PDF User Manual

  1. Home
  2. Manuals
  3. Mavigard MG-400 Operating And Maintenance Manual

Mavigard MG-400 Operating And Maintenance Manual

Made by: Mavigard
Type: Operating And Maintenance Manual
Category: Smoke Alarm
Pages: 20
Size: 2.74 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

MG-400

COMMISSIONING, OPERATING AND MAINTENANCE MANUAL

MODEL: MAVIGARD SERIES

SUB MODEL: CONVENTIONAL SYSTEM

COMBINED GAS AND FIRE ALARM CONTROL PANEL

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 2  

  

 

CONTENTS 

 

1. INTRODUCTION ----------------------------------------------------------------------------------------------------------------------------------------------- 3 

2- WARNING ------------------------------------------------------------------------------------------------------------------------------------------------------- 3 

3- MOUNTING THE PANEL ------------------------------------------------------------------------------------------------------------------------------------- 3 

4- PANEL INPUTS ------------------------------------------------------------------------------------------------------------------------------------------------- 4 

4.1 Mains Power Supply ------------------------------------------------------------------------------------------------------------------------------------ 4 

4.2 Batteries --------------------------------------------------------------------------------------------------------------------------------------------------- 4 

4.3 Channel Inputs ------------------------------------------------------------------------------------------------------------------------------------------- 4 

4.3.1 Fire detectors and MCPs ------------------------------------------------------------------------------------------------------------------------ 4 

4.3.2  4-20mA input-------------------------------------------------------------------------------------------------------------------------------------- 4 

4.3.3 Connections of 4-20mA converter card ----------------------------------------------------------------------------------------------------- 4 

4.3.4 Two-wire detectors------------------------------------------------------------------------------------------------------------------------------- 5 

4.3.5 Three-wire detectors ---------------------------------------------------------------------------------------------------------------------------- 5 

4.3.6 Flame detectors ----------------------------------------------------------------------------------------------------------------------------------- 5 

4.4 Remote control inputs --------------------------------------------------------------------------------------------------------------------------------- 5 

5- PANEL OUTPUTS ---------------------------------------------------------------------------------------------------------------------------------------------- 5 

5.1 Sounder outputs ----------------------------------------------------------------------------------------------------------------------------------------- 5 

5.2 24V DC Power Supply (Aux) Output ---------------------------------------------------------------------------------------------------------------- 5 

5.3 Relay Outputs -------------------------------------------------------------------------------------------------------------------------------------------- 5 

5.3.1 Low alarm relay:----------------------------------------------------------------------------------------------------------------------------------- 5 

5.3.2 High Alarm relay:---------------------------------------------------------------------------------------------------------------------------------- 5 

5.3.3 Over-range Relay: --------------------------------------------------------------------------------------------------------------------------------- 5 

5.3.4 Fault relay: ------------------------------------------------------------------------------------------------------------------------------------------ 6 

6- CONTROL BUTTONS ------------------------------------------------------------------------------------------------------------------------------------------ 6 

7- PANEL INDICATORS------------------------------------------------------------------------------------------------------------------------------------------- 6 

8- FUSES ------------------------------------------------------------------------------------------------------------------------------------------------------------ 7 

9- POWERING THE PANEL -------------------------------------------------------------------------------------------------------------------------------------- 8 

9.1 Normal ----------------------------------------------------------------------------------------------------------------------------------------------------- 8 

9.2 Alarm ------------------------------------------------------------------------------------------------------------------------------------------------------- 8 

9.3 Fault -------------------------------------------------------------------------------------------------------------------------------------------------------- 8 

10 PANEL MENUS ------------------------------------------------------------------------------------------------------------------------------------------------ 8 

10.1 Visualization -------------------------------------------------------------------------------------------------------------------------------------------- 8 

10.2 Access Level 2------------------------------------------------------------------------------------------------------------------------------------------ 11 

11 – OPERATING WITH REPEATER PANEL AND RELAY MODULE ------------------------------------------------------------------------------------ 18 

12- SPECIFICATIONS: ------------------------------------------------------------------------------------------------------------------------------------------- 18 

12.1 Mechanical Features: -------------------------------------------------------------------------------------------------------------------------------- 18 

12.2 Electrical Features: ----------------------------------------------------------------------------------------------------------------------------------- 18 

ANNEX-A CONNECTION SCHEME  OF  THE PANEL ----------------------------------------------------------------------------------------------------- 19 

ANNEX-B  PANEL DIMENSIONS -------------------------------------------------------------------------------------------------------------------------------- 20 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 3  

  

   

1. INTRODUCTION

 

MaviGard  MG-400  is  a  4  channel,  24  V  DC  operating  voltage  combined  gas  and  fire  alarm  control  panel. 

