIT
LIQUID LINE
CAP
PVC
CONDUIT
INSULATED
VAPOR LINE
FIGURE 4:
Heat Protection
The evaporator is pressurized.
Do not connect manifold gauges unless trouble is suspected.
Approximately 3/4 ounce of refrigerant will be lost each time a stan-
dard manifold gauge is connected.
361819-YIM-A-0208
Unitary Products Group
5
See "System Charge” section for checking and recording system
charge.
SECTION IV: INSTALLATIONS REQUIRING
TXV
For installations requiring a TXV, the following are the basic steps for
installation. For detailed instructions, refer to the Installation Instructions
accompanying the TXV kit.
Install TXV kit as follows:
1.
First, relieve the holding charge by depressing the Schrader valve
located in the end of the liquid line.
2.
After holding charge is completely discharged, loosen and remove
the liquid line fitting from the orifice distributor assembly. Note that
the fitting has
right
hand
threads
.
3.
Remove the orifice from the distributor body using a small diame-
ter wire or paper clip. Orifice is not used when the TXV assembly
is installed.
4.
After orifice is removed, install the thermal expansion valve to the
orifice distributor assembly with supplied fittings. Hand tighten and
turn an additional 1/8 turn to seal. Do not overtighten fittings.
5.
Reinstall the liquid line to the top of the thermal expansion valve.
Hand modify the liquid line to align with casing opening.
6.
Install the TXV equalizer line into the vapor line as follows:
a.
Select a location on the vapor line for insertion of the equal-
izer line which will not interfere with TXV bulb placement.
b.
Use an awl to punch through the suction tube and insert the
awl to a depth to achieve a 1/8” diameter hole.
7.
Install TXV equalizer line in 1/8” hole previously made in vapor
line. Equalizer line should not be bottomed out in vapor line. Insert
equalizer line at least 1/4” in the vapor line. Braze equalizer line
making sure that tube opening is not brazed closed.
All connections to be brazed are copper-to-copper and should be
brazed with a phosphorous-copper alloy material such as Silfos-5 or
equivalent. DO NOT use soft solder.
Install the TXV bulb to the vapor line near the equalizer line, using the
two bulb clamps furnished with the TXV assembly. Ensure the bulb is
making maximum contact. Refer to TXV installation instruction for view
of bulb location.
a.
Bulb should be installed on a horizontal run of the vapor line if
possible. On lines under 7/8" OD the bulb may be installed on
top of the line. With 7/8" OD and over, the bulb should be
installed at the position of about 2 or 10 o'clock.
b.
If bulb installation is made on a vertical run, the bulb should
be located at least 16 inches from any bend, and on the tub-
ing sides opposite the plane of the bend. The bulb should be
positioned with the bulb tail at the top, so that the bulb acts as
a reservoir.
c.
Bulb should be insulated using thermal insulation provided to
protect it from the effect of the surrounding ambient tempera-
ture.
SECTION V: ELECTRICAL CONNECTIONS
GENERAL INFORMATION & GROUNDING
Check the electrical supply to be sure that it meets the values specified
on the unit nameplate and wiring label.
Power wiring, control (low voltage) wiring, disconnect switches and over
current protection must be supplied by the installer. Wire size should be
sized per NEC requirements.
The complete connection diagram and schematic wiring label is located
on the inside surface of the unit service access panel and this instruc-
tion.
FIELD CONNECTIONS POWER WIRING
1.
Install the proper size weatherproof disconnect switch outdoors
and within sight of the unit.
2.
Remove the screws at the bottom of the corner cover. Slide corner
cover down and remove from unit. See Figure 5.
3.
Run power wiring from the disconnect switch to the unit.
4.
Remove the service access panel to gain access to the unit wiring.
Route wires from disconnect through power wiring opening pro-
vided and into the unit control box.
5.
Install the proper size time-delay fuses or circuit breaker, and
make the power supply connections.
6.
Energize the crankcase heater if equipped to save time by pre-
heating the compressor oil while the remaining installation is com-
pleted.
Never attempt to repair any brazed connections while the system is
under pressure. Personal injury could result.
Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature required is high enough
to cause oxidation of the copper unless an inert atmosphere is pro-
vided. The flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety valve to insure
that only low pressure dry nitrogen is introduced into the tubing.
Only a small flow is necessary to displace air and prevent oxidation.
In all cases, mount the TXV bulb after vapor line is brazed and has
had sufficient time to cool.
