Full Text Searchable PDF User Manual
MODEL PA10
10 SEER 3-PHASE AIR CONDITIONER
Product Data
AVAILABLE SIZES:
Nominal sizes available (036, 048 and 060) to
meet the needs of light commercial applications.
CERTIFICATION:
All models are listed with UL, (U.S. and Can-
ada), ARI, and CEC.
ELECTRICAL RANGE:
208/230v, three phase in 036, 048 and 060
sizes; and 460v, three phase in 060 size.
FAN MOTOR:
The totally enclosed fan motor provides greater
reliability under adverse conditions and depend-
able performance for many years. The permanent
split capacitor type motor was designed for opti-
mum efficiency. The motor was then qualified
under extreme conditions to help ensure a long,
reliable life.
CABINET:
A weather protective cabinet of prepainted steel is
protected underneath by a galvanized coating and
treated with a layer of zinc phosphate for a finish
that will last for many years. All screws on cabinet
exterior are coated for a long-lasting, rust-
resistant, quality appearance.
UNIT DESIGN:
The copper tube, enhanced sine wave, aluminum
fin coil is designed for optimum heat transfer. Ver-
tical air discharge carries sound and hot con-
denser air up and away from adjacent patio areas
and foliage. The base pan is designed for easy
removal of water, dirt, and leaves.
COMPRESSOR:
Each compressor is protected with internal tem-
perature- and current-sensitive overloads. An
internal pressure relief valve provides high-
pressure protection to the refrigerant system. For
improved serviceability, all models are equipped
with a compressor terminal plug.
3-PHASE
Both service valves are brass, front seating type
with sweat connections. Valves are externally
located so refrigerant tube connections can be
made quickly and easily. Each valve has a service
port for ease of checking operating refrigerant
pressures.
SERVICE VALVES:
Control board that monitors the electrical phase
and prevents compressor operation if wired
incorrectly.
SERVICEABILITY:
One panel provides access to electrical controls.
Removal of top gives access to fan motor, com-
pressor, and condenser coil.
LIMITED
Standard 1-year limited warranty on parts and 5-
year limited warranty on compressor.
FEATURES
(SCROLL
COMPRESSOR
UNITS) MONITOR
BOARD:
WARRANTY:
—2—
PA10
SOUND POWER (dBA) (A-wtd., non-pure tone corrected.)
NOTE: Tested in accordance with ARI standard 270.95. (Not listed with ARI.)
MODEL NUMBER NOMENCLATURE
UNIT
SIZE
SOUND
LEVEL
OCTAVE BAND CENTER FREQUENCY (Hz)
125
250
500
1000
2000
4000
8000
036-A
82
55.0
64.0
73.0
74.5
72.0
60.5
64.0
048-A
82
61.9
67.5
71.8
77.1
76.5
72.9
66.9
060-A
82
58.0
67.5
78.0
76.0
76.0
73.0
67.0
PA10
P
R
Type of Unit
PA10 – Electric Air Conditioner
Electrical Supply
P
— 208/230-3-60
E
— 460-3
Refrigerant–R22
REGISTERED
ISO 9001:2000
036
000
A
A
AA
Variations
Series
Variation
A — Standard Unit
Heating Capacity
Nominal Cooling Capacity
036
– 3.0 Tons
048
– 4.0 Tons
060
– 5.0 Tons
—3—
PA10
AIR IN
NOTES:
1. Allow 30 in. clearance to service side of
unit, 48 in. above unit, 6 in. on one side, 12 in.
on remaining side, and 24 in. between units for proper airflow.
2. Minimum outdoor operating ambient in cooling mode is
55
°
F, max. 125
°
F.
3. Series designation is the 14th position of the unit
model number.
4. Center of gravity .
AIR IN
3
/
8
-IN. DIA
TIEDOWN
KNOCKOUTS
(2) PLACES
H
G
F
E
L
K
J
AIR IN
M
N
AIR DISCHARGE
AIR IN
AIR DISCHARGE
AIR DISCHARGE
A
SQ
B
P
C
2
7
/
8
″
1
1
/
4
″
FIELD CONTROL SUPPLY
CONN
7
/
8
-IN.
