Rhein-Nadel Automation GmbH 

            1 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Operating Instructions 

for the Control Units 

for Vibratory Drives 

 

Type ESR 2000

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

BA 

Rhein-Nadel Automation GmbH

  

 


background image

Rhein-Nadel Automation GmbH 

            2 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 
 

Table of contents 

 
Chapt........................................................................................................................ 

 

 

Page 

 

Technical datas...................................................................................................  

 

 

Safety notes................................................................................................... 

 

 

Commissioning instructions ............................................................................... 

 

 
4  

Operation 

 

 9 

 

Dimensional drawing..................................................................................... 

 

16 

 

Connection diagram....................................................................................... 

 

17 

 
 
 
 
 

 

Declaration of conformity 

as defined by  

Low voltage directive 2014/35/EU 

and EMC directive 2014/30/EU 

 

Herewith we declare that the product complies with the following provisions:  
 

Low voltage directive 2014/35/EU 
EMC directive 2014/30/EU 

applied harmonized standards: 

DIN EN 60204 T1 
EN 61439-1 

remarks: 
 
Rhein-Nadel-Automation 
-------------------------------- 
Managing Director 
Jack Grevenstein 

 

 
 
 
 
 

 


background image

Rhein-Nadel Automation GmbH 

            3 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 

1.1  Performance Characteristics 

 
This compact control unit has been designed to operate a bowl or linear feeder. 
The unit has the following performance characteristics: 

a power regulator for vibratory drive unit with variable output frequency, load current max. 6A 

-

 

two sensor amplifiers with independently adjustable time levels (on/off). 

 

24V DC remote control input. 

two relay outputs and two optocouplers for status messages and further links. 

-

 

a membrane keyboard for setting and editing the operating values (parameters) in the setting menus. 

 

plug connections for 

bowl  or linear feeder 

sensors 

communication 

double-pole mains power switch 

 

1.2 

EC Conformity

 

 

The control device corresponds to the following regulations: 

Low voltage directive 2014/35/EU

 

EMC directive 2014/30/EU 

 

Applied harmonized standards:

 

DIN EN 60204 T1

 

EN 61439-1 

 
1.3 

Technical Data 

 

 

Mains voltage: 

230 Volt AC, 50/60 Hz, +20 / -15%  
110 Volt AC, 50/60 Hz, +10 / -10% 

Output voltage: 

0 ... 208 V

eff  

/ 230 VAC  ;   0 ... 98V

eff

 / 110VAC

 

Load current channel 1: 

6 A

eff 

Minimum load current: 

80 mA 

Output frequency 

30 to 140 Hertz 

Internal fuse: 

F1 = 10A  

Soft start time, soft stop time 

0 ... 5 sec., can be selected separately 

External setpoint: 

0 ... 10V DC 

Sensor inputs: 

Remote control input: 

24V DC (10-24 VDC) 

Sensor power supply: 

24V DC, max. 60 mA (per sensor input) 

Sensor delay ON: 

0 ... 60 sec. 

Sensor delay OFF: 

0 ... 60 sec. 

Outputs: 

2 relays / 2 potential-free change-over contacts 

Status output (optocoupler): 

max. 30V DC 10mA, 2 voltage-fed open contact 

Relay contacts: 

max. 6A 250V AC 

Operating temperature: 

0 ... 50° C 

Type of protection: 

IP 54 

 
1.4 

Accessoires 

 
Label 

Denomination 

Type 

Manufacteur  Supplier 

RNA-Mat-code 

XS1 

Connector 

 

Harting 

 

XS3 

Coupler connector, 5-poles, straight 

09 0113 70 05 

Binder 

EVG 

35051144 

XS3 

Coupler connector, 5-poles, angular 

99 0113 75 05 

Binder 

EVG 

35002546 

XS4 

Coupler connector, 7-poles, straight 

09 0126 70 07 

Binder 

EVG 

35051153 

XS4 

Coupler connector, 7-poles, angular 

99 0126 75 07 

Binder 

EVG 

35002545 

 
 
 

 


background image

Rhein-Nadel Automation GmbH 

            4 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

Safety Instructions

 

 
It  is  always  necessary  to  read  and  understand  the  safety  instructions.  This  ensures  that  valuable  material  is  not 
damaged and injuries are avoided.