All field wiring must USE COPPER CONDUCTORS ONLY and
be in accordance with Local, National Fire, Safety & Electrical
Codes. This unit must be grounded with a separate ground
wire in accordance with the above codes.
FIGURE 5:
Typical Field Wiring
CONTROL
WIRING
POWER
WIRING
CORNER
COVER
SERVICE
ACCESS
PANEL
361819-YIM-A-0208
6
Unitary Products Group
FIELD CONNECTIONS CONTROL WIRING
1.
Route low voltage wiring into bottom of control box as shown in
Figure 5. Make low voltage wiring connections inside the junction
box per Figures 7 - 12.
2.
The complete connection diagram and schematic wiring label is
located on the inside surface of the unit service access panel.
3.
Replace the corner cover and service access panel that were
removed in Steps 2 and 4 of the “Field Connections Power Wiring”
section.
4.
All field wiring to be in accordance with national electrical codes
(NEC) and/or local-city codes.
5.
Mount the thermostat about 5 ft. above the floor, where it will be
exposed to normal room air circulation. Do not place it on an out-
side wall or where it is exposed to the radiant effect from exposed
glass or appliances, drafts from outside doors or supply air grilles.
6.
Route the 24-volt control wiring (NEC Class 2) from the outdoor
unit to the indoor unit and thermostat.
NOTE:
To eliminate erratic operation, seal the hole in the wall at the
thermostat with permagum or equivalent to prevent air drafts
affecting the operation of in the thermostat.
DEHUMIDIFICATION CONTROL
A dehumidification control accessory 2HU06700124 may be used with
variable speed air handlers or furnaces in high humidity areas. This
control works with the variable speed indoor unit to provide cooling at a
reduced air flow, lowering evaporator temperature and increasing latent
capacity. The humidistat in this control opens the humidistat contacts on
humidity rise. To install, refer to instructions packaged with the acces-
sory and Figures 7 - 12. Prior to the installation of the dehumidification
control, the jumper across the HUMIDISTAT terminals on the indoor
variable speed air handler or furnace CFM selection board must be
removed.
During cooling, if the relative humidity in the space is higher than the
desired set point of the dehumidification control, the variable speed
blower motor will operate at lower speed until the dehumidification con-
trol is satisfied. A 40-60% relative humidity level is recommended to
achieve optimum comfort.
If a dehumidification control is installed, it is recommended that a mini-
mum air flow of 325 cfm/ton be supplied at all times.
CFM SELECTION BOARD SETTINGS
For proper system operation the CFM Selection Board jumpers must be
set properly.
Refer to the Tabular Data Sheet for the recommended air flow settings
for each size condensing unit.
Set the cooling speed per the instructions for the air handler or furnace
by selecting the correct COOL and ADJ taps. Verify the airflow using
the LED display on the CFM selection board.
The HEAT PUMP jumper
MUST
be removed or in the “YES” position for
proper system operation.
The HUMIDISTAT jumper must also be removed or in the “YES” posi-
tion if a dehumidistat is installed.
FIGURE 6:
CFM Selection Board
CFM SELECTION BOARD
TAP SELECTION
D
C
B
A
D
C
B
A
COOL
HEAT
ADJ
DELAY
REMOVE FOR
HEAT PUMP
HUMIDISTAT
361819-YIM-A-0208
Unitary Products Group
7
For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the
Product Catalog Section.
FIGURE 7:
Thermostat Wiring – Two-Stage Heat Pumps - Two-Stage Variable Speed Furnaces
HP 24A
Two Stage Heat Pump – Two Stage Variable Speed Furnace (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
TWO STAGE
HEAT PUMP
Bonnet Sensor
(Optional)
C
24 – Volt Common
Y1
First Stage Compressor
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U71124
*PP32U72124
THERMOSTAT
R
24 – Volt Hot
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
DHM
Dehumidistat
HM
Humidistat
O
Reversing Valve
Energized in Cool
Change FFuel jumper
on the heat pump control
to “ON”
Part Numbers:
SAP = Legacy
126768 = 031-09137
18395 = 031-01996
340512 = 031-09178
1
1
Part Numbers:
SAP = Legacy
265904 = 031-09169
2
C
24 – Volt Common
R
24 – Volt Hot
Y1
Single Stage Compressor
TWO STAGE
VARIABLE SPEED
FURNACE CONTROL
G
Fan
TWO STAGE
VARIABLE SPEED
FURNACE
W/W1
First Stage Heat
Y/Y2
Second or Full
Stage Compressor
W2
Second Stage Heat
O
Reversing Valve
X/L
Malfunction Light
DHUM
Dehumidification
2
Move HEAT PUMP
jumper to “YES”
Move DHUM
jumper to “YES”
if humidistat is to be used.
