TECHNICAL & SERVICE MANUAL
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS
CONTENTS
1. SPECIFICATIONS·································3
2. DATA ·····················································4
3. REFRIGERANT SYSTEM DIAGRAM ········7
4. PARTS LIST··········································8
Indoor unit
PLH-1.6KKB
No. OC169
1998
[Models]
PLH-1.6KKB.UK
[Service Ref.]
Refer to OC150 for outdoor (PUH-
1.6VKA
3
.UK) units, and OC119 for
indoor items other than this manual.
INDOOR UNIT
Ceiling Cassettes
Series PLH
FILTER
CHECK MODE
TEST RUN
CHECK
REMOTE CONTROLLER
The Slim Line.
From Mitsubishi Electric.
3
SPECIFICATIONS
1
Service Ref.
Power supply(phase, cycle,voltage)
External finish
Heat exchanger
Booster heater
Operation control & Thermostat
Noise level(Low-High)
Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
Defrost method
Noise level
Dimensions
Weight
Refrigerating oil (Model)
Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Input
Running current
Starting current
Fan(drive)
o
No.
Fan motor output
Airflow(Low-High)
External static pressure
Input
Running current
Starting current
Model
Motor output
Starter type
Protection devices
Fan(drive)
o
No.
Fan motor output
Airflow
Charge
W
D
H
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Function
Capacity
Total input
INDOOR UNIT
OUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
Btu/h
W
kW
kW
A
A
kW
K
/ min (CFM)
Pa(mmAq)
kW
dB(A)
mm(in)
mm(in)
mm(in)
mm(in)
kg(lbs)
kW
A
A
kW
kW
K
/ min (CFM)
dB(A)
mm(in)
mm(in)
mm(in)
kg(lbs)
CC
kg(lbs)
mm(in)
mm(in)
PLH-1.6KKB.UK
Cooling
15,000
4,400
1.59
Heating
15,900
4,650
1.51
0.15
0.64
0.70
0.10
0.45
0.50
UNIT : 660(26)
UNIT : 660(26)
UNIT : 253(10)
UNIT : 19(42)
PANEL : 760(30)
PANEL : 760(30)
PANEL : 30(1-1/8)
PANEL : 3.7(8)
1.44
6.74
1.41
6.60
PLH-1.6KKB.UK
Single, 50Hz, 220-240V
33
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan (direct)
o
1
0.030
13-16(460-565)
0(direct blow)
—
Remote controller & built-in
32-37
32(1-1/4)
PUH-1.6VKA
3.
UK
Single, 50Hz, 220-240V
Munsell 5Y 7/1
Capillary tube
Hermetic
RH247VFCT
1.2
Line start
Inner thermostat, High pressure switch
Plate fin coil
Propeller (direct)
o
1
0.065
45(1,590)
Reverse cycle
49
870(34-1/4)
295+24 (11-5/8 add 1)
650(25-5/8)
53(117)
570(MS-56)
R-22
2.2(4.8)
9.52 (3/8)
15.88(5/8)
Flared
Flared
Max. 40m
Max. 40m
w
1. Rating condition (Cooling)…Indoor 27°C D.B., 19.0°C W.B.,
Outdoor 35°C D.B.
Rating condition (Heating)…Indoor 20°C D.B.,
Outdoor 7°C D.B., 6°C W.B.
}
(JIS B8616)
4
2
DATA
1. PERFORMANCE DATA
1) COOLING CAPACITY
Note CA :Capacity (W)
P.C. :Power consumption (kW)
Cooling capacity correction factors
P.C.
1.74
1.79
1.84
1.90
CA
3,624
3,882
4,154
4,442
P.C.
1.64
1.68
1.72
1.77
CA
3,812
4,074
4,352
4,645
P.C.
1.53
1.57
1.61
1.65
CA
3,990
4,258
4,542
4,840
P.C.
1.43
1.46
1.50
1.53
CA
4,159
4,434
4,724
5,028
P.C.
1.33
1.36
1.38
1.41
CA
4,317
4,602
4,899
5,209
P.C.
1.27
1.30
1.32
1.35
CA
4,439
4,726
5,017
5,310
20
25
30
35
40
45
Outdoor intake air D.B.
°
C
Indoor
intake air
W.B.
°
C
16
18
20
22
Service Ref.
PLH-1.6KKB.UK
Refrigerant piping length(one way)
5m
1.00
10m
0.993
15m
0.984
20m
0.978
25m
0.969
30m
0.961
35m
0.956
40m
0.948
45m
–
50m
–
Service Ref.