Each channel can host 1 gas detector or 20 fire detectors with unlimited number of manual call points. Panel 
power supply unit has an automatic battery charger and charging control circuit. Alarm and fault conditions are 
showed  on  8x40  character backlight  LCD.  Panel  sounder outputs  are  supervised for  open  and  short  circuit 
conditions. The  panel  has  built-in  buzzer. Settings to  the  panel are  made  by  use  of  navigation  buttons and 
menu. The panel is microprocessor-controlled. Channels can be inhibited, sounder outputs and relays can be 
tested, 
Any  channel  can  be  disabled,  sounder  outputs  and  relays  can  be  test.  Gas  detectors  can  be  zeroed  and 
calibrated. These features are also told in the section of 

“Panel Menu” in detail. The panel is equipped with 2 

units  of  24  V  DC  500  mA  sounder  outputs  and  has  4  voltage-free changeover  contact  relay  outputs  (Low 
alarm  relay,  High  alarm  relay,  over-range  relay  and  fault  relay.  Panel  also  has  24  V  DC  500  mA  auxiliary 
power supply output. By use of remote control inputs, alarm can be silenced and all the channels in the panel 
can be disabled. 

 

Producer-

manufacturer or importer firms’ title, address, and telephone number 

Manufacturer Firm: 

MAVILI ELEKTRONIK TICARET VE SANAYI A.S. 
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY 
TEL: +90 216 466 45 05 - +90 216 466 45 10 
 

Service stations’ communication information that related spare parts have been provided 
Authorized Services: 

MAVILI ELEKTRONIK TICARET VE SANAYI A.S. 
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY 
TEL: +90 216 466 45 05 - +90 216 466 45 10 
 
TEKSIS TEKNIK ELEKTRONIK SIS.TIC. VE SAN. LTD. STI. 
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/3 UMRANIYE / ISTANBUL / TURKEY 
TEL: +90 216 313 60 60 - +90 216 313 47 49 
 

Expected operation life which has been determined and announced by related ministry 

This device’s expected operation life is 7 years. 

 

2- WARNING 

The equipment contains static-sensitive high quality electronic control equipment. Do not use the panel before 
reading this manual. In case of any fault, only the technicians of the manufacturer or technicians authorized by 
the  manufacturer  should  repair  or  maintain  the  panel.  Use  the  recommended  cable  types  defined  in  this 
manual for cabling of  power supply, detection and sounder circuits. Do not remove any  connections and  do 
not make any connections while mains power supply is connected. Pane

l’s earth connection must be made. 

The cabinet must be connected to a suitable earth point. 

Under no  circumstances should voltage or  current outside of  the limits described in  this  manual be 
used with system units. Otherwise, damage on panel may occur, which is not subject to maintenance

 

under warranty.

 

 

3- MOUNTING THE PANEL

 

MG-400;  is  not  suitable  for  hazardous  areas.  Panels  should  be  located  into  safe  areas.  With  appropriate 
protection material gas  and fire detectors can  be  connected to  the  hazardous areas. To do  that  hazardous 
areas should be checked and the protection material need to be select according to condition of this area. 
While  mounting  the  system  in  a  hazardous  area,  experienced  and  educated  technical  team  should  be 
assigned. Panel should be placed to an easy reachable, clean and dry place without forming any vibration. 
The  LCD  on  the  panel  should be  located in  flat  wall on  eye  level and  pay attention to  mount inside  of  any 
cabinet or near to high heat emitting devices.  Screws or bolts of a minimum of 4mm diameter must be used 
to  mount the  cabinet  in  3  mounting  points.  Please check  out  Annex. B.  Figure 2.  Panel  cable  entries  from 
back and top of the panel are available for easy mounting. 

 

 
 
 
 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 4  

  

4- PANEL INPUTS 

 

4.1 Mains Power Supply 

The panel is designed to operate on 220 V AC 50Hz. Earth connections must be made to earth terminal and 
earth resistor must be less than 10 Ohms. The mains power supply of the panel must be via an independent 
self-resetting fuse rated 5A  220  V AC. This fuse must be  separate from  the other fuses and  a  caution note 
should  be  written  such  as 

“ATTENTION!  GAS  ALARM  CONTROL  PANEL  FUSE.  DO  NOT  REMOVE”  to 

ensure safe operation of the panel. 
Recommended cable types are 3x2.5 NYM or 3x2.5 NYA. Connections should be same as Annex.A Figure1. 
Do not connect or disconnect the loop, mains supply input and PCB connections while the panel is energized 
to avoid an electric shock. 
 

4.2 Batteries 

Batteries  provide  continuity  of  operation  during  a  failure  of  the  mains  power  supply.  The  panel  has  an 
automatic battery charger circuit. The  panel  uses  2  units  of  12V  DC  7Ah  dry  type  batteries.  Connection 
diagram  can  be  seen  in  Annex.A Figure-2. 

 

4.3 Channel Inputs

 

These inputs provide power to the gas or fire detectors and transmit the status of gas/fire alarm, short circuit 
and open circuit. In each channel input 4-20mA or conventional fire detector connection can be made.

 

4.3.1 Fire detectors and MCPs 

For each zone line at most 20 units of detector and infinite number of button can be connected.

 

The characteristics of the cable are dependent on the length of the loop: for a loop of 0-500 metre long, use 
1x2x0.8+0.8J-Y(st)Y cable,  for  a  loop  of  500-1500  metre  long  use  1x2x1.5+0.5J-Y(st)Y.  A  6.8  k

Ω  resistor 

must be connected as an end-of-line element. 

Channel  jumper  setting  should  be  set  as  fire.  If  zener  barrier  will  use,  the  jumper  of  zener  barrier  must  be 
adjust accordingly. Connections are seen as in Annex. A 

– Figure-3.