DIA HOLE
FIELD POWER SUPPLY CONN
7
/
8
-IN.
DIA HOLE WITH
1
1
/
8
-IN.
DIA KNOCKOUT
AND 1
3
/
8
-IN.
DIA KNOCKOUT
3
/
8
-IN.
DIA LIQUID
LINE CONN
D
DIA VAPOR LINE CONN
DIMENSIONS (IN.)
NO
TE:
The data in this pub
lication is displa
y
ed f
or all ser
ies
, ho
w
e
v
e
r,
e
v
er
y ser
ies ma
y not be a
v
ailab
le from man
uf
acturer
.
UNIT
SIZE
SERIES
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Min Mounting
P
ad Dim
036
A
22-1/2
25-15/16
3-3/16
3/4
3-11/16
18-1/8
19-3/4
22-1/4
14-3/8
19-9/16
22-1/16
10-3/8
10-3/4
11
22-1/2 x 22-1/2
048
A
22-1/2
33-15/16
3-1/4
7/8
3-11/16
18-1/8
19-13/16
22-1/4
14-3/8
19-9/16
22-1/16
10-3/8
10-3/4
15-1/2
22-1/2 x 22-1/2
060
A
3
0
29-15/16
3-1/4
7/8
6-1/2
23-1/2
27-1/4
29-3/4
20
27-1/16
29-9/16
15-1/2
14
15
30 x 30
—4—
PA10
SPECIFICATIONS
* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article
336-26.
‡ Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time-delay fuse or circuit breaker.
‡‡ Furnace model numbers P08UA, P08LA, and PG8HA are not compatible with this thermostat.
N/A—Not applicable in this application.
NOTES:
1. Control circuit is 24v on all units and requires external power source.
2. All motors/compressors contain internal overload protection.
3. Copper wire must be used from service disconnect to unit.
UNIT SIZE
036
048
060
SERIES
A
A
A
A
Operating Weight (Lb)
122
154
214
Shipping Weight (Lb)
141
175
236
ELECTRICAL
Unit Volts—Hertz—Phase
208/230-60-3
208/230-60-3
208/230-60-3
460-60-3
Operating Voltage Range*
187-253
187-253
187-253
414-506
Compressor—Rated Load Amps
10.0
12.8
16.0
8.0
Locked Rotor Amps
70.0
91.0
125.0
66.5
Condenser Fan Motor—Full Load Amps
1.4
1.4
1.4
0.8
Min Unit Ampacity for Wire Sizing
13.9
17.4
21.4
10.8
Min Wire Size (60°C/75°F Copper) AWG†
14/14
14/14
12/12
14/14
Max Wire Length (60°C/75°F) (Ft)‡
65/62
52/49
66/63
165/157
Max Branch Circuit Fuse Size**
20
30
30
15
COMPRESSOR & REFRIGERANT
Compressor—Type
Reciprocating
Scroll
Temperature and Current Protection
Internal Line Break
Refrigerant—Type and Amount (Lbs)
R-22 5.00
R-22 6.25
R-22 8.31
Refrigerant Tubes (In. OD)
Vapor and Liquid (Up to 50 Ft)
3/4 and 3/8
7/8 and 3/8
1-1/8 and 3/8
CONDENSER COIL & FAN
Coil Face Area (Sq Ft)
9.1
12.4
18.5
Fan Motor—HP, Type, and RPM
1/4 PSC and 1100
1/4 PSC and 1100
Volts—Hertz—Phase
208/230—60—1
208-230—60—1
460—60—1
Condenser Airflow (CFM)
2500
2500
3400
OPTIONAL EQUIPMENT
Cycle Protector
KSACY0101AAA
Low-Pressure Switch
KAALP0101LPS
High-Pressure Switch
KSAHI0101HPS
Time-Delay Relay
KAATD0101TDR
Winter Start Control
KAAWS0101AAA
Evaporator Freeze Thermostat
KAAFT0101AAA
Compressor Crankcase Heater
KAACH1001AAA
KAACH1201AAA
KAACH1301AAA
Liquid Line Solenoid Valve
KAALS0101LLS
KAALS0101LLS
Filter Drier
P502-8083S
P502-8163S
MotorMaster® Control
32LT660004
32LT660005
Ball Bearing Fan Motor
HC40GE232
HC40GE462
Low-Ambient Pressure Switch Kit
KSALA0201R22
Compressor Sound Hood
KSASH1201COP
KSASH2001CYL
TXV (Hard Shutoff)
KSATX0601HSO
KSATX0701HSO
KSATX1001HSO
Thermostat, Manual Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool‡‡
TSTATPPBAC01-B
Thermostat, Manual Changeover,
5-2-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATPPSAC01-B
Backplate for Standard Thermostat
TSTATXXBBP01
Backplate for Programmable Thermostat
TSTATXXPBP01
Outdoor Air Temperature Sensor
TSTATXXSEN01-B
METERING DEVICE
* Piston listed is for any approved coil non-capillary tube combination.