 

Steps  must  be  taken  to  ensure  that  all  persons  working  with  this  control unit are familiar with the safety regulations 
and observe them. 
The  device  described  in  this  manual  is  a  control  unit  for  operating  RNA  bowl  feeders  and  linear  feeders.  The  limit 
values specified in the technical data must be observed.

 

 

 

      

 

 

 

Note! 

This hand indicates tips on operation of the control unit. 

 
 
 
 

 

 

Attention! 

This warning triangle indicates safety instructions. Failure to heed this warning can lead to severe 
injuries or death! 

 
 
 
 
 
 
 

 

Work  on  electrical  equipment  of the machine/plant may be carried out only by a trained electrician or 
by  untrained  persons  under  the  leadership  and  supervision  of  a  trained electrician in accordance with 
the regulations for electrical engineering! 
 
All safety and danger signs on the machine/plant must be observed! 
 
The electrical equipment of a machine/plant must be inspected and checked regularly. Defects such as 
loose connections or damaged cables must be remedied immediately! 

 
 
 
 

 
 

Before commencing operation, make sure that the earthing line (power earth, PE) is intact and installed 
at the connecting point. Only test instruments approved for this purpose may be used for checking the 
safety grounding conductor. 

 

Commissioning Instructions 

 
 
 
 
 
 

Before connecting up to the mains and switching on the control unit, it is essential to check the following 
points: 

  Is the control unit in proper working condition and closed with all screws? 

  Are the connector locks clicked in/screwed secure? 

  Are all cables and glands intact? 

  Is PROPER INTENDED USAGE ensured? 

  Does the mains voltage specification on the control unit agree with the local mains voltage? 

  Does the mains frequency specification on the vibratory drive agree with the local mains? 

  Is the correct operating mode set on the control unit?  (See "Operating Mode" section) 

 

 

 
Operation  of  the  control  unit  may  be  commenced  only  when  all  questions  asked  above  can  be  answered 
unambiguously with YES. 
 
 
 
 
 
 

Before  you  start  operation  after  repair  work  has  been  carried  out  or  control  units/vibrating  drives  have 
been  exchanged,  set  the  output  on  the  control  unit  to  minimum  before  switching  on.    Check  that  the 
system is working properly when you increase the output. 

 

 
 
 

Before opening the control unit you have to wait approx 5 min after disconnecting from the main., so that 
the charge can be unloaded to a safe voltage. 

 
 

 


background image

Rhein-Nadel Automation GmbH 

            5 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

3.1 

OPERATING MODE 

 
To  avoid  mechanical  and/or  electrical  damage  occurring  to  the  ESR  2000  control  or  connected  equipment,  the 
parameters listed in the tables below must be strictly adhered to. If you cannot find your particular type of drive unit 
listed in the tables then contact RNA AUTOMATION for advice. 
 
 
 
 
 

 

To  make  shure  that  the  drive  unit  will  run  smooth  and  stabel,  it  is  necessary  to  use  use  a  good 
balanced bowl. 
Please refer also to the manuals of the drive units, to see how the springs have to be adjusted. 
 

 

Table 1 

Bowl Feeder 

max. current 

max. magnet 

Frequency 

Colour of 

Type of Drive 

A

eff

 

gap 

mm

 

range 

Magnet 

 

 

 

 

 

SRC - N 160 - 2 

0,6 

0,5 

90...120 Hz 

Black 

SRC - N 200 - 2 

1,2 

0,5 

90...120 Hz 

black 

SRC - B 200 - 2 

1,2 

0,5 

90...120 Hz 

black 

SRC - N 250 - 2 

2,6 

1,2 

90...120 Hz 

black 

SRC - B 250 - 2 

2,8 

1,2 

90...120 Hz 

black 

SRC - N 400 - 1 

3,8 

2,8 

45...60 Hz 

red 

SRC - N 400 - 2 

4,3 

1,2 

90...120 Hz 

black 

SRHL 400 - 1 

5,7 

2,8 

45...60 Hz 

red 

SRHL 400 - 2 

5,3 

1,5 

90...120 Hz 

black 

SRC - N 630 - 1 

2,8 

45...60 Hz 

red 

 

 

 

 

 

 

Table 2 

Linear Feeder 

max. current 

max. magnet 

Frequency 

Colour of 

Type of Drive 

A

eff

 

gap 

mm

 

range 

Magnet 

SLL 175 

0,07 

0,8 

90…120 Hz 

black 

SLL 400 

0,6 

90...120 Hz 

black 

SLL 800 

1,4 

45...60 Hz 

red 

SLL 804  <1600 

1,4 

45...60 Hz 

red 

SLL 804  

1600 

2,8 

45...60 Hz 

red 

SLF 1000 

2,6 

2,5 

45...60 Hz 

red 

SLF 1500 

 

