The New Step

®

 Touch Thermostat

The Ideal Way to Control Your Warmfloor

Installation & 

Operation Manual

Do not use this equipment before reading this manual!

Model Number: EPI-LX-TC

Printed in the U.S.A.

Note: This manual contains important warnings 

and instructions. Please read and retain 
for reference.

© 01/2014 Step Warmfloor, Inc. All rights reserved.

The new Step Touch thermostat from Electro Plastics is

the elegant way to control your Step Warmfloor system.

Perfectly suited and designed from the ground up

to work seamlessly with all Step Systems.

Features:

•   Clean, simple two control design for ease of operation

•   Three digit auto-dimmable LED Display

•   Touch sensor controls that are maintenance free

•   Clear, totally flat acrylic surface for a clean contemporary look that works 

well with any decor

•   Elegant stainless steel perimeter housing

•   Displays in Fahrenheit or Celsius

•   Interfaces to an external temperature sensor

•   Works with Step Warmfloor, Step Snowmelt and Step Deicing systems

•   Standard colors: black and white. Custom colors available at additional cost

•   Capable of interfacing with smart home systems

•   No batteries needed. All settings are stored in permanent memory for 

instant recovery in the event of a power failure

•   Step Warmfloor logo is lit when system is heating

•  Green friendly low power design

Specifications: 

Set Range: 40º to 90ºF • 4º to 32ºC

Internal Ambient Temp Range: 0º to 99ºF, +/-1ºF • -9º to 37ºC, +/-0.5ºC  

External Sensor Temp Range: 0º to 99ºF / -9º to 37ºC 

Power: 9-24 VAC/VDC @ <10mA (without external temperature sensor)

© 2014 Electro Plastics, Inc.

 


background image

Physical Description

© 01/2014 Step Warmfloor, Inc. All rights reserved.

The New Step® Touch Electronic Thermostat is a zone control device specially designed for use with the STEP Warmfloor™ radiant heat system. 
The Step® Touch provides a pulsed output that complements the self-regulating nature of the STEP Warmfloor™ heating elements to offer the 
homeowner the highest energy efficiency while providing better zoned control over personal comfort.

Thermostat 
 

The thermostat is the operator interface for the Step Warmfloor System. 

It is designed to be flush wall mounted in a place that will be most 
representative of the zone it controls.

 

The thermostat consists of a digital display that indicates the measured 

air temperature or set temperature, touch sensitive switches for control 
of the set point, the air temperature sensor and indicators for the 
external sensor mode, snowmelt mode and logo illumination.

Regulator 

The regulator is an intelligent switch that enables/disables the line 
voltage in such a way that does not harm the transformer(s) and gently 
applies the load to the power system. It is designed to be surface 
mounted adjacent to the transformer(s) that it controls. The regulator 
consists of a printed circuit board mounted inside the power supply 
housing or in a junction box w/ heat sink. Each regulator is designed to

  

handle up to 1,500W of load.  

The thermostat and power supply are connected together using a 20 foot length of 
3 conductor shielded cable. For control of a zone with a load larger than 1,500W, up 
to 20 power supplies can be connected to one thermostat for a total controlled load 
of 30,000W.

Functional Features

Interface: 

 

 

UP/DOWN capacitive sensing proximity switches (no membrane 

switches)
 

These switches are used to modify the “Set Temperature”. 

Normally the display will show the ambient temperature, however 
when any switch is pressed, the Set Temperature is displayed for 3 
seconds and the units (F or C) digit is flashed. If a switch is pressed 
again, while the Set Temperature is displayed the Set Temperature is 
modified.
 

If both the UP/DOWN switches are held for more than 4 seconds, 

the unit will go into shutdown mode and completely turn the system 
off.  While these switches are held the display will count down, ie: “3”, 
“2”, “1”, “OFF”.  During this time all setting information is saved in 
memory and recovered  on power-up. To re-activate, the switches 
must be held down again for 4 seconds. 
 

All settings are permanently stored in flash memory (no batteries) 

so that in the case of a power failure, there will be no need to modify 
any settings. This also includes shutdown mode, ie: if you are out of 
town and the unit is in shutdown mode a power fluctuation will not 
cause the unit to re-enable.

Output:  

 

When the temperature measurement from either the ambient 

sensor or the floor sensor (depending on the mode of operation) is 
below the Set Temperature, the unit will trigger the system to 
activate and the Step logo will illuminate indicating heat is being 
called for.