Piston is shipped with outdoor unit and must be installed in an approved indoor coil.
UNIT SIZE-SERIES
PISTON*
IDENTIFICATION NO.
036-A
70
048-A
82
060-A
93
CHARGING SUBCOOLING
(TXV-TYPE EXPANSION DEVICE*)
UNIT SIZE
REQUIRED SUBCOOLING
(°F)
036
15
048
15
060
15
—5—
PA10
ACCESSORY USAGE GUIDELINE
* For tubing line sets between 80 and 200 ft and/or 20 ft vertical differential, (250 ft total equivalent length), refer to Residential’s Split Systems Long-Line
Application Guidelines.
† Only when low-pressure switch is used.
‡ Required for MotorMaster Low-Ambient Control (full modulation of motor speed).
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
1. Ball Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
SUGGESTED USE: Required on all units where Low-Ambient kit (full modulation feature) or MotorMaster® Control has been added.
2. Compressor Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication
on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.
SUGGESTED USE: When interconnecting tube length exceeds 80 ft.
When unit will be operated below 55°F (12.8°C) outdoor air temperature. Use with low-ambient controller.
All commercial installations.
3. Compressor Sound Hood
Wraparound sound attenuation cover for the compressor. Reduces unit sound level by about 2dBA.
SUGGESTED USE: Unit installed closer than 15 ft to quiet areas—bedrooms, etc.
Unit installed between 2 houses less than 10 ft apart.
4. Cycle Protector
Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has
been interrupted for any reason, including normal room thermostat cycling.
SUGGESTED USE: Installations in areas where power interruptions are frequent.
Where user is likely to ‘‘play’’ with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 80 ft.
High-rise applications.
5. Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: All units where winter start control has been added.
6. Filter Drier
A device for removing contaminants from refrigerant circulating in an air conditioning system: single-direction flow.
SUGGESTED USE: Suggested in all field-connected split-system air conditioners.
7. High-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to about 400
psig. Provides additional protection against compressor damage due to loss of outdoor airflow. To prevent rapid compressor recycling, cycle protector can
be used with this switch.
SUGGESTED USE: Installations exposed to very ‘‘dirty’’ outdoor air.
Installations where condenser inlet air temperature exceeds 125°F (51.7°C).
8. Liquid Solenoid Valve (LSV)
An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) and which stops and starts refrigerant
liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.
SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
In certain long line applications. (Refer to Long-Line Application Guideline.)
9. Low-Ambient Pressure Switch
A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure
within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low-ambient temperatures down to
0°F (–17.8°C) when properly installed.
SUGGESTED USE: A Low-Ambient Pressure Switch or MotorMaster®—Low-Ambient Controller must be used when cooling operating is used at outdoor
temperatures below 55°F (12.8°C).
