Full Text Searchable PDF User Manual
User, Installation and Servicing
Instructions
WARNING: THIS APPLIANCE MUST BE EARTHED
CE
£2.50 When supplied separately.
VP Classic Range Users, Installation and Servicing Instructions Issue 2 April 2009
The VPC Range
Dear Customer
This is to certify that this appliance is guaranteed for two years including parts and
labour from the date of original commissioning.
The heat exchanger, where fitted, is guaranteed (parts only) for a further eight years,
chargeable on a sliding scale basis, price relative to age.
To make a claim
In the first instance you must contact your appliance supplier, or installer and
provide:-
1. The appliance type and serial number.
2. The original commissioning documentation.
3. As much detail as possible on the fault.
Your supplier, or installer will then contact Powrmatic to make a guarantee claim
on your behalf.
Conditions of Guarantee
1. The appliance must have been installed by a competent recognised installer,
and in accordance with the manufacturers instructions, building regulations and
local regulations.
2. The appliance has been professionally commissioned.
3. The appliance has been maintained on a yearly basis by a competent servicing
company.
4. The appliance has been used in accordance with the manufacturers instructions.
5. The correct specification fuel has been used
6. No unauthorised repairs or modifications have been made.
7. Powrmatic General Conditions of Sale have been observed.
8. Except for the obligation of Powrmatic Ltd to perform warranty repairs during
the guarantee period, Powrmatic will not be liable in respect of any claim for
direct or indirect consequential losses, including loss of profits or increased costs
arising from loss of use of the appliance, or any event arising there from.
Exclusions
1. Gaskets and fan belts are not included in the guarantee
Important: This certificate must
be kept with the appliance
Certificate of Guarantee
Powrmatic Ltd, Hort Bridge, Ilminster, Somerset, TA19 9PS
tel: 01460 53535 fax: 01460 52341
email: guarantee@powrmatic.co.uk web: www.powrmatic.co.uk
1. First Start Sequence
Follow the sequence below before lighting the heater(s) for the
first time.
a) Ensure that the gas supply to the unit is turned OFF.
b) Turn on the electrical supply to the heater and programme
the controls in accordance with their instructions.
Note:The igntion sequence may start during this process
but the heater will not light, as the gas supply is turned off,
and the internal burner control will go to lockout. The lockout
indicator on the external control will be illuminated.
c) Ensure that the controls are not calling for heat i.e. the
thermostat is at minimum or the clock control is set to an
OFF period or the function switch is set to OFF.
d) Check that all warm air delivery outlets are open.
e) If necessary reset the internal control from lockout by
pressing the reset button on the external control for 3 seconds.
f) Check that the overheat reset button has not operated.
g) Ensure that the Summer/Winter switch is in the Winter
position.
h) Turn ON the gas supply.
2. Lighting the Air Heater
NOTE:
On initial lighting of the heater(s), it may take some time to
purge the internal pipework of air. If it is not possible to light
the heater after several attempts contact the local service
company.
1. Set the controls to call for heat and the ignition start up
sequence will commence. The internal exhaust fan will run.
When sufficient combustion airflow is proved by the air pressure
switch the ignition spark will be generated and the main gas
valves energized. The burners will then light.
2. If the burner fails to light the control box will attempt two
further ignition attempts before going to lockout. The lockout
light on the MC100 or Powrtrol will be illuminated (Note: If
an integral MC100 or Powrtrol are not used a remote lockout
indicator/reset will be fitted). To restart the ignition sequence
depress the reset button on the control for at least 3 seconds.
If the unit will not light after four or five attempts then shut
down the unit and call in a service engineer.
3. To Shut Down the Air Heater
3.1 For Short Periods:Turn the room thermostat to the OFF
or lowest setting.
3.2 For Long Periods:Complete step 3.1 above. Wait for 5
minutes and then turn OFF the
electrical supply at the isolator.
4. Description of Operation
Important:
All heaters must be controlled by the fitted external
controls and not by use of the main switch in the electrical
supply to the heater.
4.1 Standard Units
The ignition sequence will commence each time that the external
controls e.g. Timeclock, room thermostat etc. call for heat.
Approximately 15 - 30seconds after the main burners light the
heater fan will be automatically started. When the external
controls are satisfied the main burners will be turned off and
approximately 2 - 3 minutes later the heater fan will be
automatically stopped.
4.2 High / Lo & Modulating Units
When the main burners are alight the heat output will be
controlled either to high fire or low fire or, in the case of
modulating units, to any point between high and low fire;
depending on the requirements of the space being heated and
the control system.
4.3 Summer / Winter Modes
The integral MC100 or Powrtrol controls, and certain types of
external controls, will provide for two modes of operation i.e.
Summer:The heater fan alone will run at the dictate of the
external controls to provide air movement.
Winter:The heater will operate normally.
5. Maintenance
Regular servicing is essential to maintain efficient, reliable and
safe operation of the heater. Users are strongly recommended
to have the heater serviced by a qualified person at least annually
and preferably at the end of the heating season.
6. IMPORTANT
Free access must be maintained to and around the heater for
servicing purposes and the air supply to the heater must not be
restricted in any way. Combustible materials must not be stored
adjacent to the heater.
If at any time a gas leak is suspected turn OFF the gas supply
- DO NOT USE A NAKED FLAME - and contact the local
gas undertaking immediately.
All Powrmatic heaters use gas and electricity to power them,
they may also contain moving parts such as pulley belts. It
would be hazardous to tamper with or attempt to service unless
you are a competent person in the field of Gas and Electrical
work.
If you have any safety questions reference the servicing and
installation of any of our heaters please do not hesitate to contact
our head office for expert advice.