 

45…60 Hz 

red 

GL 01 

0,6 

1,0 

90...120 Hz 

black 

GL 1 

1,1 

1,2 

90...120 Hz 

black 

SLK - N 6 

1,4 

2,5 

45...60 Hz 

red 

SLK - N 6 G 

1,4 

2,5 

45...60 Hz 

red 

 
For easy differentiation (recognition of frequency ranges) RNA magnet cables are colour coded as follows: 
 
Cable Colour 

Netfrequency 

Variable Frequency 

 

Black 

50/(60) Hz 

45...60 Hz 

Grey 

100/(120) Hz 

90...120 Hz 

 
 
 

 

 

WARNING: 

To  avoid  serious  mechanical  damage  to  the  feeder  unit,  the  maximum  magnet  gap  and 
maximum current level MUST NOT be exceeded. 
 

3.1.1  First Running 

 

 

 

RNA  can  supply  an  adapter  for  running  with  easy  plug-in  between  controller  and  drive  unit.  The 
adapter  included  a  measuring  unit  for  load  current  and  coil  voltage  with  a  disconnecting  switch. 
Type ESZ 01 

 


background image

Rhein-Nadel Automation GmbH 

            6 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 

Please note that all parameters of the controller are tuned up to the bowl feeder if supplied as a package 
with an ESR 2000 unit and in parameter 143 User 0.3 stored. All settings are stored and retrievable. 

 
 
 
 
 
 

 

 
Reconfigurations,  exchange  of  controllers  or  mechanical  alterations  may  cause  damages  to 
springs,  vibrating  plate,  tooling  or  transfer  devices,  when  putting  the  feeder  improperly  into 
operation 

 

3.1.2  Initial Set Up 

Procedure:

 

1.

  Check  the  feeder  type  against  the  ones  shown  in  Table  1  and  2  for  correct  magnet gap settings, correct current 

settings and the frequency range.

  

2.  Connect the ESR2000 control without feeder to the mains supply and switch on.  

3.  Do not connect the feeder unit to the ESR2000 at this stage. 

4.  Select Code 001: 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Set code 

 

 Code C001

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

4

.  

Set

 

Amplitude to 50 % :

 

 Set Amplitude 

KANAL l
KANAL 2

CODE

 

 

 

0 - 100 % 

 

 

5

Set the frequency. Refer to table 1 or 2 for the drive unit

 

Frequency 

KANAL l
KANAL 2

CODE

 

 

 

 
45 - 120 

 

6. Save settings:

 

Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

7. Switch off the controller 

8. Connect the feeder to the controller 

9. Switch on the controller 

 

     

The drive unit must run now! 

 

10.  Select again Code 001 

 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Set code 

 

 Code C001

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

11.  Set

 

Amplitude to 90 % : 

 Set Amplitude 

 

 

KANAL l  
KANAL 2  

CODE 

 

 

 

0 - 100 % 

 

 

12.  Reduce the frequency until the correct speed and vibration is achieved. 

Operating Frequency 

KANAL l
KANAL 2

CODE

 

 

 

 
45 - 120 

 

 

13.  Check the current load is below the maximum level indicated in Table 1 and 2! 

        For easy running and to determine the load current, RNA can supply a plug adapter ESZ 01 

14.  Save your settings 

Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

With Code C210 you can reset to factory settings or restoring the stored user parameters 

 


background image

Rhein-Nadel Automation GmbH 

            7 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 
 
 
 
 

 
Failure  to  heed  above  mentioned  warnings  can  be  lead  to  destroy  the  feeding  equipment  or  parts 
thereof. In this case all waranty claimes cease to exist. 
 

 
After the first adjustment is succesfull, you can set the sensor inputs and the soft run or stopping time. 
 

3.2 

Sensor Inputs and Sensor Links

 

 
The control unit has two built-in sensor inputs. They can be used for checking the back pressure, the level, for cycle 
control and other monitoring functions. The following basic rules apply:

 

 
Sensor input 1 acts on channel 1, in case nothing else has been programmed in menu C006.Sensor input 2 has been 
provided for additional functions. See sensor links. The sensor inputs can only be evaluated when they are activated. 
See the connecting diagram for the sensor connections (XS3 plug connection).