10. Low-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on low side of refrigerant circuit. Cycles compressor off if refrigerant pressure drops to about 27
psig. Prevents indoor coil freeze-up due to loss of indoor airflow. Also, provides additional protection against compressor damage due to loss of refrigerant
charge. To prevent rapid compressor recycling. Cycle protector can be used with this switch.
SUGGESTED USE: Where indoor coil is exposed to ‘‘dirty’’ air.
All commercial installations.
11. MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing
temperature during operation in cooling mode only. For outdoor temperatures down to –20°F, it maintains condensing temperature at 100°F ± 10°F.
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F.
All commercial installations.
ACCESSORY
REQUIRED FOR
LOW-AMBIENT
APPLICATIONS
(Below 55°F)
REQUIRED FOR
LONG-LINE
APPLICATIONS*
(Over 80 Ft)
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 Miles)
Compressor Crankcase Heater
Yes
Yes
No
Evaporator Freeze Thermostat
Yes
No
No
Winter Start Control
Yes†
No
No
Accumulator
No
No
No
MotorMaster® Control
Yes
No
No
Wind Baffle
See low-ambient instructions
No
No
Support Feet
Recommended
No
Recommended
Liquid-Line Solenoid Valve
or
Hard Shutoff TXV
No
See Long-Line
Application
Guideline
No
Ball Bearing Fan Motor
Yes‡
No
No
—6—
PA10
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued
12. Thermostatic Expansion Valve (TXV) Kits
A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the
evaporator. Kit includes valve, adapter tubes, and external equalizer tube.
SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
13. Time-Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
14. Winter Start Control
An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load conditions.
SUGGESTED USE: All air conditioners where low-ambient controller has been added.
—7—
PA10
RATINGS AND PERFORMANCE
See notes on page 8.
UNIT
SIZE-SERIES
INDOOR
MODEL
TOT. CAP.
BTUH
FACTORY
SUPPLIED
ENHANCE-
MENT
SEER
EER
STANDARD
RATING
PAYNE GAS
FURNACE OR
ACCESSORY
TDR†
ACCESSORY
TXV‡
036-A
*CC5A/CD5AA036
33,800
NONE
10.00
10.20
10.20
9.15
CAR**3614A**
33,200
TXV
—
10.00
—
9.05
CAR**3617A**
33,200
TXV
—
10.00
—
9.00
CAR**3621A**
33,200
TXV
—
10.00
—
9.00
CAR**4221A**
34,000
TXV
—
10.00
—
9.05
CAR**4224A**
34,000
TXV
—
10.00
—
9.05
CC5A/CD5AA042
33,800
NONE
10.00
10.20
10.20
9.45
CC5A/CD5AW036
33,800
NONE
10.00
10.20
10.20
9.45
CE3AA036
33,400
NONE
10.00
10.20
10.20
9.10
CE3AA042
33,600
NONE
10.00
10.20
10.20
9.20
CF5AA036
33,600
NONE
10.00
10.20
10.20
9.40
CK3BA036
33,800
NONE
10.00
10.20
10.20
9.45
CK3BA042
33,800
NONE
10.00
10.20
10.20
9.45
CK5A/CK5BA036
33,800
NONE
10.00
10.20
10.20
9.45
CK5A/CK5BA042
33,800
NONE
10.00
10.20
10.20
9.45
CK5A/CK5BT036
33,800
NONE
10.00
10.20