Your safety is paramount to us.
Gas Safety (Installation & Use) (Amendment) Regulations
It is law that all gas appliances are installed, adjusted and, if
necessary, converted by qualified persons* in accordance with
the current issue of the above regulations. Failure to install
appliances correctly can lead to prosecution. It is in your own
interests and that of safety to ensure that the law is complied
with.
* e.g. Corgi Registered
Users Instructions
CONTENTS
Section
Title
Page
1.
Introduction
1
2.
Technical Data
2
3.
General Requirements
4
4.
Installation
5
5.
Air Distribution System
6
6.
Commissioning & Testing
7
7.
Servicing
8
8.
Fault Finding Flow Chart
10
9.
Wiring Diagrams
11
10.
Short List of Parts
11
Tables
Title
Page
1.
Dimensions
2
2.
Specifications
3
3.1
Injector Sizes & Burner Pressures
Natural Gas - Group H - G20
3
4.
Electrical Loadings 1ph
4
Figure
Title
Page
1.
Minimum Clearance Distances
5
2a.
Exhaust only System - Horizontal
7
2b.
Exhaust only System - Vertical
7
3a.
Individual System - Horizontal
7
3b.
Individual System - Vertical
7
5.
Controls Layout
8
6.
Honeywell VR425AB1007
9
7.
Honeywell VR4605AB1027
9
8.
High/Lo and Modulating Heads
9
9.
Ignition Electrode Spark Gap
10
10.
Thermostat Fan/Limit - Honeywell L4064N
10
1. INTRODUCTION
The VPC range are highly efficient gas fired, fanned circulation
floor standing air heaters that cover heat outputs of 30kW to
130kW. The units have a single closed flue system that can be
either vertical or horizontal and feature a single burner assembly
which, as standard is ON/OFF but can also be supplied in
High/Low or Modulating formats. High/Low or Modulating
formats give a turn down facility of approximately 2:1. The
heaters are certified for use on Natural Gas, Group H - G20,
and Propane - G31 only.
Appliance Categories are Cat II2H3P (GB, IE).
The heaters intended primarily for heating commercial or
industrial premises. They must not be used where the atmosphere
inside the premises could be contaminated e.g. Dust, oil mist
etc. or in areas classified as hazardous as defined in BS 5345:
Part 2. They are not suitable for siting externally.
VPC heaters have a centrifugal fan assembly fitted at the base
of the heater to circulate the air being heated past the folded
tube heat exchanger.
Heaters are fitted as standard with one set of atmospheric inshot
burners having a fully automatic control for ignition, flame
sensing, gas supply control and safety functions and an internal
exhaust fan, as well as the main air fan(s) and limit thermostat.
Gas Safety (Installation & Use) Regulations
It is law that all gas appliances are installed, adjusted and, if
necessary, converted by qualified persons* in accordance with
the current issue of the above regulations. Failure to install
appliances correctly can lead to prosecution. It is in your own
interests and that of safety to ensure that the law is complied
with.
* e.g. Corgi Registered
1
2
2. TECHNICAL DATA
DØ
Table 1. Dimensions
Unit
A
B
C
D
E
F
VPC 30
VPC 52
VPC 110
VPC 80
VPC 130
189
1108
1412 750
1676
2043
100
130
1046
F
Gas entry
E
F
Gas entry
DØ
G
238
1767
2132
2209
1049
132
134
286
340
A
A
E
VPC 30UF shown
B
G
C
Front View
Sidet View
G
C
B
Front View
Sidet View
VPC 130UF shown
Side Duct Spigot
658(h) x 658(w)
658(h) x 960(w)
658(h) x 1315(w)
Top Duct Spigot
648(h) x 658(l)
648(h) x 960(l)
648(h) x 1315(l)
Alternative flue &
combustion air
positions
Alternative flue &
combustion air
positions
Inlet pressure
20mbar
Table 3.1
Injector Sizes & Burner Pressures Natural Gas - Group H - G20 Net CV (Hi) = 34.02MJ/m³
Inlet
INJECTORS
High Fire
Low Fire
Pressure
Burner
Gas Rate
Burner
Gas Rate
20mb
Pressure
Pressure
MODEL
No.
Size Markedmbar
m³/h
mbar
m³/h
mm
VPC 30
6
1.94
194
13.8
3.45
4.6
2.02
VPC 52
12
1.94
194
10.4
5.98
3.0
3.22
VPC 80
12
2.54
254
9.0
9.19
2.1
4.44
VPC 110
10
3.00
300
11.5
12.64
3.2
6.50
VPC 130
12
3.00
300
11.8
15.52
3.6
8.26
3
Table 2 - Specifications
MODEL
INPUT
(Nett)
OUTPUT INPUT
(Nett)
OUTPUT
kg
kW
kW
m³/s
kW
VPC 30
32.6
30.0
18.0
15.7
0.8664
VPC 52
56.5
52.0
30.4
26.1
1.5884
VPC 80
87.0
80.0
42.0
36.8
2.3372
VPC 110
119.5 110.0
61.5
53.3
2.9568
VPC 130
141.3
130.0
78.1
69.0
3.6288
0.370
178
0.55
248
1.8
305
2 x 0.55
362
2 x 1.10
410
HIGH FIRE
LOW FIRE
AIR
VOLUME
FAN
MOTOR
WEIGHT
c/w Heads
NOISE
LEVEL
dB(A) @ 3m
60.0
68.0
76.0
72.0
74.0
Available
static presssure
@ Std. Airflow
Pa
Table 4
Electrical Loadings 1ph
MODEL
VPC 30
VPC 52
3.6
7.4
3.3
8.7
5.4
VPC 80
32.8 15.0
VPC 130
22.0
7.8
NOMINAL
MOTOR
R.P.M.