 

 

 

 
 

 

 

Fig.: Connecting diagram for direct sensors 
 

 


background image

Rhein-Nadel Automation GmbH 

            8 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 
 
 
 

 

+

 

-

 

A

 

XS 3.2 /

 

XS 3 /

 

XS 3.1 /

 

 

Termination of a sensor and a contact by adapter.

 

Housing

 

Y - Cable as a distribution

 

 

Fig.: Connecting diagram for sensors on 2-way   
        distributor

 

XS 3.2 /

 

XS 3 /

 

XS 3.1 /

 

 

 

Amplifierless photocell with externall preresistor 1.8 kOhms, 0.25W

 

resistor soldered into plug.

 

Housing

 

Y - Cable as distrubution

 

 

 

Fig.:  

Connecting diagram for photocell without  

 

amplifier on the 2-way distributor

 

 

3.3 

Status Outputs and Relays 

 
The  status  outputs  are  used  for  remote  diagnostics  of  the  control  unit  operating  mode  or  for  linking  several  control 
units together. They are unassigned NPN-doped transistor routes and are potential-free.

 

The  transistor  route  is  always  connected  at  the 

STANDBY

  status  output  when  the  control  unit  is  connected  to  the 

mains and switched on with the mains power switch. 
The 

ON  ACTION

  status  output  requires  the  same  conditions  as    STANDBY.  Channel  1  must  also  be  active  as  the 

transistor will block if it is set to BACK PRESSURE, OFF or STOP. The status outlet and the remote control should 
be wired via the XS4 plug connection.

 

The two relays have different functions. K1 works as a status relay parallel to the 

ON ACTION

 back pressure output. 

K2  is  either  used  for  the  delayed  switch-off  of  blow-off  air  or  for  a  cycle  control  function  for  one  of  the  two  sensor 
channels.

 

The  connections  and  the  cable  inlets  are  on  the  right-hand  side  of  the  control  unit.  The  terminal  strip  is  behind  the 
control unit panel.

 

 

 


background image

Rhein-Nadel Automation GmbH 

            9 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 

4.  

Operation 

 

4.1  

General 

 

 

 
 
 

Control unit plug connections

 

 

Mains power 
switch

 

The control unit is isolated from the mains with a double-pole switch. 

XS 3

 

Plug connector for sensors 

Channel 1

 

Plug connector for bowl feeder or linear feeder ( < 10A) 

XS 4

 

Plug connector for optocoupler outputs and remote control input 

 

 

The control unit display (membrane keyboard)

 

 

 

On/off 
This key switches all connected devices off. "OFF" will appear in the display. The 
control unit is still ready for operation. 

 

Cursor up and cursor down 
Use these keys to page through the control unit menu or to set parameters.  

 

Enter 
Use this key to confirm the parameters entered with the cursor. 

 

Decimal point in display 
If the decimal point is not flashing, you cannot make an entry. 

 

 
 
If the decimal point is flashing, you can make an entry. 

 
 

Cursor down

 

Return

 

ON/ OFF

 

Cursor up

 

Main power 
switch 

Channel 1 

XS 3 

XS 4 

 


background image

Rhein-Nadel Automation GmbH 

            10 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 
 

4.2 

Switching on the Control Unit  

 
Switch on the control unit with the mains power switch. The main menu will appear in the display showing the last 
setpoint set in channel 1 (Bowl feeder or linear feeder feed rate).

 

 

     

KANAL l
KANAL 2

CODE

 

 
The following displays may also appear depending on the circuit state of the unit. 
 

 

KANAL l
KANAL 2

CODE

 

 

The remote control has been activated but is currently not available on the unit. 

KANAL l
KANAL 2

CODE

 

 

The unit has been switched off with the upper left-hand key on the membrane keyboard, 
all functions are blocked. 

KANAL l
KANAL 2

CODE

 

 

The back pressure monitoring sensor has been assigned thus switching off channel 1 
(Bowl feeder). 

 

4.3 

Main Menu/Setting and Displaying Setpoints for Channel 1 

Display of setpoint or the channel 1 
output (Bowl feeder) 
Alternatively: STOP, OFF or BACK 
PRESSURE

 

                   (see above)

 

KANAL l
KANAL 2

CODE

 

 

 

 

No entries possible 

 

 

Enter code to change or make 
required settings.

 

KANAL l
KANAL 2

CODE

 

 

 

 

Enter code. 