10.20
9.45
CK5A/CK5BT042
33,800
NONE
10.00
10.20
10.20
9.45
CK5A/CK5BW036
33,800
NONE
10.00
10.20
10.20
9.45
CNRV*3617A**
33,200
TXV
—
10.00
—
9.00
CNRV*3621A**
33,200
TXV
—
10.00
—
9.00
CNRV*4221A**
34,000
TXV
—
10.00
—
9.10
CNRH*3617A**
33,200
TXV
—
10.00
—
9.05
CNRH*4221A**
34,000
TXV
—
10.00
—
9.10
CNRF*3618A**
33,200
TXV
—
10.00
—
9.00
CSRH*3612A**
33,200
TXV
—
10.00
—
9.15
CSRH*4212A**
34,000
TXV
—
10.00
—
9.20
PF1MNB036
33,000
TDR
10.00
—
10.00
8.90
PF1MNB042
33,800
TDR
10.00
—
10.00
9.10
PF1MNC036
33,200
TDR&TXV
10.00
—
—
8.95
PF1MNC042
34,000
TDR&TXV
10.00
—
—
9.05
048-A
*CD5AA048
46,000
NONE
10.00
10.20
10.20
9.25
CAR**4817A**
46,500
TXV
—
10.50
—
9.55
CAR**4821A**
46,500
TXV
—
10.50
—
9.45
CAR**4824A**
46,500
TXV
—
10.50
—
9.45
CAR**6021A**
47,500
TXV
—
10.50
—
9.65
CAR**6024A**
47,500
TXV
—
10.50
—
9.65
CC5A/CD5AA060
46,500
NONE
10.00
10.20
10.20
9.25
CC5A/CD5AC048
45,000
NONE
—
10.00
10.00
9.20
CC5A/CD5AW048
46,000
NONE
10.00
10.20
10.20
9.25
CC5A/CD5AW060
47,000
NONE
10.00
10.50
10.50
9.40
CE3AA048
46,000
NONE
10.00
10.20
10.20
9.35
CE3AA060
47,000
NONE
10.00
10.50
10.50
9.45
CF5AA048
46,000
NONE
10.00
10.20
10.20
9.30
CK3BA048
46,000
NONE
10.00
10.20
10.20
9.25
CK3BA060
47,000
NONE
10.00
10.50
10.50
9.45
CK5A/CK5BA048
46,000
NONE
10.00
10.20
10.20
9.25
CK5A/CK5BA060
47,000
NONE
10.00
10.50
10.50
9.45
CK5A/CK5BT048
46,000
NONE
10.00
10.20
10.20
9.25
CK5A/CK5BT060
47,000
NONE
10.00
10.50
10.50
9.45
CK5A/CK5BW048
46,000
NONE
10.00
10.20
10.20
9.25
CK5A/CK5BX060
47,000
NONE
10.00
10.50
10.50
9.55
CNRV*4821A**
46,500
TXV
—
10.50
—
9.50
CNRV*4824A**
46,500
TXV
—
10.50
—
9.50
CNRV*6024A**
47,500
TXV
—
10.50
—
9.65
CNRH*4821A**
46,500
TXV
—
10.50
—
9.50
CNRH*6024A**
47,500
TXV
—
10.50
—
9.65
CNRF*4818A**
46,500
TXV
—
10.50
—
9.45
CSRH*4812A**
46,500
TXV
—
10.50
—
9.55
CSRH*6012A**
47,500
TXV
—
11.00
—
9.70
PF1MNB048
46,500
TDR
10.00
—
10.00
9.20
PF1MNB060
48,000
TDR
10.00
—
10.00
9.20
PF1MNB070
49,000
TDR
10.50
—
10.50
9.50
PF1MNC048
46,500
TDR&TXV
10.50
—
—
9.40
PF1MNC060
47,500
TDR&TXV
10.50
—
—
9.60
060-A
*CC5A/CD5AW060
57,000
NONE
10.00
10.20
10.20
9.20
CAR**6021A**
57,000
TXV
—
11.00
—
9.60
CAR**6024A**
57,000
TXV
—
11.00
—
9.60
CC5A/CD5AA060
55,000
NONE
10.00
10.20
10.20
9.05
CE3AA060
57,000
NONE
10.20
10.50
10.50
9.30
CK3BA060
56,000
NONE
10.00
10.20
10.20
9.15
CK5A/CK5BA060
56,000
NONE
10.00
10.20
10.20
9.15
CK5A/CK5BT060
56,000
NONE
10.00
10.20
10.20
9.15
CK5A/CK5BX060
58,000
NONE
10.20
10.50
10.50
9.35
CNRV*6024A**
57,000
TXV
—
11.00
—
9.55
CNRH*6024A**
57,000
TXV
—
11.00
—
9.55
CSRH*6012A**
57,000
TXV
—
11.00
—
9.60
PF1MNB060
57,500
TDR
10.00
—
10.00
8.95
PF1MNB070
58,000
TDR
10.50
—
10.50
9.30
PF1MNC060
57,000
TDR&TXV
10.50
—
—
9.30
—8—
PA10
* Tested Combination
† In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance.