PLATE
AMPS
(A)
START
AMPS
(A)
RUN
AMPS
(A)
18.5
10.3
5.8
5.8 +3.0
13.6
900
900
950
1400 + 900
4.7 x 2
750 x 2
ELECTRICAL
SUPPLY
230V 1N
230V 1N
230V 1N
400V 3N
POWER
INPUT
(kW)
0.80
1.10
3.0
2.37
3.145
400V 3N
VPC 110
150
200
225
150
200
Inlet pressure
37mbar
Table 3.2
Injector Sizes & Burner Pressures Propane - G31 Net CV (Hi) = 88.00MJ/m³
Inlet
INJECTORS
High Fire
Low Fire
Pressure
Burner
Gas Rate
Burner
Gas Rate
20mb
Pressure
Pressure
MODEL
No.
Size Markedmbar
m³/h
mbar
m³/h
mm
VPC 30
6
1.36
136
21.7
1.33
7.0
0.74
VPC 52
12
1.25
125
27.0
2.31
8.0
1.24
VPC 80
12
1.55
155
24.1
3.55
6.0
1.72
VPC 110
10
1.94
194
26.5
4.89
7.0
2.51
VPC 130
12
1.94
194
25.0
5.78
7.9
3.19
3. General Requirements
3.1 Related Documents
The installation of the air heater(s) must be in accordance with
the rules in force and the relevant requirements of the Gas Safety
Regulations, Building Regulations and the I.E.E. Regulations
for Electrical Installations.
It should also be in accordance with any relevant requirements
of the local gas region, local authority and fire authority and
the relevant recommendations of the following documents.
Institution of Gas Engineers & Managers
IGE/UP/1 (Ed.2)
Strength and tightness testing and purging
of industrial and commercial gas installations.
IGE/UP/1A
Soundness testing and direct purging of small low
pressure industrial and commercial gas installations.
IGE/UP/2
Gas installation pipework, boosters and compressors
on industrial and commercial premises.
IGE/UP/10
Installation gas appliances in industrial and
commercial premises.
British Standards Code of Practice
BS 5588
Fire precautions in the design and construction of
buildings.
Part 2 :1985 Code of Practice for Shops
Part 3 : 1983 Code of Practice for Office Buildings
BS 6230:
1991 Installation of Gas Fired Forced Convection
Air Heaters for Commercial and Industrial Space Heating.
Those appliances having a gross input rating not exceeding
60kW viz. VPC30, and installed so as to take their combustion
air from within the building must be installed in accordance
with the relevant recommendations of the following document.
BS 5440
Flues and Air Supply for gas appliances of rated input
not exceeding 60kW (1st and 2nd family gases), Part 2 - Air
Supply
3.2 Location
The location chosen for the air heater must permit:
- the provision of a satisfactory flue system and an adequate air
supply.
- adequate space for servicing and air circulation around the air
heater.
The heater(s) must not be installed in conditions for which it
is not specifically designed e.g. where the atmosphere is corrosive
or salty. Standard units are not suitable for outdoor location.
Where the location of the air heater is such that it might suffer
external mechanical damage e.g. from overhead cranes, fork
lift trucks, it must be suitably protected.
VPC units are designed to operate within an ambient temperature
range of -10 to 25°C.
3.3 Gas Supply
3.3.1 Service Pipes
The local gas undertaking should be consulted at the installation
planning stage in order to establish the availability of an adequate
supply of gas. An existing service pipe must not be used without
prior consultation with the local gas undertaking.
3.3.2 Meters
A gas meter is connected to the service pipe by the local gas
undertaking or a local gas undertaking contractor. An existing
meter should be checked, preferably by the gas undertaking, to
ensure that the meter is adequate to deal with the total rate of
gas supply required.
3.3.3. Installation Pipes
Installation pipes should be fitted in accordance with
IGE/UP/2. Pipework from the meter to the air heater must be
of adequate size. Do not use pipes of a smaller size than the
inlet gas connection of the heater. The complete installation
must be tested for soundness as described in the above Code.
3.3.4. Boosted Supplies
Where it is necessary to employ a gas pressure booster the
controls must include a low pressure cut off switch at the booster
inlet. The local gas undertaking must be consulted before a gas
pressure booster is fitted.
3.4 Flue System
VPC units must be used with a closed flue system and have an
internal exhaust fan, mounted downstream of the heat exchanger,
to both assist the evacuation of the products of combustion and
to draw in air for combustion.
The flue should terminate in a freely exposed position and must
be so situated as to prevent the products of combustion entering
any opening in a building in such concentration as to be
prejudicial to health or a nuisance.
3.5 Combustion Air Supply
Where VPC units are to be installed within the space being
heated and take the air from combustion from that space then
for buildings having a design air change rate of less than 0.5/h,
and the heated space has a volume less than 4.7 m³/kW of total
rated heat input grilles shall be provided at low level as follows:-
(1)
for heaters of heat input less than 60 kW, the
total minimum free area shall not be less than 4.5 cm²
per kilowatt of rated heat input.
(2)
for heaters of heat input 60 kW or more, the total
minimum free area shall not be less than 270cm² plus
2.25 cm² per kilowatt in excess of 60 kW rated heat
input.
All air vents should have negligible resistance and must not be
sited in any position where they are likely to be easily blocked
or flooded or in any position adjacent to an extraction system
which is carrying flammable vapour.
Grilles or louvres should be so designed that high velocity air
streams do not occur within the plant room.