See section 4.4 for 
description of code. 

 

 
 

Setpoint preset  
(Bowl feeder or linear feeder)

 

KANAL l
KANAL 2

CODE

 

 

 

 

Entry in %; return to 
display mode to store 

 

 

From these three basic displays you can page through the main menu using the cursor keys (UP/DOWN). Press the 
ENTER key in the main menu to activate a menu item for setting or adjustment. The decimal point will flash once you 
have pressed the ENTER key. Changes can now be made using the cursor keys (UP/DOWN). Confirm the entries by 
pressing the ENTER key again. The decimal point will no longer flash. You can scroll further through the menu using 
the cursor keys. This procedure is also used in the code menus described below.

 

 
All  displays  shown  in  the  following  section  represent  the  factory  settings.  If  the  actual  display  on  the  control  unit 
differs, the factory setting has been changed in the individual codes for a specific application.

 

 
4.4 

Description of the Individual Codes for Programming the Control Unit 

 

KANAL l
KANAL 2

CODE

 

 

Settings for channel 1 

The following functions can be set or limited for channel 1 in this submenu: 
- vibration amplitude              - signal direction of the remote control 
- remote control                     - soft start time and soft stop time 

KANAL l
KANAL 2

CODE

 

 

Lock setpoint 

This submenu allows the setpoints (oscillation amplitude) to be blocked in the main menu. The 
setpoints for channel 1 can no longer be changed in the main menu. This prevents the output 
values being accidentally changed. Changes can only be made using code C001. 

KANAL l
KANAL 2

CODE

 

Setting sensor input 1 

Sensor input 1 is activated in this submenu. The following functions can also be set.

 

- invert input signal direction        - time before switch-on  

 


background image

Rhein-Nadel Automation GmbH 

            11 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 

- time before switch-off  

KANAL l
KANAL 2

CODE

 

 

Setting sensor input 2 

Sensor input 2 is activated in this submenu. The following functions can also be set.

 

- invert input signal direction        - time before switch-on  
- time before switch-off  

KANAL l
KANAL 2

CODE

 

 

Selecting the sensor links 

The sensors activated with codes C004 and C005 can be linked to each other in this submenu.  

KANAL l
KANAL 2

CODE

 

 

Setting the cycle control system 

Set the sensor input to be monitored and how the control will react when there is a fault.  

KANAL l
KANAL 2

CODE

 

 

Display status 

This submenu is used to check the set vibration frequency and the sensor inputs and reset of 
error signals 

KANAL l
KANAL 2

CODE

 

 

Programmed application examples 

Call memorized settings P1-10 based on application examples. 
 

(ask for our catalogue fax 0241/5109-219 or by Internet www.rna.de)

  

 

KANAL l
KANAL 2

CODE

 

 

Output preset with an external voltage. 0-10V or potentiometer 

 

KANAL l
KANAL 2

CODE

 

 

Store parameters 

If the values (user parameters) previously set in the different submenus are to be stored, call 
this submenu. 

KANAL l
KANAL 2

CODE

 

 

Block all setting functions 

This code blocks all entry options on the control unit. The values can no longer be changed. 
The menu can now only be enabled using this code. 

KANAL l
KANAL 2

CODE

 

 

Reset parameters 

This submenu allows the user to reset the control unit to the factory settings. If user 
parameters have been stored, the control unit can also be set to these settings. 

 

4.5 

Application-specific Changes to the Factory Settings 

 
4.5.1  Code C001 for power output 

Aim: 

Setting and limiting the vibration amplitude, the remote control, the soft start time and the soft stop time. 

 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Set code 

 

 Code C001

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

 Set vibration amplitude

 

KANAL l
KANAL 2

CODE

 

 

 

0 - 100 % 

 

 Limit vibration amplitude 

 For RNA-Feeder with 100V/200 V  
 Magnets 90% 
 

KANAL l
KANAL 2

CODE

 

 

 

50 - 100 % (*) 

 

 Remote control

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

 Remote control signal direction

 

KANAL l
KANAL 2

CODE

 

 

 

I = start = 24V DC 
0 = stop = 24V DC 

 

 Soft start time

 

KANAL l
KANAL 2

CODE

 

 

 

0 - 5 sec. 

 

 Soft stop time

 

KANAL l
KANAL 2

CODE

 

 

 

0 - 5 sec. 