PV(8/9)
ID MODELS
(F/L)*(8/9)V
YORKGUARD VI
CONTROL
(G/L)(8/9)V
YZE
OD MODELS
YZH
H*5
H*8
24VAC Humidifier
(Optional)
Step 1 of the Thermostat
Installer Table must be
set to Heat Pump
E2/P Switch must be in the
E2 position
Step 2 of the Thermostat
Installer Table must be
set to 2
Step 5 of Thermostat User
Configuration Menu must
be set to “ON” for
Dehumidification
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
361819-YIM-A-0208
8
Unitary Products Group
FIGURE 8:
Thermostat Wiring – Two-Stage Heat Pump - Two-Stage Variable Speed Furnaces
HP 24C
Two Stage Heat Pump – Two Stage Variable Speed Furnace (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
TWO STAGE
HEAT PUMP
Bonnet Sensor
(Optional)
Change FFuel jumper
on the heat pump control
to “ON”
Part Numbers:
SAP = Legacy
126768 = 031-09137
18395 = 031-01996
340512 = 031-09178
1
1
Part Numbers:
SAP = Legacy
265904 = 031-09169
2
C
24 – Volt Common
R
24 – Volt Hot
Y1
Single Stage Compressor
TWO STAGE
VARIABLE SPEED
FURNACE CONTROL
G
Fan
TWO STAGE
VARIABLE SPEED
FURNACE
W/W1
First Stage Heat
Y/Y2
Second or Full
Stage Compressor
W2
Second Stage Heat
O
Reversing Valve
X/L
Malfunction Light
DHUM
Dehumidification
2
Move HEAT PUMP
jumper to “YES”
Move DHUM
jumper to “YES”
if humidistat is to be used.
PV(8/9)
ID MODELS
(F/L)*(8/9)V
YORKGUARD VI
CONTROL
(G/L)(8/9)V
YZE
OD MODELS
YZH
H*5
H*8
C
24 – Volt Common
R
24 – Volt Hot
Y1
First Stage Compressor
O
Reversing Valve
Energized in Cool
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*DN22H00124
*DP22U70124
THERMOSTAT
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
C
24 – Volt Common
Y
First Stage Compressor
O/B
Reversing Valve
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U70124
THERMOSTAT
E
Emergency Heat
R
24 – Volt Hot
(Heat XFMR)
RC
24 – Volt Hot
(Cool XFMR)
AUX
Auxiliary Heat
Step 1 of Thermostat
Installer/Configuration
Menu must be set to “HP2”
Selection of GAS/ELEC
switch on thermostat
not necessary
Thermostat Installer Setup
0170-System Type-
must be set to 12
3 Heat/2 Heat Pump
Thermostat Installer Setup
0190-Changeover Valve-
must be set to 0
O/B terminal
Energized in Cooling
Thermostat Installer Setup
0200-Backup Heat Source-
must be set to 1
Heat Pump Backup Heat
Source is Fossil Fuel
External Humidistat
(Optional)
Open on Humidity Rise
Thermostat Installer Setup
0210-External Fossil Fuel
Kit- must be set to 1
Heat Pump Control
is Controlling Heat Pump
Backup Heat
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
3
361819-YIM-A-0208
Unitary Products Group
9
FIGURE 9:
Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Air Handler
HP 27A
Two Stage Heat Pump – Variable Speed Air Handler (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
TWO STAGE
HEAT PUMP
C
24 – Volt Common
Y1
First Stage Compressor
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U71124
*PP32U72124
THERMOSTAT
R
24 – Volt Hot
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
DHM
Dehumidistat
HM
Humidistat
Step 1 of the Thermostat
Installer Table must be
set to Heat Pump
O
Reversing Valve
Energized in Cool
1
24VAC Humidifier
(Optional)
Part Numbers:
SAP = Legacy
159481 = 031-09157
2
COM
24 – Volt Common
R
24 – Volt Hot
W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
Y1
Single Stage Compressor
Y/Y2
Second or Full
Stage Compressor
O
Reversing Valve
Energized in Cool
X/L
Malfunction Light
HUM
Dehumidification-
Open on Humidity Rise
VARIABLE SPEED
AIR HANDLER CONTROL
G
Fan
Move the MODE
jumper to “HP”
Move the HUM STAT
jumper to “YES”
if humidistat is to be used.