 

4.3.2  4-20mA input 

It provides 28V DC  supply voltage for both fire and gas detectors. It follows 4-20 mA analogue current input 
via  100  Ohms  resistor.  It  is  possible to mount 2-  or  3-  wire gas  or  flame detectors, in  either sink  or  source 
mode.  Control  panel  can  make  the  tracking  of  the  analogue  values  between  4mA-21.5mA.  When  the 
currents  exceed 21.5 mA,  panel  gives  the fault  of 

“OVERRANGE”. Connection can be  seen from Annex. A 

figure -9.

 

4.3.3 Connections of 4-20mA converter card 

1-   The jumper settings on both converter card and gas alarm control panel adjusted as 

“SOURCE” or 

“SINK”. The point here is both adjustments should be same. 

 

2- 

Before  connecting  4-20  mA  card  to  the  panel,  from  the  panel  menu,  channel  device  type  must  be 

selected as 

“det 4-20 srce” or “det 4-20 sink”. 

 

3- 

Before doing the signal connection of converter card to the panel, card is energized from the panel. 

 

4- 

Voltmeter

’s probes, are connected to (+) and (-) supply terminals of CON1 socket go to detector. Value 

seen on Voltmeter is adjusted to 2V by using TP3(detector voltage potentiometer.) potentiometer. 

 

5-   Then converter card

’s energy is turned off. When all the connections are made, it is reenergized. 

 

6-      Voltmeter

’s  probes  are  connected  to  the  test  points  TP4  and  TP3.  Value  seen  on  the  voltmeter  is 

brought to zero by using TP4 (balance potentiometer)O. Make sure that 0 value see continuously. 
7-      Voltmeter

’s  probes  are  connected  to  the  test  points  TP2  and  TP1.  Value  seen  on  the  voltmeter  is 

brought to 40mV by using TP2 (zero potentiometer). 

8-   

After these settings applied, the measured value should be read as 0. 

 
 
 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 5  

  

4.3.4 Two - wire detectors 

In Figure-8, Annex. A ; a sink current detector

’s connection is shown. Appropriate jumper settings should 

be selected. 

4.3.5 Three - wire detectors

 

In  Figure-9  Annex-A;  a  3-wire  detector

’s  connection  is  shown.  Appropriate  jumper  settings  should 

be selected as sink or source. 

4.3.6 Flame detectors

 

Jumper settings are adjusted according to detector is sink or source. Definitely do not select fire settings 

 

4.4 Remote control inputs 

Some of controls of gas alarm control panel can also be done remotely. These are: 

 

·

Alarm Silence / Reset - As/R: 

In case of alarm, to silence the sounders, switch is closed for one time. 

If  it is closed again, alarm situation is reset and system turns back to its initial position. 

 

·Inhibiting All Channels - Inh: 

Inhibits  all  channels. In  this  case  panel keeps  tracking detectors. Yet, if 

there is an alarm from any fire or gas detectors, it shows the situation only from LCD panel. 

 

Connections should be as in figure- 7 Annex. A. Screening table should be used. 

 

5- PANEL OUTPUTS 
5.1 Sounder outputs 

The panel has 2 sounder outputs, each rated 24V DC 500mA. Current consumption more than 500mA will 
cause  a  fault  condition in  sounder line.  Sounder circuits  are  continuously monitored for  open  and  short 
circuit  faults  by  connecting  the  end  of  line  resistor  on  the  last  device  on  the  circuit.  2x1.5  mm

²  cable 

should  be  used  for  cabling  of  sounder  outputs.  Connections  should  be  made  according  to  Annex-A 
Figure-4.  Polarised  type  sounders  should  be  used.  Otherwise,  fire  alarm  control  panel  displays  a  fault 
condition. 

 

5.2 24V DC Power Supply (Aux) Output 

The  panel  is  equipped  with  an  auxiliary  24V  DC  500mA  power  supply  output.  The  output  is  used  to 
energise  external  devices  such  as  telephone  dialler  or  gas  detector.  Overloading the  output  will  cause 
device  malfunction  or  output  fault  respectively.  Connections  should  be  made  according  to  Annex-A 
Figure-5. 
 

5.3 Relay Outputs 

Panel has 4 volt free changeover relay outputs rated 1A at 30 V DC. These volt-free outputs, high alarm 
relay  (normally  de-energized),  low  alarm  relay  (normally  de-energized),  over-range  relay  (normally  de-
energized) and fault alarm (normally energized) relay. Connections should be made according to Annex-A 
Figure-6. 

 

5.3.1  Low  alarm  relay:

 

Low  alarm  relay  is  activated  when  the  detectors  channel  low  limit 

value  exceeds  in  the  medium.  Features  of  low  alarm  relay;  threshold,  latching/non-latching,  NO/NC 
operating is adjusted by the user. 

 

5.3.2  High  Alarm  relay:

 

High  alarm  relay  is  activated  when  the  detectors  channel  high  limit 

value  exceeds  in  the  medium.  Features  of  low  alarm  relay;  threshold,  latching/non-latching,  NO/NC 
operating are adjusted by the user. 

If channels include conventional fire alarm detectors, when detectors sends fire alarm signal, high 

a

la

rm relay will be activated.