 

 


background image

Rhein-Nadel Automation GmbH 

            12 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

Operating Frequency 

(see 3.1 Operating Mode) 

KANAL l
KANAL 2

CODE

 

 

 

 
35 - 140 

 

 Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

 

4.5.2  Code C003 Lock Setpoint 

Aim: 

Blocking the setpoints in the main menu. The values can no longer be changed directly. Changes can only be  

         made using code C001. 
 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Set code 

 

 Code C003

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

 Setpoint (vibration amplitude)

 

KANAL l
KANAL 2

CODE

 

 

 

1 = can be set 
0 = entry blocked 

 

 Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

 

4.5.3  Code C004 Sensor Input 1 and Code C005 Sensor Input 2 

Aim: 

Activating and setting the sensor inputs 

 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Set code 

 

 Code C004

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

 Sensor 1 input

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

 Invert input signal direction

 

KANAL l
KANAL 2

CODE

 

 

 

I = start = 24V DC 
0 = stop = 24V DC 

 

Sensor state delay 
FREE, time before switch on. 

 

KANAL l
KANAL 2

CODE

 

 

 

0 -60 sec. 

 

Sensor state delay 
ASSIGNED, time before switch-off. 

 

KANAL l
KANAL 2

CODE

 

 

 

0 -60 sec. 

 

Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

   Code 

C005

 is used for sensor input 2 in the same way. 

 

4.5.4  Code C006 Sensor Links 

Aim:

 Linking two previously activated sensor inputs. 

 

 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

set code  

 

 Code C006

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

 

 

  Only one of the eight sensor links can be set active.  

 

And (And) link with blow-off of the 
outlet tracks

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

And (und) link without blow-off of the 
outlet tracks 

(since Versions-No. 10

)

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

Or link

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

Min/Max link

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

And / S2 link 

(since Versions-No. 10

)

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

Level control for the hopper controller 

(since Versions-Nr. 10

)

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

 


background image

Rhein-Nadel Automation GmbH 

            13 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

Level control

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

Single link

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to the 
main menue 

 

 

 
A brief description of the individual links 

 

And (AND) link of the two sensor inputs with blow-off of the outlet tracks. 

 

Example: 

Application:  Two-track feeding system with back pressure control 

Solution:  Track 1 (Sensor 1) full = blow-off track 1 (Relais K1) 

Track 2 still free 
Track 2 (Sensor 2) full = blow-off track 2 (Relais K2) 
Track 1 still free 
Track 1 + Track 2 full = bowl feeder (chanal 1) stop blow-off air after approx. 4 sec  

 

And (UND) link of the two sensor inputs without blow-off of the outlet track. 

 

The bowl feeder (chanal 1) switches off, if both sensors are assigned. The air for sorting may be  

            de-energizes later (4 sec) through relay K2. 

 

Or link of both sensor inputs. 

 

The bowl feeder switches off (chanal1), if one of both sensors is assigned. The air for sorting may be  

            de-energizes later (4 sec) through relay K2. 

 

Min/Max link of both sensor inputs. 

 

The bowl feeder (chanal 1) switches off, if both sensors are assigned. Only when both sensors   

            become free, the bowl feeder (chanal 1) switches on again. Relay K1 connects, with the switch off of    
            the bowl feeder. Relay K2 connects 4 sec later (to switch off the blow-off air)  

 

And / S2 link  

 

The bowl feeder (chanal 1) switches off, when both sensors are assigned. When the sensor 2 is free,   

             the system is switched on. The air for sorting can be switched off later (4sec) through relay K2. 

 

Level control for the hopper 
Sensor 2 switches relay K1 according to the entered delay time (C005). When the sensor 1 is     
darkened, relay K1 releases (looking of the hopper). 

Application: 

Sensor 1  = traffic sensor ; Sensor 2  = level control ; Relay K1 = control hopper 

 

Level control 

 

Sensor 2 switches relay K1 according to the entered delay time (C005). 

Application:  Sensor 2 will be used as a level control (z.B. LC-N 24V DC). Relais K1 switches with a 

level controller: 

Bowl feeder or linear feeder empty

 
4.5.5  Code C008 Cycle Control 

Aim:

 Control sensors 1 (back pressure control) and/or 2.

 

The links "AND, SOL" must not be activated in code C006 when the cycle control system is activated. 

 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Set code 

 

 Code C008

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

 Sensor input 1 is monitored

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

 Sensor input 2 is monitored

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

 Monitoring dependent on 
 channel 1

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

 Time until alarm signal 

KANAL l
KANAL 2

CODE

 

 

 

3 - 240 sec. 