The basic minimum effective area requirements of the air vents
are as follows:
(a) Low Level (inlet)
(1) for heaters of total rated heat input less than 60kW:
9cm² per kilowatt of rated heat input.
(2) for heaters of total rated heat input 60kW or more:
540 cm² plus 4.5 cm² per kilowatt in excess of 60kW
total rated input.
(b) High Level (outlet)
(1) for heaters of total rated heat input less than 60kW:
4.5cm² per kilowatt of rated heat input.
(2) for heaters of total rated heat input 60kW or more:
270 cm² plus 2.25 cm² per kilowatt in excess of
60kW total rated input.
3.6 Air Distribution System
VPC units used in buildings having a low heat loss i.e. where
single units are required to cover a large floor area, and in
buildings with high roof or ceiling heights Calecon thermal
economiser units should be fitted to ensure even heat distribution
and minimise stratification.
Care should be taken to avoid impeding the air throw with
racking, partitions, plant or machinery etc.
Care must be taken to ensure that return-air intakes are kept
clear of sources of smells and fumes, and where there is any
possibility of pollution of the air by dust, shavings etc.,
precautions must be taken to prevent contamination.
If necessary suitable barrier rails should be provided to prevent
any combustible material being placed within 900mm of the
warm air outlets.
4
5
4. Installation of Air Heater(s)
4.1 General
Before installation, check that the local distribution conditions,
nature of gas and pressure, and adjustment of the appliance are
compatible.
The air heater must be installed in accordance with the rules in
force and the relevant requirements of any fire regulations or
insurance company's requirements appertaining to the area in
which the heater is located, particularly where special risks are
involved such as areas where petrol vehicles are housed, where
cellulose spraying is carried out, in wood working departments
etc.
The following minimum clearances for installation and servicing
must be observed.
RHS Clearance (looking at front of heater)
0.5m
LHS Clearance (looking at front of heater)
0.5m
Top of the heater to ceiling
1.0m
Rear of heater to nearest wall
0.5m
Front of heater to nearest wall
1.0m
Any combustible material adjacent to the air heater and the flue
system must be so placed or shielded as to ensure that its
temperature does not exceed 65 °C.
IMPORTANT:
1.
Heaters shall not be installed in:-
a) Those parts of spaces within buildings that have been classified
as hazardous areas as defined in BS 5345 : Part 2.
b) Where there is a foreseeable risk of flammable particles or
gases or corrosion inducing gases or vapours being drawn into
either the heated air stream or the air for combustion.
c) In areas subjected to significant negative pressures due to
extract systems.
3.7 Electrical Supply
Wiring external to the air heater must be installed in accordance
with the I.E.E. Regulations for Electrical Installations and any
local regulations which apply. Wiring should be completed in
flexible conduit.
All standard heaters are supplied by 230V - 1N, 50Hz or 400V
- 3N, 50Hz depending on the size. The method of connection
to the main electricity supply must:-
- facilitate the complete electrical isolation of the unit(s)
- be in a readily accessible position adjacent to the unit(s)
- serve only the unit(s)
- have a contact separation of at least 3mm in all poles. See the
accompanying wiring diagram for the heater electrical
connections.
4.2 Fitting the Air Heater
If necessary consideration should be given to mounting the
heater on resilient pads, or equivalent, to minimise transfer of
noise and vibration to the structure of the building.
Floor mounted heaters must be installed on a level
noncombustible surface.
Heaters mounted at high level must be supported on a purpose
designed platform or framework that is suspended from vertical
drop rods, chains or straps or mounted on specifically designed
cantilever brackets from a non-combustible wall. The method
of installation support must be capable of adequately supporting
the weight of the unit
(See Table 2, Page 3)
and any ancillary
equipment. Before installing the heater the existing structure
must be inspected to ensure it is suitable. All supports should
be protected against the effects of rust or corrosion.
.Any combustible material adjacent to the air heater and the flu
system must be so placed or shielded as to ensure that its
temperature does not exceed 65 °C.
If the method of mounting allows for any movement of the
heater it is essential that all gas, duct, and electrical connections
to the heater are made with flexible connections to maintain
continuity of connection.
4.3 Flue/Combustion Air Duct System
All models are supplied as standard with a top flue outlet and
combustion air inlet.
4.3.1.1. Conversion to Side Flue Outlet
1.Remove the two blanking plates from the flue /combustion
a i r o p e n i n g s a t t h e s i d e o f t h e u n i t .
2. Disconnect the flexible pipe from the exhaust spigot.
3. Remove the four screws securing the exhaust spigot and
reposition the spigot to the side of the heater using the top
position. Refit the flexible pipe.
4. Remove the four screws securing the combustion air spigot
and reposition spigot to the side of the heater.
5. Refit the blanking plates to cover the holes in the top of the
heater.
4.3.1.2 Internal Combustion Air
1. If ducted combustion air is not required
(see Section 3.5)
fit
the mesh inlet plate (supplied loose) behind the unused
combustion air inlet hole.
4.3.2. General Requirements
See Figures 2a to 3b for the different types of flue installation.
In all cases the flue outlet socket must be connected via the
provided flue system to outside air. The maximum permitted
length of flue system is 6m, or 12m if the flue outlet only is
used. If an offset is required two sets of 45° bends may be used
each set being equivalent to 0.5m of flue length. The minimum
flue length (end of flue terminal to side or top of heater) shall
not be less than 1.3m.
All outer joints must be finished with the provided locking
bands. A smear of silicon grease to the inside of sockets will
assist in fitting components together. All flue and combustion
air ducts must be supported independently of the air heater. The
flue or flue/combustion air terminal must not be installed so as
to be less than:
- 300mm below an opening e.g. window, air brick etc.