 

 

5.3.3 Over-range Relay:

 

If  the gas level in  the medium exceeds a fixed high limit (21.5 mA), 

over- range relay is activated. Latching/non-latching, NO/NC operating is adjusted by the user. 

 

 

 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 6  

  

5.3.4 Fault relay:

 

When fault condition or panel

’s energy is cut off, it changes its position. When 

the fault condition disappears, fault relay gets back to its initial position. 

 

Important Note:  Under  no  circumstances should  voltage  or  current  outside  of  1A  at  30  V  DC  used 
with  contacts. Otherwise, damage on  panel  may occur,  which  is  not  subject  to  maintenance under 
warranty.  If  the  relay  outputs  are  used  in  an  application  requiring  continuous  high  current,  even 
below the rated values, an  appropriate contactor should be  used between the device and the alarm 
contacts. If not, main board of panel can blow or become damaged. Warranty excludes in this case. 

 

6- CONTROL BUTTONS 

Alarm silence 

If there is a gas or fire alarm at the panel, pressing 

“Alarm silence button” silences all sounder and relay 

outputs which are programmed as latching. Buzzer keeps beeping discretely and the information of sounders 
are silenced is seen on LCD screen. 

 

Buzzer silence

 

Buzzer rings in case of alarm and fault situations, to silence buzzer, press 

“Buzzer silence” button. 

 

Lamp test

 

By pressing 

“Lamp test” button, the control of all LEDs is made. 

 

Reset

 

Reset button is used to reset the system when there is a gas or fire alarm situation in the system. 

 

Up (+) and down (+) Buttons

 

“Up (+)” and “Down (-)” buttons, are used to make a pass through panel functions. 

 

Enter Button

 

“Enter” button, is used to activate the selected function. 

 

Exit Button

 

“Exit” button, is used to go back one menu up. 

 

Microprocessor reset button

 

Microprocessor, is locked when it cannot run the system and 

“System fault” in front panel is lit. In such case, 

by pressing microprocessor reset button system is  restarted. Also  after  changing system  configuration, this 
button helps to start new configuration. (Annex-A Figure 11) 

 

LCD backlight: 

LCD contrast could adjust by a trim pot. (Annex-A Figure 10) 

 

7- PANEL INDICATORS 

 

Power On

 

Under normal conditions only the green 

“Power On” LED illuminates. 

 

General Fault

 

If there is a fault on the system except for system faults, 

“General Fault” LED Illuminates with related fault 

LED. 

 

System fault

 

The 

“System Fault” LED will illuminate if the software of the panel configuration has not operated correctly. 

Microprocessor button should be used.

 

 

Inhibit active

 

Light when channels are inhibited and which channels are inhibited on LCD screen.

 

 

Low Alarm

 

Low alarm shows detectors channel low limit value if exceeds and shows the low alarm relay is active. 

 

High Alarm

 

High alarm shows detectors channel high limit value if exceeds and shows the high alarm relay is active. 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 7  

  

 

Over - Range

 

Shows the gas level in the medium exceeds a fixed high limit (21.5 mA), over-range relay is activated. 

 

General Alarm

 

Shows if there is a gas or fire alarm from the detectors connected to the channels. 

 

8- FUSES 

 

Sounder 1 Fuse (F1) 

F1 fuse; is self-resetting and activate on 500 m

А current overload. 

 

Sounder 2 Fuse (F2) 

F2 fuse; is self-resetting and activate on 500 m

А current overload.

 

 

System Fuse (F3) 

F3; is self-resetting and activates 

on 4А current overload or a short circuit 

on panel PCBs. On activation of the fuse the SMPS 24 V output fault LED indicator illuminates. 

 

Battery Fuse (F4) 

F4; is self-resetting and activates on 500 m

А current overload or a short circuit on battery inputs. Illuminating 

of the respective LED indicator on SMPS and silk screen label means the batteries are disconnected. 

 

24 V DC Auxiliary Power Supply Output Fuse (F5) 

F5; is self-resetting and activates on 500 m

А current overload. On the fuse activation the 24 V DC Fault LED 

illuminates. 

 

Channel Fuses (F6, F7, F8, F9) 

They are 100 mA self-resetting fuses. It gets activated in case of any short circuit in channels inputs. In this 
condition system takes energy from the batteries. 

 

Mains Fuse (F10) 

is  glass  type and  activates on  2

А current overload, a  short circuit or exceeding 220 V AC on mains supply 

input. On the fuse activation, the POWER FAULT LED indicator on SMPS illuminates and power to the panel 
is supplied from the batteries. 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 8  

  

9- POWERING THE PANEL 

 

9.1 Normal 

During normal mode, only green system is on LED lights. On the screen the gas levels read by channels is 

 

9.2 Alarm 

When  the  gas  detectors  exceed  the  levels  of  predetermined  threshold  levels  in  each  channel,  panel  goes 
into alarm mode. These alarms can be either low or high alarm level. In these situations each assigned output 
is activated. Pressing Reset makes the system work in initial position. 

 

9.3 Fault 

In case of  any fault condition at  the panel leads to  light 

“General Fault” LED, rings the buzzer ad fault relay 

changes  its  switch. When fault  condition disappears,  panel  automatically turns  back  to  its  normal  operating 
status. 