 

 


background image

Rhein-Nadel Automation GmbH 

            14 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 Switch off channel 1 

KANAL l
KANAL 2

CODE

 

 

 

I = see below 
0 = see below 

 

 Switch (Relay K1)  

KANAL l
KANAL 2

CODE

 

 

 

I =  warning at relay K1 
0 = warning at relay K2 

 

 Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

 
 
 
 

 

The cycle control system monitors the FREE sensor state. The time (A 180) is used to set the  

 

maximum time which a sensor may be free before an alarm signal is issued.

 

 

Relay K1 is picked up when an alarm signal is issued. The fault is cleared by covering the sensor. 

 

 

If OUT = 1 and a fault occurs, the bowl feeder or linear feeder will also be switched off in addition to  

 

relay K1 (indicator lamp: fault) and an ERROR message will appear in the display.

 

 

The fault is cleared with the cursor key at the bottom right. 

            If OUT = 0 and a fault occurs, only relay K1 is energized (indicator lamp: fault). The fault is cleared  
 

automatically when sensor 1 is assigned. 

 

If A.I. = 1 Relay K1 is checked on breakdown (switch changed over from relay K2 to K1) 

 

4.5.6  Code C009 Display Status/Return ERROR - signals 

Aim: 

Checking the set vibration frequency and the sensor inputs.

 

 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Set code 

 

 Code C009 Clear error

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

 Remote control signal 
 channel 1

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

 Signal at sensor input 1

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

 Signal at sensor input 2

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

 Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

 

 With the menu item HA = half-wave you can check whether the operating mode (100

–50Hz) has been  

 

correctly selected.

 

 

4.5.7  Code C200 Blocking all Setting Functions 

Aim: 

The user can no longer (accidentally) change the set values.(4.3 available)

 

 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Set code 

 

 Code C200

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

 Block the setting functions

 

KANAL l
KANAL 2

CODE

 

 

 

I = enabled 
0 = block 

 

 Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

 

 

Now only code C200 will be accepted!!! 

            It is possible to change the setpoint for chanel 1 and 2 in the main menu (see 4.3) 
 

4.5.8  Code C100 Output Preset with an External Voltage 

Aim: Setpoint adjustment with external voltage

 

 

 


background image

Rhein-Nadel Automation GmbH 

            15 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Select code 

 

 Code C100

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

 External supply channel 1

 

KANAL l
KANAL 2

CODE

 

 

 

I = active 
0 = inactive 

 

 Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

 
 
 
 

 

If the external supply is activated, the last set digital output value (%) will be the minimum output for 0  

 

volt. The maximum output for 10 volts should be set with the parameter P in C001.

 

 

 

 

The external voltage supply should be connected to terminal 31, 32 and 33 in the control unit. The  

 

connection is potential-free. 

 

Terminal 31 = +10V 

 

Terminal 32 = E 

 

Terminal 33 = 0V

 

 
4.5.9  Code C143 Store Parameters 

 

Aim: 

Storing user parameters.

 

 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Select code 

 

 Code C143 
 
 
 Selection memory space 0-3

 

KANAL l
KANAL 2

CODE

 

 

 

KANAL l  
KANAL 2  

CODE 

 

 

 

 

 

 Store

 

KANAL l
KANAL 2

CODE

 

 

 

KANAL l
KANAL 2

CODE

 

 

 

 Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

 

 

Once PUSH has been confirmed with ENTER, the selected parameters will be stored separately 

 

by pressing a cursor key.

  

 

4.5.10 Code C210 Reset Parameters 

 

Aim: 

Resetting to factory settings or restoring the stored user parameters. 

 

 Select code

 

KANAL l
KANAL 2

CODE

 

 

 

Set code 

 

 Code C210

 

KANAL l
KANAL 2

CODE

 

 

 

 

 

 Factory setting

 

KANAL l
KANAL 2

CODE

 

 

 

KANAL l
KANAL 2

CODE

 

 

 

 User parameters

 

 

 

KANAL l  
KANAL 2  

CODE 

 

 

 

KANAL l
KANAL 2

CODE

 

 

 

 Return

 

KANAL l
KANAL 2

CODE

 

 

 

Store and return to 
main menu 

 

 

 

FAC Selection and confirmation of FAC. applies the factory settings. 