- 200mm below eaves or gutter.
- 300mm from an internal or external corner.
- 1200mm from a surface facing the terminal.
- 1500mm vertically from another terminal on the same wall.
- 300mm horizontally from another terminal on the same wall.
- 2000mm from ground level.
1.0m
1.0m
0.5m
0.5m
0.5m
Fig 1 Minimum clearance distances
6
5. Air Distribution System
5.1 General
VPC heaters, if required, can be used with duct work either to
more precisely define the point of air delivery, and /or provide
ducted return air or ducted fresh air inlet.The system should be
checked to ensure that the installation work has been carried
out in accordance with the design requirements.
Particular attention should be given to the correct arrangement
of delivery ducts and registers, return air ducts and grills and
general adequacy of return air paths.
Ensure that the total duct system resistance does not exceed the
available air pressure of the equipment supplied refer to Table
2
(Page 3)
. If the duct system resistance is less than the available
air pressure of the equipment supplied additional resistance
must be introduced e.g. by adjustment of duct outlet nozzles
and balancing of the duct system. Conversely if the duct system
resistance is greater than the available air pressure of the heater
supplied the system resistance must be reduced.
5.2 Room Thermostat Siting
If a separate room thermostat is used it should be fitted at a
point which will be generally representative of the heated area
as far as temperature is concerned. Draughty areas, areas
subjected to direct heat e.g. from the sun, and areas where the
air movement is relatively stagnant e.g. in recesses, are all
positions to be avoided for siting the thermostat.
The thermostat should be mounted about 1.5m from the floor.
Any room thermostat, frost thermostat, time clock etc. must be
suitable for switching 230V, 5A and must be of the 'snap action'
type to minimise contact bounce.
For electrical connections of external controls see the
accompanying wiring diagram.
4.3.3 Installation of Flue System
Note:
A terminal guard, as supplied by Powrmatic Ltd, must be
fitted to horizontal flue terminals.
4.3.3.1 Horizontal System - Side Outlet
1. Locate the position of the flue terminal, allowing for a slight
gradient running down from the heater to the terminal of 2° -
3° and cut a hole in the building wall to suit.
2. Fit the flue terminal, securing via the wall plate and weather
with silicon sealant or similar.
3. Fit the twin to concentric adaptor to the terminal section and
extend the flue and combustion air ducts to the heater using
straight lengths. Fit an adjustable length prior to the unit, to
facilitate flue disconnection for servicing. Extend the adjustable
lengths to make the final connection to the appropriate heater
inlet/outlet spigots.
4. Ensure that internal silicon sealing rings are in place and that
all tubes are pushed fully home. Secure concentric lengths with
the locking bands provided.
4.3.3.2 Vertical System - Top Outlet
1. Locate the position of the flue terminal cut a hole in the roof
to suit.
2. Fit the flashing and the flue terminal so that the lower edge
of the outer case is over the top of the flashing. Weather with
silicon sealant or equivalent.
Fit a condensate drain lenth into the flue socket on the heater
and an equivalent straight length onto the combustion air socket.
3. Fit the twin to concentric adaptor to the terminal section and
then extend down to the heater using straight lengths. Fit
adjustable lengths as the final connection pieces, to facilitate
flue disconnection for servicing. Extend the adjustable lengths
to make the final connection but do not exceed the maximum
extended length so as to maintain joint integrity.
Extend the drainage offtake of the condensate drainage length
to a suitable gully or drain.
4. Ensure that internal silicon sealing rings are in place and that
all tubes are pushed fully home. Secure concentric lengths with
the locking bands provided.
4.3.3.3 Internal Combustion Air Systems
1. Complete the run of flue sections from the terminal spigot
to the flue outlet socket of the heater generally as described in
4.3.3.1 and 4.3.3.2, ensuring that the internal silicon sealing
rings are in place.
2. Ensure that the mesh inlet plate has been fitted (see 4.3.1.2).
4.4 Gas Connection
To facilitate servicing a servicing valve and downstream union
must be fitted at the inlet to the air heater. The gas supply to
the air heater must be completed in solid pipe work and be
adequately supported. Heaters suspended by drop rods, straps
or chains must have a flexible connection as the final link
between the gas supply pipe work and the heater. Sufficient
slack must be left in the connection to take account of normal
movement of the heater.
Warning
When completing the final gas connection to the heater do not
place undue strain on the gas pipe work of the heater.
4.5 Electrical Connections
All units are fully prewired and only require final connections
for the incoming mains supply and fitment of the MC100. The
control is shipped inside the heater burner compartment. Pass
the connection cable through the hole in the front door, fit the
control onto the outside of the door and connent the cable to
the pcb inside the heater. If a MC100 or Powrtrol are not being
used, complete the control circuit (230V) via a room thermostat,
time clock etc.
All units must be earthed. The electrical supply must be run to
a point adjacent to the heater and be suitably terminated to
provide an isolation point that will prevent remote activation
of the unit during servicing. Reference must be made to Table
4
(Page 3)
to ascertain the electrical loading of the unit(s) being
installed so that cables of adequate cross-sectional area are used
for the electrical installation. The length of the conductors
between the cord anchorage and the terminals must be such that
the current carrying conductors become taut before the earth
conductor if the cable or cord slips out of the cord anchorage.
All external controls must be of an approved type.
See the wiring diagram accompanying these instructions.