PLH-1.6KKB.UK
2) HEATING CAPACITY
Note CA :Capacity (W)
P.C. :Power consumption (kW)
Heating capacity correction factors
CA
3,184
3,049
2,930
P.C.
1.03
1.11
1.18
-10
CA
3,650
3,506
3,364
P.C.
1.14
1.23
1.31
-5
CA
4,160
4,003
3,844
P.C.
1.25
1.35
1.44
0
CA
4,714
4,538
4,370
P.C.
1.38
1.48
1.59
5
CA
5,312
5,112
4,942
P.C.
1.51
1.62
1.74
10
CA
5,952
5,724
5,560
P.C.
1.64
1.77
1.90
15
Outdoor intake air D.B.
°
C
Indoor
intake air
D.B.
°
C
15
20
25
Service Ref.
PLH-1.6KKB.UK
Refrigerant piping length(one way)
5m
1.00
10m
1.00
15m
1.00
20m
1.00
25m
1.00
30m
1.00
35m
0.998
40m
0.995
45m
–
50m
–
Service Ref.
PLH-1.6KKB.UK
5
Heating
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-12-10
-5
0
5
10
15
OUTDOOR W.B.(
°
C)
INDOOR D.B. (
°
C)
INDOOR D.B. (
°
C)
15
20
25
25
20
15
TOTAL INPUT (RATIO)
CAPACITY (RATIO)
Cooling
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-5
5
15
25
35
45
52
OUTDOOR D.B.(
°
C)
TOTAL INPUT (RATIO)
CAPACITY (RATIO)
INDOOR W.B.(
°
C)
INDOOR W.B.(
°
C)
22
20
18
16
22
20
18
16
2. PERFORMANCE CURVE
PLH-1.6KKB.UK
Input (kW)
Current (A)
Starting current (A)
Input (kW)
Current (A)
Starting current (A)
Mode
Capacity (W)
Total Input (kW)
Indoor
Outdoor
Cool
4,300
1.48
0.12
0.60
0.66
1.36
6.79
30
Heat
4,550
1.40
0.08
0.41
0.45
1.32
6.59
30
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Service Ref.
Power Supply
PLH-1.6KKB.UK
PUH-1.6VKA
3
.UK
220V 50Hz 1phase
220V 50Hz 1phase
Cool
4,350
1.54
0.14
0.62
0.68
1.40
6.76
32
Heat
4,600
1.45
0.09
0.43
0.47
1.36
6.57
32
PLH-1.6KKB.UK
PUH-1.6VKA
3
.UK
230V 50Hz 1phase
230V 50Hz 1phase
Cool
4,400
1.59
0.15
0.64
0.70
1.44
6.74
33
Heat
4,650
1.51
0.10
0.45
0.50
1.41
6.60
33
PLH-1.6KKB.UK
PUH-1.6VKA
3
.UK
240V 50Hz 1phase
240V 50Hz 1phase
3. ELECTRICAL DATA
6
Capacity
Input
Indoor unit Service Ref.
Phase,Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
SHF
BF
Mode
Total
W
kW
V
A
V
A
MPa•G
(kgf/
F
•G)
MPa•G
(kgf/
F
•G)
°
C
°
C
°
C
m
D.B.
°
C
W.B.
°
C
D.B.
°
C
D.B.
°
C
W.B.
°
C
PLH-1.6KKB.UK
Service Ref.
Cooling
4,400
1.59
Heating
4,650
1.51
6.74
1.80
(18.3)
0.54
(5.51)
78.7
48.5
8.5
5
27
19
16.1
35
24
0.83
0.21
6.60
1.70
(17.3)
0.40
(4.08)
77.2
–
0.7
5
20
15
35.2
7
6
–
–
0.64
0.45
PLH-1.6KKB.UK
1,50
240
PUH-1.6VKA
3
.UK
1,50
240
Electrical circuit
Refrigerant circuit
Indoor
side
Outdoor
side
Air flow
Air speed
Coverage range
K
/min
m/
W
.
m
PLH-1.6KKB.UK
16.0
5.6
6.0
Air flow
Air speed
Coverage range
Total width of discharge outlets
K
/min
m/
W
.
m
mm
17.0
5.9
6.4
0
Standard
High ceiling
4. STANDARD OPERATION DATA
5. OUTLET AIR SPEED AND COVERAGE RANGE
W
The air coverage range is the value up to the position where the air speed is 0.25m/sec.
When air is blown out horizontally from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and
the furniture inside the room.
The unit of pressure has been changed to Mpa based on the international SI system.
The corversion factor is : 1 (Mpa · G) = 10.2 (kgf/cm
2
· G)
7
REFRIGERANT SYSTEM DIAGRAM
3
W
1
O.D.