VARIABLE SPEED
AIR HANDLER
2
Part Numbers:
SAP = Legacy
126768 = 031-09137
18395 = 031-01996
340512 = 031-09178
1
AV
ID MODELS
SV
MV
YZE
OD MODELS
YZH
H*5
YORKGUARD VI
CONTROL
H*8
24VAC
Electronic Air Cleaner
(Optional)
E2/P Switch must be in the
E2 position
Step 2 of the Thermostat
Installer Table must be
set to 2
Step 5 of Thermostat User
Configuration Menu must
be set to “ON” for
Dehumidification
EAC(24 VAC out)
Electronic Air Cleaner
Refer to AH documentation
for W1 and W2 electric
heat staging options.
HUM OUT
(24 VAC out)
Second stage auxiliary
heat will be controlled by
the thermostat, not the
heat pump control when
wired as shown.
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
361819-YIM-A-0208
10
Unitary Products Group
FIGURE 10:
Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Air Handler
HP 27C
Two Stage Heat Pump – Variable Speed Air Handler (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
TWO STAGE
HEAT PUMP
C
24 – Volt Common
R
24 – Volt Hot
Y1
First Stage Compressor
O
Reversing Valve
Energized in Cool
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*DN22H00124
*DP22U70124
THERMOSTAT
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
Step 1 of Thermostat
Installer/Configuration
Menu must be set to “HP2”
Selection of GAS/ELEC
switch on thermostat
not necessary
C
24 – Volt Common
Y
First Stage Compressor
O/B
Reversing Valve
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U70124
THERMOSTAT
E
Emergency Heat
R
24 – Volt Hot
(Heat XFMR)
RC
24 – Volt Hot
(Cool XFMR)
Thermostat Installer Setup
0170-System Type-
must be set to 12
3 Heat/2 Heat Pump
Thermostat Installer Setup
0190-Changeover Valve-
must be set to 0
O/B terminal
Energized in Cooling
Thermostat Installer Setup
0200-Backup Heat Source-
must be set to 0
Heat Pump Backup Heat
Source is Electric
AUX
Auxiliary Heat
1
24VAC Humidifier
(Optional)
Part Numbers:
SAP = Legacy
159481 = 031-09157
2
COM
24 – Volt Common
R
24 – Volt Hot
W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
Y1
Single Stage Compressor
Y/Y2
Second or Full
Stage Compressor
O
Reversing Valve
Energized in Cool
X/L
Malfunction Light
HUM
Dehumidification-
Open on Humidity Rise
VARIABLE SPEED
AIR HANDLER CONTROL
G
Fan
Move the MODE
jumper to “HP”
Move HUM STAT
jumper to “YES”
if humidistat is to be used.
VARIABLE SPEED
AIR HANDLER
2
Part Numbers:
SAP = Legacy
126768 = 031-09137
18395 = 031-01996
340512 = 031-09178
1
AV
ID MODELS
SV
MV
YZE
YZH
H*5
YORKGUARD VI
CONTROL
H*8
24VAC
Electronic Air Cleaner
(Optional)
EAC(24 VAC out)
Electronic Air Cleaner
External Humidistat
(Optional)
Open on Humidity Rise
HUM OUT
(24 VAC out)
Refer to AH documentation
for W1 and W2 electric
heat staging options.
Second stage auxiliary
heat will be controlled by
the thermostat, not the
heat pump control when
wired as shown.
OD MODELS
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
3
Part Number:
S1-2HU16700124
3
361819-YIM-A-0208
Unitary Products Group
11
FIGURE 11:
Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Modulating Furnace
HP 28A
Two Stage Heat Pump – Variable Speed Modulating Furnace (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
YORKGUARD VI
CONTROL
TWO STAGE
HEAT PUMP
Bonnet Sensor
(Optional)
C
24 – Volt Common
Y1
First Stage Compressor
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U71124
*PP32U72124
THERMOSTAT
R
24 – Volt Hot
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
DHM
Dehumidistat
HM
Humidistat
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
Y1
Single Stage Compressor
VARIABLE SPEED
MODULATING
FURNACE CONTROL
G
Fan
VARIABLE SPEED
MODULATING
FURNACE
Y/Y2
Second or Full
Stage Compressor
HUM
Dehumidification-
Open on Humidity Rise
W
Modulating Heat
Change FFuel jumper
on the heat pump control
to “ON”
1
Part Numbers:
SAP = Legacy
171334 = 031-09153
2
2
Move HUMIDISTAT
jumper to “YES”
if humidistat is to be used.