Notes for all systems.
i)
Final overall length of adjustable disconnection piece must be between 360 - 415mm.
ii)
45° offsets may be used if required. Each set is equivalent to 0.5m of flue length.
iii) Where VPC heaters are used in clean environments it is permissible to take the combustion air directly from the heated space. The supplied
mesh intake plate, must be fitted to the combustion air inlet on the rear of the heater.
Fig 2a Exhaust only system - horizontal
Fig 3a Individual system - horizontal
7
Fig 3b Individual system - vertical
6m maximum
Terminal
Lengths
Adjustable
lengths
Single to twin
adaptor
Flashing
Flue socket
Combustion air
socket
Condensate drain
length
Fig 2b Exhaust only system - vertical
12m maximum
Terminal
Lengths
Adjustable
length
Flashing
F l u e
socket
Combustion air entry
(fitted with inlet grille)
Condensate drain
length
Terminal
Lengths
Adjustable
length
F l u e
outlet
Combustion air entry
(fitted with inlet grille)
12m maximum
Terminal
Lengths
Adjustable
length
Single to twin
adaptor
Flue socket
Combustion
air duct
6m maximum
Combustion
air socket
8
6. Commissioning & Testing
6.1 Electrical Installation
Checks to ensure electrical safety must be carried out by a
qualified person.
6.2 Gas Installation
The whole of the gas installation, including the meter, should
be inspected and tested for soundness and purged in accordance
with the recommendations of IGE/UP/1 (Edition 2) or
IGE/UP/2A as appropriate.
6.3 First Start Sequence
Follow the sequence below before lighting the heater(s) for the
first time.
a) Ensure that the gas supply to the unit is turned OFF.
b) Turn on the electrical supply to the heater and set up the
controls in accordance with their instructions.
Note:The igntion sequence may start during this process
but the heater will not light, as the gas supply is turned off,
and the internal burner control will go to lockout. The lockout
indicator on the external control will be illuminated.
c) Ensure that the controls are not calling for heat i.e. the
thermostat is at minimum or the clock control is set to an
OFF period or the function switch is set to OFF.
d) Check that all warm air delivery outlets are open.
e) If necessary reset the internal control from lockout by
pressing the reset button on the external control for 3 seconds.
f) Check that the overheat reset button has not operated.
g) Ensure that the Summer/Winter switch is in the Winter
position.
h) Turn ON the gas supply.
6.4 Lighting the Air Heater
NOTES:
1. On initial lighting of the heater(s), it may take some time to
purge the internal pipework of air.
IMPORTANT:
The internal pipework of the appliance has been tested for
soundness before leaving the factory. After establishing the
main burners test round the gas inlet connection using a leak
detection fluid e.g. soap solution.
6.4.1 All Models
1. Adjust the controls to call for heat and the ignition sequence
will commence. After a delay of approximately 45 seconds the
ignition spark will be generated and the main gas valves
energized. The burners will then light followed in 15 - 30seconds
by the main air fan.
2. If the burners fail to light the control box will attempt two
further ignition tries before going to lockout and the lockout
light on the internal pcb will be illuminated. To restart the
ignition sequence depress the reset button adjacent to the lockout
light for at least 3 seconds.
3.
SHUT OFF
Set the clock control to OFF or set the room thermostat to MIN.
6.5 Adjustments
6.5.1 Burner Gas Pressure
This is set for the required heat input before despatch. In the
case of Hi/Lo and Modulating units both high and low pressures
are set. Pressures should be checked in the following manner.
Fig 5 Controls Layout
Main Gas Valve
Burner Manifold
(Cover removed
for clarity)
Exhaust Fan
Rectification
Electrode
Main control panel
Exhaust Fan airflow
proving pressure switch
Fan/Limit Thermostat
Flue outlet and
combustion air inlet
(alternative positions on top of unit)
Ignition
Electrode
(Behind gas
valve)
9
Fig 8 High/Low and Modulating Head
A
Low pressure
setting screw
B
Valve stem
C
Valve body
D1
Locking spring
(Modulating Head)
D2
Locking spring
(Hi/Low Head)
E
Locknut
F
Spring
D
2
A
F
B
E
D1
C
6.6.1.1 Standard Units
1. Set external controls to ensure that the main burner is off.
Open the access door. Connect a pressure gauge to the burner
pressure test point on the multifunctional control.
2. Set external controls so as to turn on the main burner. Compare
the measured burner gas pressure to that stated on the data plate.
If necessary adjust the burner gas pressure by turning the
regulator screw anticlockwise to decrease the pressure, or
clockwise to increase the pressure.
3. In addition it is advisable to check the gas rate using the gas
meter dial pointer. Ensure that no other appliances supplied
through the meter are in operation.
If required, after checking or setting the burner pressures, the
CO2 content in the flue gases can be checked by sampling in
the first section of flue fitted to the flue outlet of the unit.
Nominal CO2 values are 8-9%.
5. Turn off the main burner as in 6.5.1. and disconnect the
pressure gauge and replace the sealing screw. Turn on the main
burner as above and test for gas soundness around pressure test
joint using a leak detection fluid e.g. soap solution.
6.6.1.2 High/Lo and Modulating Heads
1. Set external controls to ensure that the main burner is off.
Open the access panel. Connect a pressure gauge to the burner
pressure test point on the multifunctional control.
2. Set external controls so as to turn on the main burner and
maintain high fire. Compare the measured burner gas pressure
to that stated on the data plate. In addition it is advisable to
check the gas rate using the gas meter dial pointer. Ensure that
no other appliances supplied through the meter are in operation.
3. Repeat 2 above with external controls set to maintain low
fire.