Use either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. Most Payne furnaces are equipped with TDR.
‡ Requires hard shutoff TXV; based on computer simulation.
EER
— Energy Efficiency Ratio
SEER
— Seasonal Energy Efficiency Ratio
TDR
— Time-Delay Relay
TXV
— Thermostatic Expansion Valve
N/A — Not Applicable
NOTES:
1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.
2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other
combinations are determined under DOE computer simulation procedures.
3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan-coil or furnace-coil literature.
4. Minimum outdoor operating ambient in cooling mode is 55°F (12.8°C), maximum 115°F (46.1°C).
5. The dashes (—) appearing in the SEER WITH ACCESSORY TDR column indicate no improvement in efficiency due to time-delay function built
into unit as manufactured (see table).
—9—
PA10
DETAILED COOLING CAPACITIES*
See notes on page 11.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75
85
95
105
115
CFM
EWB
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
PA10036-A Outdoor Section With CC5A/CD5AA036 Indoor Section
1050
72
40.10
20.78
3.18
38.64
20.34
3.41
36.81
19.70
3.65
34.68
18.95
3.90
32.40
18.12
4.16
67
37.01
25.79
3.10
35.19
25.14
3.32
33.09
24.32
3.55
30.86
23.38
3.76
28.54
22.45
3.96
62
33.44
30.40
3.01
31.46
29.44
3.21
29.48
28.41
3.39
27.41
27.41
3.58
25.59
25.59
3.78
57
31.89
31.89
2.98
30.42
30.42
3.17
28.89
28.89
3.36
27.29
27.29
3.57
25.58
25.58
3.78
1200
72
40.42
21.37
3.26
39.22
21.15
3.49
37.38
20.58
3.73
35.33
19.94
3.98
32.98
19.14
4.25
67
37.76
27.30
3.18
35.93
26.72
3.40
33.80
25.93
3.63
31.50
25.03
3.87
29.07
24.06
4.06
62
34.27
32.45
3.09
32.30
31.46
3.30
30.29
30.29
3.49
28.53
28.53
3.70
26.75
26.75
3.91
57
33.39
33.39
3.07
31.83
31.83
3.29
30.24
30.24
3.49
28.52
28.52
3.70
26.76
26.76
3.91
1350
72
40.97
22.12
3.33
39.58
21.83
3.56
37.81
21.38
3.81
35.78
20.83
4.06
33.34
20.05
4.32
67
38.22
28.62
3.25
36.44
28.16
3.47
34.35
27.51
3.70
31.97
26.61
3.94
29.47
25.55
4.16
62
34.94
34.25
3.17
33.09
33.09
3.38
31.35
31.35
3.62
29.54
29.54
3.82
27.73
27.73
4.04
57
34.56
34.56
3.16
33.04
33.04
3.38
31.33
31.33
3.62
29.60
29.60
3.82
27.74
27.74
4.04
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
CAR**
3614A**
1.00
0.99
CK5A/CK5BT
036
1.00
1.00
3617A**
1.00
0.99
042
1.00
1.00
3621A**
1.00
0.99
CK5A/CK5BW
036
1.00
1.00
4221A**
1.00
0.99
CNRV*
3617A**
1.00
0.99
4224A**
1.00
0.99
3621A**
1.00
0.99
CC5A/CD5AA
036
1.00
1.00
4221A**
1.00
0.99
042
1.00
1.00
CNRH*
3617A**
1.00
0.99
CC5A/CD5AW
036
1.00
1.00
4221A**
1.00
0.99
042
1.00
1.01
CNRF*
3618A**
1.00
0.99
CE3AA
036
0.99
1.00
CSRH*