Internal Temp Sense: 

 

Ambient temperature is sensed via the three vent slots on the 

front panel

External Temp Sense: 

 

The unit also provides for the sensing of temperature externally 

via the EPI-LX-TS sensor supplied. This could be necessary, if the 
thermostat is located in an area that has a falsely high temperature 
(ie: near a large piece of machinery on a factory floor) or can be used 
as a floor temperature sensor. It would also be used in the case of 
SnowMelt mode where the sensor would need to be installed in the 
concrete that is being sensed. 
 

This connection is made via a very common 6 position 4 contact 

modular connector and allows the sensor to be extended to a 
maximum distance of 50 feet. Try doing that with a platinum RTD? 
The external sensor has a small micro-controller built in and digitally 
transmits the temperature data so there is no loss in accuracy with 
distance.

Home Control Shutdown:

 

It is also possible, via the modular jack on the rear of the unit, that 

the unit can be shut down via a relay closure from an external Home 
Control system. If Pins 1 and 6 are shorted together the unit will 
shutdown. 

© 2014 Electro Plastics, Inc. 

 

Illustration 1 - Thermostat Features

External 

Sensor 

Indicator

SnowMelt 

Mode 

Engaged

Temperature 

Units

Temperature 

Display

Up

Down
Ambient 

Temperature 

Sensor

Illuminated Logo

 


background image

© 01/2014 Step Warmfloor, Inc. All rights reserved.

Installation

Interface: 

 

 

UP/DOWN capacitive sensing proximity switches (no membrane 

switches)
 

These switches are used to modify the “Set Temperature”. 

Normally the display will show the ambient temperature, however 
when any switch is pressed, the Set Temperature is displayed for 3 
seconds and the units (F or C) digit is flashed. If a switch is pressed 
again, while the Set Temperature is displayed the Set Temperature is 
modified.
 

If both the UP/DOWN switches are held for more than 4 seconds, 

the unit will go into shutdown mode and completely turn the system 
off.  While these switches are held the display will count down, ie: “3”, 
“2”, “1”, “OFF”.  During this time all setting information is saved in 
memory and recovered  on power-up. To re-activate, the switches 
must be held down again for 4 seconds. 
 

All settings are permanently stored in flash memory (no batteries) 

so that in the case of a power failure, there will be no need to modify 
any settings. This also includes shutdown mode, ie: if you are out of 
town and the unit is in shutdown mode a power fluctuation will not 
cause the unit to re-enable.

Output:  

 

When the temperature measurement from either the ambient 

sensor or the floor sensor (depending on the mode of operation) is 
below the Set Temperature, the unit will trigger the system to 
activate and the Step logo will illuminate indicating heat is being 
called for.

Internal Temp Sense: 

 

Ambient temperature is sensed via the three vent slots on the 

front panel

External Temp Sense: 

 

The unit also provides for the sensing of temperature externally 

via the EPI-LX-TS sensor supplied. This could be necessary, if the 
thermostat is located in an area that has a falsely high temperature 
(ie: near a large piece of machinery on a factory floor) or can be used 
as a floor temperature sensor. It would also be used in the case of 
SnowMelt mode where the sensor would need to be installed in the 
concrete that is being sensed. 
 

This connection is made via a very common 6 position 4 contact 

modular connector and allows the sensor to be extended to a 
maximum distance of 50 feet. Try doing that with a platinum RTD? 
The external sensor has a small micro-controller built in and digitally 
transmits the temperature data so there is no loss in accuracy with 
distance.

Home Control Shutdown:

 

It is also possible, via the modular jack on the rear of the unit, that 

the unit can be shut down via a relay closure from an external Home 
Control system. If Pins 1 and 6 are shorted together the unit will 
shutdown. 

 

The Step® Touch thermostat can be used in conjunction with all 

the EPI-LX-R power supply series and the STEP DC Controllers. Be sure 
to install the thermostat on an interior wall away from direct sun and 
drafts. Measure the distance from the power supply to the thermostat 
to identify the length of the thermostat wire. The low-voltage (24) 
thermostat is connected to the power supply using a 3-conductor 
shielded cable and can control up to 20 power supplies or 20 DC 
Controllers.
 