4. If it is necessary to adjust the high pressure setting then
proceed from step i). If it is only necessary to adjust the low
fire pressure setting proceed from step vii).
i) Set external controls to turn main burner OFF.
ii) Pull back the clip D retaining the actuator coil to its mounting
stem and remove the coil.
iii) Set external controls to turn main burner ON.
iv) Screw adjustment screw A fully clockwise.
v) Release the M13 locknut E that secures the actuator stem B
into the mfc governor pack and turn the actuator stem to set the
HIGH FIRE pressure
(clockwise to increase pressure).
vi) Tighten the locknut without further turning the actuator
stem.
vii) Unscrew adjustment screw A to set the LOW FIRE pressure
(anti clockwise to decrease pressure.
viii) Set external controls to turn burner OFF and replace valve
body C onto the valve stem ensuring that it clips into position.
5. Turn off the main burner as in 6.5.1 disconnect the pressure
gauge and replace the sealing screw. Turn on the main burner
as in 6.5.1 and test for gas soundness around pressure test joint
using a leak detection fluid. Replace access panel.
6.6.2 Air Heater Controls
1. Close the gas service tap and ensure that the gas valve is
heard to close within 1 second and that the lockout light is
illuminated. Note that the heater will attempt three reignitions
before going to lockout. Open the gas service tap and reset the
unit from lockout.
2. Check that the room thermostat and all automatic controls
are operating satisfactorily.
6.7 Handing over the Air Heater
Hand the Users Instructions to the user or purchaser for retention
and instruct in the efficient and safe operation of the air heater
and associated controls.
Adjust the automatic controls to those values required by the
User.
Finally, advise the user or purchaser that, for continued efficient
and safe operation of the air heater, it is important that servicing
is carried out annually.
In the event that the premises are not yet occupied turn off the
gas and electricity supplies and leave instructional literature
adjacent to gas meter.
7. Servicing
WARNING:
Always switch off and disconnect electricity
supply and close the gas service valve before carrying out any
servicing work or replacement of failed components.
NOTE:
If a suspended air heater is to be serviced do not lean ladders
against the heater. Ensure that an access tower or equivalent is
used.
7.1 General
Full maintenance should be undertaken not less than once per
year by a qualified person. After any servicing work has been
complete or any component replaced the air heater(s) must be
fully commissioned and tested for soundness as described in
Section 6.
7.2 Main Burner Assembly Removal
1. Ensure that the gas service valve is turned OFF and then
unscrew the union nut situated immediately down stream of it.
2. Disconnect the spark and rectification leads from the pcb
and remove the electrical plug connections from the top of the
gas control valve assembly.
3. If required remove the manifold by first removing the front
heat shield and then removing the four screws securing the
manifold to the burner assembly.
4. Remove the two screws that secure the top of the burner
assembly to the bulkhead and lift out burner assembly
5. Using a stiff brush, not a wire brush, brush the burners to
Governor adjustment screw
under cover cap
(Honeywell VR4605A
B1027)
Governor adjustment screw
under cover cap
(Honeywell
VR425AB1007)
Fig 7
Fig 6
10
dislodge accumulated deposits. Inspect the burners both internally
and externally to ensure that they are clean. Examine the injectors
and if damaged or deteriorated, replace with new ones of the
correct size and marking. If deemed necessary, clean the injectors.
Do not broach out with wire.
6. Reassemble the injectors, manifold and burners in reverse
order to that above.
7.3 Ignition and Rectification Electrodes
1. Inspect the electrodes, making sure that they are in a sound
and clean condition. In particular check that the ignition electrode
is clean and undamaged. Check that the spark gap is 2.5mm.
7.4 Heat Exchanger
Whilst the main burner assemblies are removed from the unit
check that the primary sections that the burners fire into are
clean.
7.5 Main Fan Assembly
1. Inspect the fan blades to see that they are not damaged and
that there is no excessive build up of deposits that could give
rise to an imbalance.
7.6 Replacement of Faulty Components
7.6.1 Multifunctional Control
1. Remove the electrical plug connections from the top of the
gas control valve assembly
2. Release the flanged connections at the inlet and outlet of the
multifunctional control and remove the multifunctional control.
3. Reconnect the new valve in the reverse order to that above
ensuring that the valve is correctly orientated. Renew the sealing
'O' rings if necessary.
7.6.2 Burners
1. Remove the burner assembly as previously described in
Section 7.2.
2. Remove the end plates of the burner assembly and the central
burner support plate.
3. Exchange burners as required and reassemble components
in reverse order.
4. Re-commission the appliance as described in Section 6.
7.6.3 Electrode Assemblies
1. Disconnect the electrode leads from the pcb terminal as
appropriate.
2. Remove the screw securing the electrode assembly to the
burner assembly side plate and withdraw the assembly.
3. Fit replacement and reassemble in reverse order. Check that
the spark gap is 2.5mm (See Fig. 9).
7.6.4 Limit Thermostat -
Honeywell L4064N
1. Release the single screw securing the fan and limit thermostat
cover and remove cover by pulling forward.
2. Release wiring from clamp terminals by pushing a small
screwdriver into the clamp release holes adjacent to the clamps.
3. Remove the 2 screws securing the thermostat to the heater
panel and withdraw thermostat.
4. Reassemble new unit in reverse order referring to the heater
wiring diagram to ensure correct wiring location.
Important:
A replacement fan/limit thermostat will have a
brass link between the bottom fan terminal and the bottom limit
terminal (situated in the slot between the two terminals). This
MUST
be removed, by breaking the link off using a pair of thin
nose pliers, before the replacement thermostat is installed.
NB. Ensure that the thermostats are set correctly before fitment
Limit Thermostat settings:-
VPC 30, 52
90°C
VPC 80
80°C
VPC 110, 130
120°C
Note:
The new L4064N may be supplied with the limit
temperature mechanically limited to less than the setting required.