Part Numbers:
SAP = Legacy
126768 = 031-09137
18395 = 031-01996
340512 = 031-09178
1
PC(8/9)
ID MODELS
FC(8/9)C
FL(8/9)C
YZE
OD MODELS
YZH
H*5
H*8
Step 1 of the Thermostat
Installer Table must be
set to Heat Pump
E2/P Switch must be in the
E2 position
Step 2 of the Thermostat
Installer Table must be
set to 2
Step 5 of Thermostat User
Configuration Menu must
be set to “ON” for
Dehumidification
24VAC Humidifier
(Optional)
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
361819-YIM-A-0208
12
Unitary Products Group
FIGURE 12:
Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Modulating Furnace
HP 28C
Two Stage Heat Pump – Variable Speed Modulating Furnace (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
YORKGUARD VI
CONTROL
TWO STAGE
HEAT PUMP
Bonnet Sensor
(Optional)
C
24 – Volt Common
R
24 – Volt Hot
Y1
Single Stage Compressor
VARIABLE SPEED
MODULATING
FURNACE CONTROL
G
Fan
VARIABLE SPEED
MODULATING
FURNACE
Y/Y2
Second or Full
Stage Compressor
HUM
Dehumidification-
Open on Humidity Rise
W
Modulating Heat
Change FFuel jumper
on the heat pump control
to “ON”
1
Part Numbers:
SAP = Legacy
171334 = 031-09153
2
2
Move HUMIDISTAT
jumper to “YES”
if humidistat is to be used.
Part Numbers:
SAP = Legacy
126768 = 031-09137
18395 = 031-01996
340512 = 031-09178
1
PC(8/9)
ID MODELS
FC(8/9)C
FL(8/9)C
YZE
OD MODELS
YZH
H*5
H*8
C
24 – Volt Common
R
24 – Volt Hot
Y1
First Stage Compressor
O
Reversing Valve
Energized in Cool
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*DN22H00124
*DP22U70124
THERMOSTAT
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
C
24 – Volt Common
Y
First Stage Compressor
O/B
Reversing Valve
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U70124
THERMOSTAT
E
Emergency Heat
R
24 – Volt Hot
(Heat XFMR)
RC
24 – Volt Hot
(Cool XFMR)
AUX
Auxiliary Heat
Step 1 of Thermostat
Installer/Configuration
Menu must be set to “HP2”
Selection of GAS/ELEC
switch on thermostat
not necessary
Thermostat Installer Setup
0170-System Type-
must be set to 12
3 Heat/2 Heat Pump
Thermostat Installer Setup
0190-Changeover Valve-
must be set to 0
O/B terminal
Energized in Cooling
Thermostat Installer Setup
0200-Backup Heat Source-
must be set to 1
Heat Pump Backup Heat
Source is Fossil Fuel
External Humidistat
(Optional)
Open on Humidity Rise
Thermostat Installer Setup
0210-External Fossil Fuel
Kit- must be set to 1
Heat Pump Control
is Controlling Heat Pump
Backup Heat
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
3
361819-YIM-A-0208
Unitary Products Group
13
SECTION VI: EVACUATION
It will be necessary to evacuate the system to 500 microns or less. If a
leak is suspected, leak test with dry nitrogen to locate the leak. Repair
the leak and test again.
To verify that the system has no leaks, simply close the valve to the vac-
uum pump suction to isolate the pump and hold the system under vac-
uum. Watch the micron gauge for a few minutes. If the micron gauge
indicates a steady and continuous rise, it’s an indication of a leak. If the
gauge shows a rise, then levels off after a few minutes and remains
fairly constant, its an indication that the system is leak free but still con-
tains moisture and may require further evacuation if the reading is
above 500 microns.
SECTION VII: SYSTEM CHARGE
The factory charge in the outdoor unit includes enough charge for the
unit, a 15 ft. line set and the smallest rated indoor coil match-up. Some
indoor coil matches may require additional charge. See tabular data
sheet provided in unit literature packet for charge requirements.