 

10- PANEL MENUS 

 

In normal mode, access level of the panel is 1. In order to see the panel configuration and reach the functions 
of  access  level  2,  first  you  need  to  main menu. To  do  this,  in  normal operating mode press 

“Enter”  button. 

Under the main menu there are  2  submenus. These  are 

“Visualization” and “Access level 2” menus. These 

menus are selected by using 

“Up (+)” and “Down (-)” buttons. Then, pressing “Enter” button results to enter the 

selected submenu.

 

 

10.1 Visualization 

When Visualization function is selected, pressing 

“Enter” button pops up 4 sub visualization function. 

To enter these sub-functions, function is  selected by using 

“Up (+)” and “Down (-)” buttons. Then, pressing 

“Enter” button results to enter the selected sub-function.

 

 

 

*** Visualize ***

 

Relays status 
Sounders status 
Signal levels 
Configuration 

----------------------------------------------------------------- 

Enter 

– Ok 

Exit 

–Up 

Menu 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 9  

  

10.1.1 Relay Activation Status 

 It enables to track the position of relay outputs of the panel. 

 

***  RELAYS STATUS ***

 

Low Alarm Relay: Active 
High  Alarm  Relay: Not  Active 
Over-range Relay: Not Active 
Fault Relay: Active 
------------------------------------------------------------- 
----- 
Exit 

– Pre Menu 

 

 

10.1.2 Sounder Activation Status 

 It follows whether sounder outputs are active or not. 

 

***  SOUNDERS STATUS *** 

Sounder 1 : Not active 
Sounder 2 : Active 

 

 

------------------------------------------------------------- 
----- 

Menu 

Exit 

– Pre 

 

10.1.3 Signal Levels 

 Input of each channe

l’s signal level can be tracked. 

 

 

*

 SIGNAL  LEVELS * 

 

Channel 1 : 

00.0  mA 

Channel 2 : 

05.5  mA 

Channel 3 : 

10.7  mA 

Channel 4 : 

25.5  mA 

------------------------------------------------------------- 
----- 
Exit 

– Pre Menu 

 

 

10.1.4 Configuration 

 System operation is seen from the operating configuration of channels, sounders and relays. It is composed   
 of 4 sub-functions. 

 

CONFIGURATION 

> System 

Common Relay settings 
Sounder settings 
Channel settings 

Enter 

–Ok 

Exit 

– Pre-menu 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 10  

  

10.1.4.1 System 

 In this menu, panel

’s language is shown. 

 

SYSTEM 

Language: English 
Access Level 2 Password: Active 

 

 

--------------------------------------------------------- 
---- 
Exit 

– Pre-menu 

 

 

10.1.4.2 Common relay settings 

 It is possible to check how pane

l’s relay works (latching or non-latching and N/O or N/C) 

 

 

*COMMON RELAY SETTINGS* 

Low 

Alarm Relay : Latching / NO High 
Alarm Relay: Non-latching / NC 
Over-range Relay: Latching OK / NO 
Fault Relay : Non-Latching  / NO 
--------------------------------------------------------------- 
--- 
Exit 

– Pre-menu 

 

 

10.1.4.3 Sounder settings 

 It is possible to check how pane

l’s sounder outputs operates (latching or non-latching) 

 

SOUNDER SETTINGS

Sounder 1 : Latching 
Sounder 2 : Non-latching 

 

 

------------------------------------------------------------ 

Exit 

– Pre-menu 

 

 

10.1.4.4 Channel settings 

 Operating condition of all channels are monitored 

 

*** CHANNEL SETTINGS 

*** 

> Channel 1  configuration 

Channel 2  configuration 
Channel 3 configuration 
Channel 4  configuration 

Enter 

– Ok 

Exit

–Pre-menu 

 

 For example, if channel 1 is selected, then pressing 

“Enter” makes to monitor all features of the channel. 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 11  

  

*** 

CHANNELS 

*** Channel 

1config

ıuration Detector 

measurement range : Zero 
forcing: 

2 mA condition: 
Warm-up delay : 
----------------------------------------------------------- 

Exit 

– Pre-menu 

 

 

*** CHANNELS *** 

Channel 1config

ıuration 

Fire Reset time : 

1

st 

Level Alarm position : 

1

st  

Level Alarm Entrance Value: 

1

st 

Level Alarm End Value : 

------------------------------------------------------------ 
Exit 

– Pre Menu 

 

*** CHANNELS ***

 

Channel 1 Configuration 

2

nd 

Level Alarm Position  Value : 

2

nd 

Level Alarm Entrance Value : 

 

 

------------------------------------------------------------- 
Exit - Pre Menu 

 

10.2 Access Level 2 

In order to get into the access level 2, person shall use the password 

“1111”.Password display as the 

following table. 

 

ACCESS LEVEL 2 

Enter Access Level 2 Password 

****

 

 

------------------------------------------------------------ 
Exit 

– Pre Menu 

 

In this screen, first press to 

“Up (+)” button and instead of the star “*”, number 1 comes to the end. Then by 

pressing 

“Enter “button 4 times makes the user to get in access level 2. 

 

The screen of the 

“Access Leve2” pops up, if correct password is entered, by the functions here control 

panels operating features are programmed.