 

 


background image

Rhein-Nadel Automation GmbH 

            16 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 

US.PA. Selection and confirmation of US.PA restores the user parameters previously stored  

 

under C143. 

 

 


background image

Rhein-Nadel Automation GmbH 

            17 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 

4.5.11  Failure 
 

In case of failure, the controller shut-

off automatically showing a flashing „ERROR“ text. The error signal is stored 

even on disconnecting the line up to the momemt when the error indication is cleared in C009.  

 Overload limiting ERROR

 

KANAL l
KANAL 2

CODE

 

 

 

KANAL l
KANAL 2

CODE

 

 

The output power is beyond allowable limit 

Short circuit break

 

KANAL l
KANAL 2

CODE

 

 

 

KANAL l
KANAL 2

CODE

 

 

A short circuit occurs when in operation 

Overvoltage circuit break

 

KANAL l
KANAL 2

CODE

 

 

 

KANAL l
KANAL 2

CODE

 

 

Voltage is or was to high 

Peak current limiting

 

KANAL l
KANAL 2

CODE

 

 

 

KANAL l
KANAL 2

CODE

 

 

An excessive peak current occurred 
 

Scale Drawing 

 

 

 
 

 


background image

Rhein-Nadel Automation GmbH 

            18 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 
 

Connecting Diagram 

 

 

External rated value  0-10 VDC

External potentiometre

R

e

la

is

 “

S

Y

S

T

E

M

-A

IR

/A

L

A

R

M

R

e

la

is

 “

S

T

A

T

U

S

Contact - load max. 6 A, 250 V AC

S

ta

tu

s

 “S

T

A

N

D

B

Y

S

ta

tu

s

 “

A

C

T

IV

E

0

 V

o

lt,

 r

e

m

o

te

 c

o

n

tr

o

l

+

2

4

 V

, r

e

m

o

te

 c

o

n

tr

o

l

0

 V

o

lt,

 r

e

fe

re

n

c

e

S

e

n

s

o

r 1

, i

n

p

u

t

+

2

0

 m

A

+

2

4

 V

o

lt,

 m

a

x

. 1

2

0

 m

A

S

e

n

s

o

2

, i

n

p

u

t

Load
max. 6A

Mains supply
230 V; 50/60 Hz

 

 


background image

Rhein-Nadel Automation GmbH 

            19 

   

 

 

        14.04.2014 

VT-BA ESR2000-GB 

 

 

Rhein-Nadel Automation GmbH 

 

Reichsweg 19/23  

  D - 52068 Aachen 

Tel (+49) 0241/5109-159  

  Fax +(49) 0241/5109-219 

Internet www.rna.de  

  Email vertrieb@rna.de 

Rhein-Nadel Automation GmbH 

 

Zweigbetrieb Lüdenscheid 

Nottebohmstraße 57  

  D - 58511 Lüdenscheid 

Tel (+49) 02351/41744  

  Fax (+49) 02351/45582 

Email werk.luedenscheid@rna.de 

Rhein-Nadel Automation GmbH 

 

Zweigbetrieb Ergolding 

Ahornstraße 122  

  D - 84030 Ergolding 

Tel (+49) 0871/72812  

  Fax (+49) 0871/77131 

Email 

werk.ergolding@rna.de

 

PSA Zuführtechnik GmbH

 

Dr. Jakob-Berlinger-Weg 1  

  D 

– 74523 Schwäbisch Hall 

Tel +49 (0)791/9460098-0  

  Fax +49 (0)791/9460098-29   

Email info@psa-zt.de 

 

 

 

HSH Handling Systems AG

 

Wangenstr. 96 

 CH - 3360 Herzogenbuchsee 

Tel +(41) 062/95610-00  

  Fax (+41) 062/95610-10 

Internet www.rna.de 

 Email info@handling-systems.ch 

  

 

 

RNA AUTOMATION LTD

 

Hayward Industrial Park 

Tameside Drive, Castle Bromwich 

GB - Birmingham, B 35 7 AG 

Tel (+44) 0121/749-2566  

  Fax (+44) 0121/749-6217 

Internet www.rna-uk.com 

 Email rna@rna-uk.com 

 

Vibrant S.A.

 

Pol. Ind. Famades C/Energía Parc 27 

E - 08940 Cornellà Llobregat (Barcelona) 

Tel (+34) 093/377-7300  

 Fax (+34) 093/377-6752 

Internet www.vibrant-rna.com 

 Email info@vibrant-rna.com