The “TOTAL SYSTEM CHARGE” must be permanently stamped on the
unit data plate.
Total system charge is determined as follows:
1.
Determine outdoor unit charge from tabular data sheet.
2.
Determine indoor coil adjustment from tabular data sheet.
3.
Calculate the line charge using the tabular data sheet if line length
is greater than15 feet.
4.
Total system charge = item 1 + item 2 + item 3.
5.
Permanently stamp the unit data plate with the total amount of
refrigerant in the system.
Use the following subcooling charging method whenever additional
refrigerant is required for the system charge. A superheat charging
method is not suitable for TXV equipped systems.
Measurement Method
If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly.
Check flare caps on service ports to be sure they are leak tight. DO
NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).
Subcooling Charging Method
For the
heating operation
, there is no accurate subcooling method for
charging the unit. If unit charging is required during heating operation,
the unit must be evacuated and charge weighed-in per the marking on
the rating plate.
For the
cooling operation
, the recommended subcooling is typically
around 10°F. This may vary greatly based on each unique system.
1.
Set the system running in the cooling mode by setting the thermo-
stat at least 6°F below the room temperature.
2.
Operate the system for a minimum of 15-20 minutes.
3.
Refer to the tabular data sheet for the recommended airflow and
verify this indoor airflow (it should be about 400 SCFM per ton).
4.
Measure the liquid refrigerant pressure P and temperature T at the
service valve.
5.
Calculate the saturated liquid temperature ST from Table 2 on the
last page of this document.
6.
Subcooling temperature TC = Saturated Temperature (ST) - Liquid
Temp (T).
Add charge if the calculated subcooling temperature TC in Step 6 is
lower than the recommended level. Remove and recover the refrigerant
if the subcooling TC is higher than the recommended level.
See rating plate for unit specific subcooling chart.
See Figure 13 to trace the flow of refrigerant through the system.
R-410A refrigerant cylinders are rose colored, and have a dip tube
which allows liquid to flow out of the cylinder in the
Upright Posi-
tion.
Always charge the system slowly with the tank in the upright
position.
Do not leave the system open to the atmosphere. Unit damage
could occur due to moisture being absorbed by the POE oil in the
system. This type of oil is highly susceptible to moisture absorp-
tion.
Refrigerant charging should only be carried out by a qualified air
conditioning contractor.
Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.
Example: The pressure P and temperature T measured at the liquid
service port is 360 Psig and 93°F. From Table 2, the saturated tem-
perature for 360 Psig is 109°. The subcooling temperature TC =
109°-93°=16°F
FIGURE 13:
Heat Pump Flow Diagram
.
TXV
(Cooling)
SHOWN IN COOLING POSITION.
COOLING CYCLE FLOW
HEATING CYCLE FLOW
INDOOR COIL
4-WAY
REVERSING
VALVE
SUCTION
ACCUMULATOR
COMPRESSOR
OUTDOOR
COIL
FIELD CONNECTED LINE
FILTER DRYER
(Solid core)
LIQUID
SENSOR
FIELD CONNECTED LINE
TXV
(Heating)
361819-YIM-A-0208
14
Unitary Products Group
SECTION VIII: SYSTEM OPERATION
For more information on the control operation, refer to “Operation
Instructions - DEMAND DEFROST CONTROL BOARD in this Booklet.
REQUIRED CONTROL SETUP
IMPORTANT: The following steps must be taken at the time of
installation to insure proper system operation.
1.
Consult system wiring diagram to determine proper thermostat
wiring for your system.
2.
If hot heat pump configuration is desired, change HOT HEAT
PUMP jumper to ON position.
3.
If installation includes a fossil fuel furnace, change FFUEL jumper
to ON position.
4.
Set low temperature cutout (LTCO), balance point (BP), switch
point (SP), and Y2 Lock jumpers as desired.
5.
Verify proper system functionality. Confirm room thermostat opera-
tion including fault code display capability.
6.
Upon completion of installation, verify that no fault codes are
stored in memory. Clear the fault code memory if necessary.
DEFROST OPERATION
The following defrost curve selection jumper positions are set from fac-
tory.
INDICATIONS OF PROPER OPERATION
Cooling
Cooling operation is the same as any conventional air conditioning unit.
1.
The outdoor fan should be running, with warm air being dis-
charged from the top of the unit.
2.