 

 

*** 

ACCESS LEVEL 2  ***

 

> Inhibit 

Zeroing 
Calibration 
Test 
Configure 

------------------------------------------------------------ 
Enter 

– Ok                                      Exit – Pre 

               Menu 

 

10.2.1 Inhibit 

 By use of Inhibit function, any channel or all channel of the control panel can be inhibited. 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 12  

  

*** 

INHIBIT***

 

> All 

:Inhibition not active 

Channel 1   :Inhibition not active 
Channel 2   :Inhibition not active 
Channel 3   : Inhibition Active 
Channel 4   : Inhibition Active 

------------------------------------------------------------ 
Enter 

– Ok 

Exit  - Pre 

Menu 

 

 

Using 

“Up (+)” and “Down (-)” buttons channel which wants to be inhibited is selected. The sign ‘>’ on the left 

of  the  channel  is  moved).  Then  pressing  enter  selects  the  channel  you  want  to  be  inhibited.  (On  the  right 
side of the channel the sign 

‘<’ appears. In this position pressing ‘Down (-)’ button “Inhibited is active” text is 

screened. Hence  channel  is  inhibited. If  the  channel  inhibited  before, then  selecting  channel  using 

“Up(+)” 

button changes the text 

“Inhibited is active” into ““Inhibited is inactive” and channel is no longer inhibited. 

 

10.2.2 Zeroing 

 When zero adjustment wants to apply channels, this function is used. 

 

*** 

ZEROING***

 

 

Select the channel  for zeroing 

 

#1:Channel1 
------------------------------------------------------------ 
Enter 

–Ok 

Exit 

– Pre Menu 

 

First of all the channel which want to be zeroed is selected. To do that 

“Up (+)” and “Down (-)” buttons are 

used and after determining the specific channel, press 

“Enter” button to get into the zeroing submenu. 

 

*** 

ZEROING***

 

#1:Channel1 
Zeroing channel is inhibited!!! 
When get ready press 

“Enter” 


------------------------------------------------------------- 

Exit 

– Pre Menu 

 

To start zeroing, press 

“Enter” once again and system performs zeroing of the related channel. 

 

*** 

ZEROING***

 

#1:Channel1 
Zeroing channel is inhibited!!! 
20 
Input fault 
-------------------------------------------------------------- 

Exit 

– Pre Menu 

 

*** 

ZEROING***

 

#1:Channel1 
Zeroing channel is inhibited!!! 

Zeroing has been done 
-------------------------------------------------------------- 

Exit 

– Pre Menu 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 13  

  

10.2.3 Calibration 

 In order to make the calibration of the detectors, this function is used. It composes of 3 sub-functions. 

 

*** 

CALIBRATION ***

 

> Calib. Channel. 

Calib. Level: 
Calibrate 

 

------------------------------------------------------------ 
Exit 

– Pre Menu 

 

First of  all the channel which want to be calibrated is  selected. To do that the sign 

“>” should be in the left 

side of the sub-function 

“Calib Channel”. Press “Enter”. (The sign “<” will be seen on the right side of the sub- 

function 

“Calib. Channel). Using “Up (+)” and “Down (-)” buttons channel name is found. By pressing “Enter 

Butt

on” the related channel is selected. 

After  that  calibration  level  shall  be  adjusted.  To  do  this,  again,  using 

“Up  (+)”  and  “Down  (-)”  buttons 

“Calibration  level”  sub-function  is  selected.  When  you  press  “Enter”  button,  on  the  right  side  of  the 
“Calibration Level” text  the  sign “<” is  seen. In  this  position, calibration level value is  adjusted between 25 
and 100. To confirm the value press 

“Enter Button”. 

 

Once  you  done  with  these  adjustments, calibration process  can  be  started.  For  calibration 

“Calibrate” sub- 

function is selected and   then 

“Enter” is pressed. In such setting the screen is shown as: 

 

Calibration process gets started by pressing 

“Enter” button. 

 

*** 

CALIBRATION ***

 

Calibrating channel is inhibited!!! 

When get ready press 

“Enter” 

 

 

 

Calibration process gets started by pressing 

“Enter” button. 

 

 

a)  IF CALIBRATION NOT SUCCEEDED 

 

*** 

CALIBRATION ***

 

 

Calibrating channel is inhibited!!! 
30 
Input fault 
------------------------------------------------------------ 
Exit-Ana Menu 

 

 

b)   IF CALIBRATION SUCCEEDED 

 

*** 

CALIBRATION ***

 

 

Calibrating channel is inhibited!!! 
50 
Calibration has been done 
Exit after gas level lowered 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 14  

  

10.2.4 Test 

This function enable us test the relays and sounder outputs. 

 

*** TEST *** 
> Relay Test 

Sounder Test 

 

 

------------------------------------------------------------ 
Exit-Main Menu 

 

10.2.4.1 Relay Test 

In the Relay test function, the current status of the relays are monitored at the panel. 