3612A**
1.00
0.98
042
0.99
0.99
4212A**
1.00
0.97
CF5AA
036
0.99
1.00
PF1MNB
036
0.98
1.01
CK3BA
036
1.00
1.00
042
1.00
1.01
042
1.00
1.00
PF1MNC
036
0.98
0.99
CK5A/CK5BA
036
1.00
1.00
042
1.00
0.99
042
1.00
1.00
—
—
—
—10—
PA10
DETAILED COOLING CAPACITIES* Continued
See notes on page 10.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75
85
95
105
115
CFM
EWB
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
PA10048-A Outdoor Section With CC5A/CD5AA048 Indoor Section
1400
72
52.44
27.12
4.34
50.89
26.57
4.73
49.02
25.94
5.15
46.92
25.15
5.63
44.62
24.27
6.13
67
48.51
33.51
4.27
46.71
32.83
4.66
44.62
31.96
5.10
42.34
30.99
5.56
39.85
29.96
5.99
62
44.11
39.53
4.21
42.11
38.57
4.58
39.96
37.47
4.95
37.75
36.31
5.36
35.25
35.25
5.78
57
41.80
41.80
4.17
40.16
40.16
4.52
38.49
38.49
4.90
36.83
36.83
5.32
34.92
34.92
5.77
1600
72
53.16
28.05
4.44
51.62
27.58
4.83
49.80
27.01
5.26
47.65
26.30
5.73
45.30
25.45
6.23
67
49.37
35.32
4.36
47.62
34.74
4.75
45.50
33.97
5.19
43.22
33.04
5.65
41.07
32.43
6.09
62
45.15
42.21
4.30
43.15
41.12
4.71
40.91
39.86
5.07
38.62
38.62
5.47
36.50
36.50
5.91
57
43.62
43.62
4.28
41.99
41.99
4.65
40.29
40.29
5.05
38.40
38.40
5.47
36.47
36.47
5.91
1800
72
53.66
28.86
4.53
52.15
28.47
4.92
50.31
27.97
5.36
48.15
27.34
5.82
45.77
26.55
6.32
67
50.02
36.96
4.46
48.25
36.48
4.84
46.10
35.81
5.27
43.78
34.93
5.74
41.76
34.50
6.21
62
45.93
44.48
4.39
43.77
43.77
4.79
41.74
41.74
5.19
40.11
40.11
5.62
37.92
37.92
6.08
57
45.07
45.07
4.38
43.47
43.47
4.79
41.65
41.65
5.19
39.85
39.85
5.61
38.06
38.06
6.04
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
CAR**
4817A**
1.00
0.97
CK5A/CK5BT
048
1.00
1.00
4821A**
1.00
0.98
060
1.00
0.98
4824A**
1.00
0.98
CNRV*
4821A**
1.00
0.98
6021A**
1.01
0.97
4824A**
1.00
0.98
6024A**
1.01
0.97
6024A**
1.01
0.98
CC5A/CD5AA
060
1.00
1.00
CNRH*
4821A**
1.00
0.98
CC5A/CD5AC
048
0.98
0.99
6024A**
1.01
0.98
CC5A/CD5AW
048
1.00
1.00
CNRF*
4818A**
1.00
0.98
060
1.01
0.99
CSRH*
4812A**
1.00
0.97
CD5AA
048
1.00
1.00
6012A**
1.01
0.97
CE3AA
048
1.00
0.99
CK5A/CK5BW
048
1.00
1.00
060
1.01
0.99
CK5A/CK5BX
060
1.01
0.98
CF5AA
048
1.00
0.99
PF1MNB
048
1.00
1.01
CK3BA
048
1.00
1.00
060
1.01
1.02
060
1.00
0.98
070
1.02
1.00
CK5A/CK5BA
048
1.00
1.00
PF1MNC
048
0.99
0.98
060
1.00
0.98
060
1.01
0.98
—11—
PA10
DETAILED COOLING CAPACITIES* Continued
* Detailed cooling capacities are based on indoor and outdoor unit at same elevation per ARI standard 210/240-94. If additional tubing length and/or indoor
unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C). When the required data falls between the published data, interpolation may be performed.