The indoor blower (furnace or air handler) will be operating, dis-
charging cool air from the ducts. Coils or other parts in the air cir-
cuit should be cleaned as often as necessary to keep the unit
clean. Use a brush, vacuum cleaner attachment, or other suitable
means.
3.
The vapor line at the outdoor unit will feel cool to the touch.
4.
The liquid line at the outdoor unit will feel warm to the touch.
Heating
Indications of proper Heating operation is as follows:
1.
The outdoor fan should be running, with cool air being discharged
from the top of the unit.
2.
The indoor blower (furnace or air handler) will be operating, dis-
charging warm air from the ducts.
3.
The vapor line at the outdoor unit will feel warm to the touch.
4.
The liquid line at the outdoor unit will feel cool to the touch.
SECTION IX: INSTRUCTING THE OWNER
Assist owner with processing warranty cards and/or online registration.
Review Owners Guide and provide a copy to the owner and guidance
on proper operation and maintenance. Instruct the owner or the opera-
tor how to start, stop and adjust temperature setting.
When applicable, instruct the owner that the compressor is equipped
with a crankcase heater to prevent the migration of refrigerant to the
compressor during the “OFF” cycle. The heater is energized only when
the unit is not running. If the main switch is disconnected for long peri-
ods of shut down, do not attempt to start the unit until 8 hours after the
switch has been connected. This will allow sufficient time for all liquid
refrigerant to be driven out of the compressor.
The installer should also instruct the owner on proper operation and
maintenance of all other system components.
MAINTENANCE
1.
Dirt should not be allowed to accumulate on the outdoor coils or
other parts in the air circuit. Clean as often as necessary to keep
the unit clean. Use a brush, vacuum cleaner attachment, or other
suitable means.
2.
The outdoor fan motor is permanently lubricated and does not
require periodic oiling.
3.
If the coil needs to be cleaned, it should be washed with Calgon
Coilclean (mix one part Coilclean to seven parts water). Allow
solution to remain on coil for 30 minutes before rinsing with clean
water. Solution should not be permitted to come in contact with
painted surfaces.
4.
Refer to the furnace or air handler instructions for filter and blower
motor maintenance.
5.
The indoor coil and drain pan should be inspected and cleaned
regularly to prevent odors and assure proper drainage.
TABLE 1:
Defrost Initiate Curves
Defrost Curve Selection
Jumper Position
1
2
3
4
Heat Pump Model
N/A
N/A
3 Ton
N/A
IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING
REPAIR, SERVICE, MAINTENANCE OR THE FINAL DIS-
POSAL OF THIS UNIT.
WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND
THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE
THE OWNER’S APPROVAL.
TABLE 2:
R-410A Saturation Properties
TEMP.
°
F
PRESSURE
PSIG
TEMP.
°
F
PRESSURE
PSIG
TEMP.
°
F
PRESSURE
PSIG
TEMP.
°
F
PRESSURE
PSIG
TEMP.
°
F
PRESSURE
PSIG
45
129.70
60
169.60
75
217.40
90
274.10
105
340.50
46
132.20
61
172.60
76
220.90
91
278.20
106
345.30
47
134.60
62
175.50
77
224.40
92
282.30
107
350.10
48
137.10
63
178.50
78
228.00
93
286.50
108
355.00
49
139.60
64
181.60
79
231.60
94
290.80
109
360.00
50
142.20
65
184.60
80
235.30
95
295.10
110
365.00
51
144.80
66
187.70
81
239.00
96
299.40
111
370.00
52
147.40
67
190.90
82
242.70
97
303.80
112
375.10
53
150.10
68
194.10
83
246.50
98
308.20
113
380.20
54
152.80
69
197.30
84
250.30
99
312.70
114
385.40
55
155.50
70
200.60
85
254.10
100
317.20
115
390.70
56
158.20
71
203.90
86
258.00
101
321.80
116
396.00
57
161.00
72
207.20
87
262.00
102
326.40
117
401.30
58
163.90
73
210.60
88
266.00
103
331.00
118
406.70
59
166.70
74
214.00
89
270.00
104
335.70
119
412.20
361819-YIM-A-0208
Unitary Products Group
15
SECTION X: WIRING DIAGRAM
FIGURE 14:
Wiring Diagram
Subject to change without notice. Printed in U.S.A.
361819-YIM-A-0208
Copyright
©
by Unitary Products Group. 2008. All rights reserved.
Supersedes: 128596-YIM-A-0505
Unitary
5005
Norman
Product
York
OK
Group
Drive
73069