 

*** RELAY TEST***

 

Low Alarm Relay: Active 
High Alarm Relay: Not Active 
Over-range Relay: Active 
Fault  Relay: Not Active 

 

------------------------------------------------------------- 

Enter 

– OK 

Exit 

– Pre Menu 

 

 

On this screen, it is possible to select the relay which you may want to test, using arrow buttons. (On the left 
‘>’ sign should be next to that relay.) By pressing “Enter” relay is selected. (On the left of the relay ‘<’ sign is 
present.) After selecting relay, press 

“Up(+)” button to test it. 

 

10.2.4.2 Sounder Test

 

When you enter the sounder test function, the current condition of the sounders is monitored. 

 

*** 

SOUNDER TEST***

 

>  Sounder 1: 

Active 

Sounder 2: 

Not Active 

 

 

------------------------------------------------------------ 
Enter 

– OK 

Exit 

– Pre Menu 

 

On this screen, it is possible to select the sounder output which you may want to test, using arrow buttons. 
(On the left 

‘>’ sign should be next to that sounder output.) By pressing “Enter” sounder output is selected. 

(On the left of the sounder 

‘<’ sign is present.) After selecting sounder output, press “Up(+)” button to test 

sounder then press 

“Down(-) button to exit from the test.

 

 

10.2.5 Configure 

By using this function, system operating features are programmed. 

 

*** 

CONFIGURATION 

*** 

> System 

Common Relay Settings 
Sounder Settings 
Channel Settings 

------------------------------------------------------------- 
Enter 

– Ok 

Exit 

– Pre-Menu 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 15  

  

10.2.5.1 System

 

Panel: Network Address, communication rate, panel name, serial number and panel language are adjusted 
by the help of system menu. 

 

*** 

SYSTEM 

*** 

>   Language: English 

Access Level 2  Password: Active 

 

 

-------------------------------------------------------------- 
Enter 

– Ok 

Exit 

– Pre Menu 

 

 

10.2.5.2 Common Relay Settings

 

In this sub-function, relays operating structure are set as latching, non-latching or latching acceptance of 
operating status and N/O or N/C is adjusted. 

 

*** 

COMMON  RELAY SETTINGS 

*** 

> Low  Alarm  Relay 

High  Alarm  Relay 
Over-range Relay 

 

------------------------------------------------------------ 

Enter 

– OK 

Exit 

– Pre Menu 

 

On this screen, it is possible to select the relay which you may want to adjust setting, using 

“Up(+)” and 

“Down(-)”arrow buttons. (On the left ‘>’ sign should be next to that relay.) By pressing “Enter” relay is 
selected. In this condition, this screen is monitored;

 

 

*** 

COMMON  RELAY SETTINGS 

*** 

Low  Alarm Relay 
> Relay Type: Latching 

Normally :Open 

 

------------------------------------------------------------ 
Enter 

– OK 

Exit 

– Pre Menu 

 
 

“Relay Type” Sub-function: 

By this sub-function, relay

’s operating conditions can be selected as latching 

non-latching and latching acceptance operating status. These features can be defined as below: 

 

-

Latching: 

W hen  the  gas  level  in  the  medium,  exceeds  the  pre-determined  threshold  value  for  that 

channel, relay gets activated. The gas level even then lowers than the threshold value; relay does not get 
back to its previous position. In order to make the relay turns back to its previous position, 

“Alarm Silence” 

button should be used. 

-

Non-Latching: 

When  the  gas  level  in the  medium, exceeds  the  pre-determined threshold value for  that 

channel, The gas level even then lowers than the threshold value; relay gets back to its previous position 
without any interfering to the system. 

-

Latching Accept: 

When the gas level in the medium, exceeds the pre-determined threshold value for that 

channel.  When  system  is  in  Alarm  condition,  it  may  possible  to  turn  back  the  relay  back  its  previous 
condition. To do that 

“Latching Accept” is selected and then press to “Alarm Silence” button. Additionally, 

the operating condition of the relay whether normally Open or normally closed is set from tjis sub-function. 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 16  

  

10.2.5.3 Sounder settings 

The sounder outputs of the control panel are adjusted.

 

*** 

SOUNDER SETTINGS 

* ** 

> Sounder 1 : Latching 

Sounder 2 : Non-latching 

 

 

------------------------------------------------------------ 

Enter 

– OK 

Exit 

– Pre Menu 

 

On this screen, it is possible to find the sounder output which you may want to adjust setting, using 

“Up(+)” 

and 

“Down(-)”arrow buttons. (On the left ‘>’ sign should be next to that sounder output.) By pressing “Enter” 

sounder  output  is  selected.  After  selecting  sounder  output,  pressing 

“Up(+)” button  enables to  select  the 

sounder  output  as 

“latching”,  “non-latching”  or  “latching  accept”.  These  operating  features  were  just 

described on section 10.2.5.2. 

 

10.2.5.4 Channel settings 

The operating features of the channels of the control panel are adjusted.