The process of installing the EPI-LX-TC involves preplanning of 

mounting locations and roughing in of the necessary hardware. The 
installation of the EPI-LX-TC typically occurs during new construction 
or a remodel project where access to the walls is possible for the 
rough in work. If access to the walls is not possible, as during some 
remodel projects, the EPI-LX-TC installation may require the use of 
surface mounted raceway products such as those manufactured by 
Wiremold® (www.wiremold.com).

Plan mounting Locations
 

Thermostat – Locate the thermostat approximately 60” off the 

floor in a location that is most representative of the zone that it 
controls. Do not install where exposed to direct sunlight or drafts.

 Rough In 
 

The thermostat is designed to be flush mounted on a single gang 

junction box. Install such a box at the desired mounting location.
 

Install the supplied 3-conductor shielded cable between the 

housing and the power supply. The cable can be installed in the wall 
without the use of conduit as it only carries a low voltage signal. If the 
cable is not long enough, acquire a suitable length of an equivalent 
cable sufficient to run the full length between the boxes. Do not 
splice the cable – only use a full new length. If an additional power 
supply will be connected, install the supplied 3-conductor shielded 
cable between the supplies.

Thermostat 
 

Terminate the 3-conductor shielded cable to the thermostat. Trim 

back the shield flush with the outer cable jacket and do not ground 
the drain wire at the thermostat. Only ground the drain wire at the 
regulator. Remove the face plate from the housing to expose the 
mounting holes. Push the excess cable into the box and install the 
Thermostat using the screws provided. Reinstall the face plate on to 
the housing.

Dip Switches:
 

FACEPLATE REMOVAL: The faceplate is retained via high power 

magnets. Illustration 2 shows proper technique to remove the 
faceplate and gain access to the dip switches and connections. In 
order to remove, first grasp the top edge of the acrylic faceplate with 
your first three fingers, with your thumb on the bottom edge of the 
faceplate, rotate the display away from the housing until it is free.
 

Dip switches are extremely easy to access via the magnetically 

attached front panel. No fasteners or annoying plastic clips. Electrical 
connection between the front panel and the base are made via 
gold-plated, spring-loaded contacts ensuring extremely long life. The 
4 position dip switch is located on the inside of the front panel PCB.

 

1. C/F: 

 

Simply changes the units of measurement between Fahrenheit 

and Celsius.

 

2: AUTODIM MODE: 

Many people do not like a bright LED display to be on all the time, 
especially at night. The AutoDim feature simply dims the display 
when the unit is not being modified. If a switch is pressed, the display 
is brightened and stays bright for several seconds after modifications 
have been completed.  When AutoDim mode is not enabled, the 
display is bright all the time.

 

3. EXTERNAL TEMPERATURE SENSOR: 

When this switch is enabled the unit will make decisions based on the 
temperature reading from the external sensor. The display will always 
show the temperature of the external temp sensor, however if the 
user wishes to check the ambient temperature, they can simply press 
and release both the UP/DOWN switches within 1 second and the 
ambient temperature will be displayed for several seconds after 
which it will revert to the temperature of the external sensor. If, by 
mistake, both the External Temperature Switch and the SnowMelt 
switch are activated, the SnowMelt switch is dominant and this mode 
will be enabled. Whenever the external sensor is active the dot in the 
upper left-hand corner of the display will be illuminated.

 

4. SNOWMELT MODE: 

This mode is enabled when the thermostat is being used with the 
snowmelt elements. The external temp sensor is installed in the 
concrete and the Set Temperature is adjustable between 32-41F/0-5C. 
This value is maintained in flash memory. The display will show this 
measurement and, as with external mode, when both the UP/DOWN 
switches are pressed and released within 1 second, the display will 
show the ambient temperature for a short period after which it will 
revert to the external temperature sensor. When in SnowMelt Mode, 
the snowflake logo on the front panel will glow blue.
  

Dip Switches:
 

FACEPLATE REMOVAL: The faceplate is retained via high power 

magnets. Illustration 2 shows proper technique to remove the 
faceplate and gain access to the dip switches and connections. In 
order to remove, first grasp the top edge of the acrylic faceplate with 
your first three fingers, with your thumb on the bottom edge of the 
faceplate, rotate the display away from the housing until it is free.
 

Dip switches are extremely easy to access via the magnetically 

attached front panel. No fasteners or annoying plastic clips. Electrical 
connection between the front panel and the base are made via 
gold-plated, spring-loaded contacts ensuring extremely long life. The 
4 position dip switch is located on the inside of the front panel PCB.

