SCU 800 
d-LIST Control Unit 

The   sensor   control   unit   SCU   800   is   the   central 
supervisory element for the d-LIST-system. It provides 
up to two d-LIST sensor cables with power, performs 
the cyclic addressing of the connected sensors every 
10   seconds,   acquires   the   temperature   values 
measured by each sensor and evaluates the data with 
reference to various criteria.
A fire alarm is generated if either a given maximum 
threshold is exceeded, or if an increase in temperature 
takes   place   within   a   certain   time   (differential 
evaluation). The two thresholds (set-points) can be set 
individually for each of the attached sensor cables.

The measurement resolution of 0,1° gives the system a high sensitivity. The tried and tested algorithms used in 
the evaluation eliminate false alarms due to natural temperature variations.
Alarms are indicated by LEDs on the front-panel and via floating contacts to a fire terminal station (fire control  
panel), host computers or other transmission systems. Hereby, alarms generated by the two sensor cables are 
signalled individually.
Resetting takes place via an external signal from the fire terminal station or by pressing the front-panel mounted  
reset button.
The serial RS-232 interface can be used for programming and setting of system parameters.  LISTEC

®

  GmbH 

offers the terminal software LISTterm 8 for this purpose.
For the visualisation of the system status, message- and temperature-lists, as well as a graphic display of the  
temperature and alarm data, LISTgraph II and the Data Management Unit DMU 600 is available.
A LIST®controller can be used to connect and control several SCU 800 from a central point via a RS-485  
interface.

1/2

60V041-06/ 02.12.13

 


background image

General:

Collective display (LED's) for

Fire cable A

Fire cable B

Fault

Operation

Temperature measurement

Data transmission

Alarm criteria

Alarming due to the exceeding of an absolute- or a 
differential-threshold (set-point). All thresholds are 
individually settable for each sensor cable. 
For both alarm criteria a pre-alarm can be set in the 
range between 10 to 90% of the alarm thresholds. 

Fault recognition

Sensor cable faults, such as the malfunctioning of a 
sensor or a cable break, are recognised and 
indicated within one measuring cycle, generally 
within 10 seconds. Faults in the control unit are 
registered in the internal message list and are 
signalled immediately.

Interface

RS-232 Serial-interface for programming 
parameters and interrogation of system data.
Optionally a RS-485 interface. 

Connections

All connections take place inside the unit via 
terminals.
The RS-232 interface, 9 pin D-Sub female, is 
accessible once the unit is opened.

System specifications:

Number of measuring points

Max. 99 sensors per cable connection

Sensor cable length

Max. overall length of the sensor cable, including 
connection cables is 250 m.
The sensor cable may consist of separate cable 
pieces

Delivery extent:

CD with data sheet, operation manual, description 
of commands and system messages, installation 
guidelines

Serie 800

SCU800/3    Item number: G00231

SCU800/16       Item number: G00233

Continuous operating temperature: 

-10°C .. +60°C

Dimensions:

260 x 150 x 90 mm

Power supply:

21 – 29 V

DC

Housing material:

aluminium

Power consumption:

21 – 29 V

DC

Weight:

1,9 kg

Weight:

2,3 kg

Power consumption: (normal use)

1,9 W

Power consumption: (normal use)

2,7 W

Outputs:

Floating change-over contacts with space for user defined supervisory 
resistors: 
Fire alarm

2 relays (1 per cable)

Fault alarm

1 relay (fail safe)

Outputs:

Floating change-over contacts with space for user defined supervisory 
resistors: 
Fire alarm

16 zonal relays

Fault alarm

1 relay (fail safe)

Switching voltage: 

48 V

DC

 / 32 V

AC 

max.

Switching current:

  250 mA max. (ohmsche Last)

Input:  

5 V

DC

 reset input, galvanically isolated

2/2