To release the mechanical limit push a pointed object into the
small hole at the top of the dial. At the same time prevent the
dial from rotating and push the limit temperature adjuster around
to the required setting.
7.6.5 Exhaust Fan
1. Disconnect the flexible pipe from the fan outlet.
2. Disconnect fan electrical connections from the terminals on the pcb.
3. Remove the fan and fan mounting plate from the bulkhead
(4 screws).
4. Fit replacement exhaust fan, using new gaskets, and reassemble
in reverse order.
7.6.6 Air Pressure Switch
1. Disconnect electrical connections.
2. Pull off the sensing tube from the air pressure switch.
3. Remove the screws fixing the air pressure switch and remove
switch.
4. Fit replacement in reverse order refitting the sensing tube to
the negative (- or L) tapping on the pressure switch.
7.6.7 Printed Circuit Board (pcb)
1. Disconnect all electrical connections.
2. Release the through hole clips securing the pcb and remove
pcb.
3. Fit replacement in reverse order.
7.6.8 Main Air Fan(s)
1. Remove the lower side panels.
2. Disconnect the fan motor electrical lead from the controls.
3. Remove the screws securing the fan to the fan shroud and
slide fan out. Note that the fans on the VPC110 and 135 are
removed through the rear of the heater.
4. Fit replacement in reverse order.
2.5mm
Fig 9 Ignition Electrode Spark Gap
C
A
U
T
I
O
N
DO NOT
ROT
AT
E - HOLD
DIAL
WHEN SETTING POINTERS
20 40 60 8
0
10
0
12
0
FAN L
IM
IT
OFF ON
O
FF
C°
Limit Setpoint
Adjustment
Fan Circuit
Limit Circuit
Limit Reset
Fan ON
Override
Set Point Dial
Brass Link Location
Mechanical Limiter
Release Point
Mechanical limiter
Fan OFF Setpoint
Adjustment
Limit Circuit
Fan Circuit
Fan ON Setpoint
Adjustment
Fig 10 Thermostat Fan / Limit - Honeywell L4064N
11
8. Fault Finding Flow Chart
Gas & Electrical
supplies present at heater
Yes
No
Turn supplies on
Check fuses/connections
Lock out light on
after 3 secs.
Exhaust fan runs
Faulty gas valve.
Check/replace
resistor on PCB
between gas valve
2 live & neutral
230V at Heat terminal on PCB
Check control circuit (Time clock/thermostats) calling for heat
No
Yes
Voltage at limit stat 1 on PCB
Check Fuse 1
Ok
Faulty PCB
No
Voltage at limit stat 2 on PCB
Check limit stats, reset manual stat. Check connections
No
Yes
Yes
Ok
230V to air pressure
switch common
No
Faulty PCB
Yes
230V to air pressure
switch N.O.
No
230V to exhaust
fan
Pressure switch sensing
pressure. Adjust set
point/replace
Replace exhaust
fan
Yes
Yes
230V to air pressure
switch N.O.
No
Yes
Check pressure sensing tube. Adjust pressure switch set point.
Change pressure switch
Yes
Yes
Yes
Gas valve opens
230V to gas valve
Faulty PCB
No
No
Ignition sparks
Check/replace rectification probe. Faulty PCB
No
Yes
Yes
Faulty gas valve
Burners light
Check gas pressures. Replace gas valve
No
Check spark
probe/lead.
Faulty PCB
Burners remain
alight
3 ignition attempts then goes to lock out.
No
Main fan runs
230V at main
fan motor
Check connections. Check contactor
Reset overload. Faulty PCB
No
No
Replace motor or fan/motor assembly
Yes
Yes
Heater working correctly
Exhaust fan runs
Check fuse 2
Replace
No
Failed
START
Yes
Failed
Replace
12
ITEM
USAGE
PART #
MFC - Honeywell VR4605AB1027
30-80
145035204
MFC - Honeywell VR425AB1007
110, 130
141378715
Ignition Electrode (small)
30-80
142423002
Ignition Electrode (large)
110, 130
142423004
Rectification Electrode
30- 130
142423003
Burner - Bray P51 AB 19001
30-80
142400240
Burner - Bray P51 AB 19002
110, 130
142400241
10. Short List of Parts
Only originally specified parts may be fitted as service replacements.
Please refer to Powrmatic Ltd for any parts not detailed in the listing below.
Hi/Lo Governor Head - Anglo Nordic MD20003
30-130 -/HL
142466410
Modulating Governor Head - Anglo Nordic MD1003/MD
30-130 -/MOD
142466421
Amplifier board - Johnsons PIB-24
30-130 -/MOD
142400304
Exhaust Fan - Sifan WFFB 0223-006
30, 52
140210499
Exhaust Fan - Torin 077445
80-130
140201505
Dungs LGW 3A2
30, 52
146522174
Dungs LGW 10A2
80-130
142961107
Contactor - Danfoss CI 12
All
143000610
Main PCB
All
142403610/3
9. Wiring Diagram
See the wiring diagram supplied with the heater
Every effort is made to ensure accuracy at time of going to press. However as part of our policy of continual product improvement, we reserve the right to alter specifications without prior notice.
HEATING DIVISION
Hort Bridge
Ilminster, Somerset TA19 9PS
Tel: 01460 53535 Fax: 01460 52341
BSI Registered Firm
FM 414
Ind. & Comm. Air Heaters;
Air Moving Equipment;
Natural Smoke & Heat
Ventilators;
Powered Supply & Extract
Fans & Systems.
ISO 9001