{
3.2
o
I.D.
{
1.6–
R
630
O.D.
{
3.2
o
I.D.
{
1.8–
R
600
High pressure protect switch
PLH-1.6KKB.UK / PUH-1.6VKA
3
.UK
Unit : mm
8
PARTS LIST
4
PANEL PARTS
PLH-1.6KKB.UK
1
2
3
4
5
6
7
T7W 560 003
R01 29H 500
R01 29H 691
R01 29H 061
T7W 14K 200
T7W 556 305
Part No.
Part Name
Specification
No.
Wining
Diagram
Symbol
Recom-
mended
Q
,
ty
Price
Unit Amount
AIR OUTLET GRILLE
AIR FILTER
INTAKE GRILLE
HINGE
–
GRILLE HANGER
REMOTE CONTROLLER
REMOTE CONTROLLER CABLE 12m
R.B
Remarks
(Drawing No.)
1
1
1
2
1
1
1
Q
,
ty/set
PLH-1.6
KKB.UK
(BG88H096H01)
7
2
3
1
4
5
6
9
PANEL PARTS
PLH-1.6KKB.UK
1
2
3
4
5
6
7
R01 29H 002
R01 29H 085
R01 29H 223
R01 29H 063
R01 29H 056
R01 29H 047
Part No.
Part Name
Specification
No.
Wining
Diagram
Symbol
Recom-
mended
Q
,
ty
Price
Unit Amount
AUTO VANE
AIR GUIDE
VANE MOTOR
SPRING JOINT 1
T7W 33K 063
SPRING JOINT
PUSH BUTTON
VANE SUPPORT
8
T7W 560 258
COARD HEATER
9
R01 29H 040
GRILLE GEAR (RIGHT)
10
R01 29H 041
GRILLE GEAR (LEFT)
240V 28.2W
H
MV
Remarks
4
1
1
1
1
1
8
1
1
1
<3/SET>
Q
,
ty/set
PLH-1.6
KKB.UK
1
1
4
4
4
7
10
7
1
3
7
9
7
7
6
2
1
5
8
10
FUNCTIONAL PARTS
PLH-1.6KKB.UK
1
3
6
7
2
5
2
13
14
24
25
26
23
16
9
20
22
18
3
4
30
29
27
8
10
34
11
17
31
19
21
28
15
34
11
1
2
3
4
5
6
7
Part No.
Part Name
Specification
No.
Wining
Diagram
Symbol
Recom-
mended
Q
,
ty
Price
Unit Amount
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
Remarks
(Drawing No.)
Q
,
ty/set
KKB.UK
PLH-1.6
–
–
–
T7W E00 762
R01 29H 105
–
R01 41N 114
R01 08K 202
R01 29H 523
T7W 55K 355
R01 W28 266
R01 W28 527
T7W 580 480
S70 A00 529
–
–
–
–
–
T7W 521 716
T7W 517 716
T7W 515 716
R01 29H 255
–
T7W 58K 310
T7W 520 239
T7W 580 799
R01 J07 202
–
–
R01 08K 097
R01 A48 524
R01 005 533
S70 A00 675
BASE
LEG
LEG
FAN MOTOR
MOTOR MOUNT
INNER COVER
TURBO FAN
INDOOR COIL THERMISTOR
DRAIN SOCKET
DRAIN PUMP
DRAIN SENSOR
DRAIN HOSE
HEAT EXCHANGER
DRAIN PAN
CORNER SUPPORT(1)
CORNER SUPPORT(2)
CORNER SUPPORT(2)
CORNER SUPPORT(3)
LEAD WIRE COVER
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
FAN MOTOR CAPACITOR
CONTROLLER CASE
INDOOR CONTROLLER BOARD
FUSE
TRANSFORMER
ROOM TEMPERATURE THERMISTOR
BELL MOUTH
ELECTRICAL PARTS COVER
SPL WASHER
DRAIN PLUG
SENSOR HOLDER
FAN GUARD
(BG00T765G01)
(BG00K209G01)
(BG00K209G02)
(BG00T770G01 )
(BG00K210G01)
(BG00K211G01)
(BG00K212G01)
(RG00T856G01)
(BG00T861G01)
(BG25J542H04)
(BG00N936G07)
(RG00C610G01)
PAI-V30F
3P(L,N,
;
)
3P(1,2,3)
2P(1,2)
2.5
µ
F 400V
250V 6.3A
1
2
2
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MF1
RT2
DP
DS
TB2
TB4
TB5
C1
I.B
F1<I.B>
T
RT1
Part numbers that are circled not shown in the figure.