 

*** CHANNEL SETTINGS 

*** 

>  Channel  1  configuration 

Channel  2  configuration 
Channel  3  configuration 
Channel 4 configuration 

------------------------------------------------------------ 
Enter 

– OK 

Exit 

– Pre Menu 

 

On this screen, it is  possible to find the channel which you  may want to adjust setting, using 

“Up(+)” and 

“Down(-)”arrow buttons. (On the left ‘>’ sign should be next to that channel.) By pressing “Enter” channel is 
selected. In this condition, this screen is monitored as; 

 

*** CHANNEL SETTINGS 

*** 

Channel 1  configuration 

>  Device Type: DET 4-20 Source 

Channel Name : Channel 1 
Zone Name :Mavili Elektronik 
Measuring Unit: % LEL 

------------------------------------------------------------ 
Enter 

– OK 

Exit 

– Pre Menu 

 

· Using “Type” function, detector type is  selected. “Fire  4-20  Sink”, “Fire 4-20 Source”, “Detector 4-20 
Sink

”, “Detector 4-20 Source”, “Fire Conventional”, “ESU” and “None”  features can be selected. 

·Using “Name” function, panel name can be written. 
·Using “Zone” function, the zone name of the control panel can be given. 
·Using “Unit” function, gas measuring unit can be selected as: “%LEL”, “PPB”, “PPM”, “%VOL” and “FIRE”.

 

 

After adjusting these settings press 

“Down (-)” button to see the upcoming screen. 

 

*** CHANNEL SETTINGS 

*** 

Channel 1  configuration 

>  Detector Measuring Range: 9999 

Zero Suppression: Active 
2mA Status: Fault 
Warm-Up Delay: 120 sec. 

 

------------------------------------------------------------ 
Enter 

– OK 

Exit 

– Pre Menu 

·By “Measuring Range” function, detector’s gas measuring range is estimated. 
·By “Zero suppression” function, it is selected that zeroing process whether active or not. 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 17  

  

·By “2mA detection” function, in case of decreasing current which comes from detector or converter card, the 
system response is determined.  In this condition system may give fault warning, notification warning or 
cannot be counted as a warning status. 
·By “Warm-up delay” function, it is told to the control panel that, in the start –up session, the signals coming 
from the detectors cannot be evaluated by the panel. This is because detector will have more stable values 
after warm-up time. Hence they will measure accurate values. 

 

After adjusting these settings press 

“Down (-)” button to see the upcoming 3

rd 

screen. 

 

*** CHANNELS 

*** 

Channel 1 
configuration 

> Fire Reset Time : Alarm 

L1 Direction : Alarm L1 
On Threshold: Alarm L1 
Off Threshold: 

------------------------------------------------------------ 
Enter 

– OK 

Exit 

– Pre Menu 

 

·“Fire Reset Time”: Function that during fire alarm condition, when pressed to “Reset”, the determination of 
interruption time of the energy of the channel which detector connected to that channel is adjusted. 

 

· “Low  alarm  direction”:  Function  that  estimates  the  sensitivity  of  low  alarm  warning  as  increasing  or 
decreasing level of the gas in the medium. 
· “Low alarm opening level” Function that determines the threshold of  gas level of  the low alarm warning 
value. 

 

·“Low  alarm  closing  level”:  Function  that  determines  the  gas  level,  when  panel  pass  from  low  alarm  to 
warning to normal status. 

 

After adjusting these settings press 

“Down (-)” button to see the upcoming 4

th 

screen. 

 

*** CHANNELS 

*** 

Channel 1 
configuration 

> 2

nd 

level Alarm Direction: 

2

nd 

level Alarm Input Value: 

 

------------------------------------------------------------ 

Enter 

– OK 

Exit 

– Pre Menu 

 

·“High  alarm  direction”  Function  that  estimates  the  sensitivity  of  high  alarm  warning  as  increasing  or 
decreasing level of the gas in the medium. 
·“High alarm opening level” Function that determines the threshold of gas level of the high alarm warning 
value. 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 18  

  

11 – OPERATING WITH REPEATER PANEL AND RELAY MODULE 

 

MG-400 Series Control Panel has appropriate connections for repeater panel and relay module for each 
zone output. Yet these features are not available to use currently. 

 

12- SPECIFICATIONS: 

 

12.1 Mechanical Features: 
 

Dimensions (mm)

 

400 x 300 x 100 mm 

Weight (excl. battery)

 

5.3 kg 

Body

 

Panel Box; 1.2 mm  front  1.5 mm DKP 

Operating Temperature

 

(-10

ºC)- (+ 55ºC) 

Relative Humidity

 

% 0  - 95 

Mounting

 

Surface mounting 

Cable Inputs

 

Upper and back inputs 

 

12.2 Electrical Features: 

 

Gas Channel

 

Operating Voltage

 

24 V DC 

Battery

 

2 x 12 V 7Ah 

Supply Voltage

 

220 V AC 50 Hz 

Sounder Output

 

2 x (500 mA 24 V DC) 

24V DC Output

 

500 mA 24 V DC 

Extinguishant Output

 

500 mA 24 V DC 

Low Alarm Relay

 

30 V DC 8 A, 250 V AC 10 A N/K 

High Alarm Relay

 

30 V DC 8 A, 250 V AC 10 A N/K 

Over-range Relay

 

30 V DC 8 A, 250 V AC 10 A N/K 

Fault Relay

 

30 V DC 8 A, 250 V AC 10 A N/K 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 19  

  

 

 

ANNEX-A CONNECTION SCHEME  OF  THE PANEL 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 


background image

KK-642.014 Rev.No:1  01.08.12                                                                                                                                                             Page | 20  

  

 
 
ANNEX-B  PANEL DIMENSIONS