** Unit kW is total of indoor and outdoor unit kilowatts.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75
85
95
105
115
CFM
EWB
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
PA10060-A Outdoor Section With CC5A/CD5AA060 Indoor Section
1950
72
65.78
33.91
5.12
63.76
33.16
5.59
61.29
32.26
6.11
58.55
31.20
6.68
55.48
30.06
7.30
67
60.83
41.73
5.02
58.56
40.81
5.49
56.01
39.73
6.00
53.08
38.47
6.52
50.44
37.61
7.01
62
55.48
49.20
4.93
53.14
48.04
5.36
50.44
46.70
5.77
47.70
45.29
6.26
44.84
43.75
6.78
57
52.32
52.32
4.84
50.52
50.52
5.26
48.89
48.89
5.76
46.35
46.35
6.19
44.33
44.33
6.69
2000
72
66.67
35.03
5.24
64.66
34.41
5.71
62.19
33.57
6.23
59.39
32.57
6.80
56.30
31.50
7.42
67
61.97
43.97
5.14
59.61
43.12
5.60
57.00
42.08
6.11
54.07
40.90
6.67
50.98
39.65
7.23
62
56.63
52.35
5.04
54.24
51.12
5.51
51.50
49.66
5.93
48.58
48.58
6.40
45.98
45.98
6.96
57
54.52
54.52
5.01
52.66
52.66
5.44
50.94
50.94
5.94
48.24
48.24
6.38
46.15
46.15
6.89
2250
72
67.33
36.04
5.35
65.30
35.52
5.82
62.84
34.77
6.35
60.00
33.87
6.93
56.93
32.86
7.54
67
62.76
46.05
5.25
60.41
45.31
5.71
57.75
44.36
6.22
54.80
43.27
6.78
51.66
41.98
7.37
62
57.55
55.11
5.14
55.14
53.81
5.61
52.43
52.43
6.08
49.85
49.85
6.59
47.51
47.51
7.14
57
56.36
56.36
5.13
54.42
54.42
5.60
52.22
52.22
6.07
49.95
49.95
6.58
47.72
47.72
7.09
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
CAR**
6021A**
0.98
0.96
CK5A/CK5BX
060
1.00
0.98
6024A**
0.98
0.96
CNRV*
6024A**
0.98
0.96
CC5A/CD5AA
060
0.98
0.99
CNRH*
6024A**
0.98
0.96
CC5A/CD5AW
060
1.00
1.00
CSRH*
6012A**
1.00
0.98
CE3AA
060
1.00
0.99
PF1MNB
060
1.01
1.04
CK3BA
060
0.98
0.99
070
1.02
1.01
CK5A/CK5BA
060
0.98
0.99
PF1MNC
060
1.01
1.02
CK5A/CK5BT
060
0.98
0.99
—
—
—
—12—
© Payne Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
Printed in U.S.A.
edition date: 3/06
Catalog No. SS-PA10-11
Manufacturer reserves the right to change, at any time, specifications or designs without notice and obligations
Replaces: SS-PA10-10
SYSTEM DESIGN
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature is 125°F (51.7°C).
4. For reliable operation, unit should be level in all horizontal planes.
5. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 60 ft, indoor coil below = 200 ft.
6. For interconnecting refrigerant tube lengths greater than 80 ft or 20 ft vertical differential (250 ft total equivalent length), consult Long-Line Appli-
cation Guideline available from equipment distributor.
7. Crankcase heater required when interconnecting refrigerant tube length exceeds 80 ft.
8. If any refrigerant tubing is buried, provide a minimum 6 in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in.
may be buried without further consideration.
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.