 

1. C/F: 

 

Simply changes the units of measurement between Fahrenheit 

and Celsius.

 

2: AUTODIM MODE: 

Many people do not like a bright LED display to be on all the time, 
especially at night. The AutoDim feature simply dims the display 
when the unit is not being modified. If a switch is pressed, the display 
is brightened and stays bright for several seconds after modifications 
have been completed.  When AutoDim mode is not enabled, the 
display is bright all the time.

 

3. EXTERNAL TEMPERATURE SENSOR: 

When this switch is enabled the unit will make decisions based on the 
temperature reading from the external sensor. The display will always 
show the temperature of the external temp sensor, however if the 
user wishes to check the ambient temperature, they can simply press 
and release both the UP/DOWN switches within 1 second and the 
ambient temperature will be displayed for several seconds after 
which it will revert to the temperature of the external sensor. If, by 
mistake, both the External Temperature Switch and the SnowMelt 
switch are activated, the SnowMelt switch is dominant and this mode 
will be enabled. Whenever the external sensor is active the dot in the 
upper left-hand corner of the display will be illuminated.

 

4. SNOWMELT MODE: 

This mode is enabled when the thermostat is being used with the 
snowmelt elements. The external temp sensor is installed in the 
concrete and the Set Temperature is adjustable between 32-41F/0-5C. 
This value is maintained in flash memory. The display will show this 
measurement and, as with external mode, when both the UP/DOWN 
switches are pressed and released within 1 second, the display will 
show the ambient temperature for a short period after which it will 
revert to the external temperature sensor. When in SnowMelt Mode, 
the snowflake logo on the front panel will glow blue.
  

© 2014 Electro Plastics, Inc. 

Illustration 2  - Faceplate Removal

 


background image

External

 

 

  3 digit auto-dimmable LED display (ie: 70 ‘F)

 

(Front) 

  UP touch switch (not membrane switch)

 

 

  DOWN touch switch (not membrane switch)

 

External 

  3 position terminal block (AC/DC, TRG, COM)

 

(Rear) 

  6 position 6 contact modular jack

 

  

 

Internal 

  Fahrenheit/Celsius switch

 

(dip switch) 

  AutoDim switch

 

 

  External Temperature Sensor Mode switch

 

 

  Snowmelt Mode Switch

 

  

Specifications:

Internal Ambient temp Range:  

  0-99˚F/-9-37˚C

External Sensor temp Range:  

  0-99˚F/-9-37˚C

Internal Sensor Mode Set Temp Range:     40-90˚F, 4-32˚C 
External Sensor Mode Set Temp Range:     40-90˚F, 4-32˚C
Snow Melt Mode Set Temp Range:  

  32-41˚F, 0-5˚C

Power:  

 

  9-24 VAC/VDC @ 12mA max

© 01/2014 Step Warmfloor, Inc. All rights reserved.

 

Operation

Physical Dimensions

Normal Operation 

 

The Step Touch digital display indicates the measured room temperature during normal operation.

 

Set-point change 

 

The set-point is modified by using the “Up” and “Down” switches located on the thermostat faceplate. The first press of 

the switches will cause the digital display intensity to increase and to display the present set-point.  Subsequent press-

ing of the switches will allow you to change the set temperature to the desired setting. After a few seconds of inactivity, 

the digital display will dim back to its original intensity and will return to displaying the measured room temperature.

 

Normal Operation 

 

The Step Touch digital display indicates the measured room temperature during normal operation.

 

Set-point change 

 

The set-point is modified by using the “Up” and “Down” switches located on the thermostat faceplate. The first press of 

the switches will cause the digital display intensity to increase and to display the present set-point.  Subsequent press-

ing of the switches will allow you to change the set temperature to the desired setting. After a few seconds of inactivity, 

the digital display will dim back to its original intensity and will return to displaying the measured room temperature.

 

Mechanical Features

2.75”

4.50”

4.60”

2.85”

1.08”

1.89”

0.49”

3X      0.187”

0.56”

2.41”

1.02”

1.43”

  

STEP T

OUCH THERMOST

AT

M

ADE IN USA

EXTERNAL TEMP SENSE

 AC 

TRG 

COM

 (DC) 

 

(GND)