N100

plus

 Inverter RS485 Interface 

Instruction Manual 

 

 

 

 

 

 

 

 

 

 

 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

Contents 

1. 

RS485 Communication function .....................................................................................................1 

1.1  Communication function........................................................................................................1 

1.1.1  Interface Cable Pin Arrangement .............................................................................1 

1.1.2  Interface Cable Pin Arrangement .............................................................................2 

1.1.3  RS485 Communication specification ........................................................................3 

1.1.4  RS485 Communication setting in Inverter................................................................3 

1.1.5  Communication order................................................................................................4 

1.2  Communication protocol .......................................................................................................4 

1.2.1  Inverter read frame...................................................................................................5 

1.2.2  Request frame for setting parameter .......................................................................6 

2. 

Example of Transmit/Receive Data frame.................................................................................. 11 

2.1  Read Request & Response Data ........................................................................................ 11 

2.1.1  A prior condition .................................................................................................... 11 

2.1.2  Example 1 

 Output frequency Monitoring (Function code : D01) ....................... 11 

2.1.3  Example 2 

 Output frequency (Function code : F01) .......................................... 12 

2.1.4  Example 3 

 Acceleration time (Function code : F02).......................................... 12 

2.2  Setting Request & Response Data ..................................................................................... 13 

2.2.1  A prior condition .................................................................................................... 13 

2.2.2  Output frequency setting (Function code : F01) ................................................... 13 

2.2.3  Example 4 

 Acceleration time 1 setting (F02) .................................................... 13 

2.2.4  Example 5 

 Deceleration time 1 setting (F03) .................................................... 13 

2.3  Frequency Command.......................................................................................................... 14 

2.3.1  A prior condition .................................................................................................... 14 

2.3.2  Example 6 

 Frequency Command (In case of 60Hz) ........................................... 14 

2.3.3  Example 7 

 Frequency Command (In case of 50Hz) ........................................... 14 

2.4  RUN command parameter .................................................................................................. 15 

2.4.1  A prior condition .................................................................................................... 15 

2.4.2  Example 8 

 FWD(Forward) RUN Command......................................................... 15 

2.4.3  Example 9 

 REV(Reverse) RUN Command.......................................................... 15 

2.4.4  Example 10 

 STOP Command .............................................................................. 16 

 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

N100_Inverter RS485 Interface Manual(English).doc

 1 

 

1. 

RS485 Communication function 

1.1 

Communication function 

Communication circuit for RS485 is built in N100 Inverter. 

It  is  possible  to  control  1~32  Inverters  (Slave)  from  a  main  control  device  (Master)  by 
using RS485 serial communication is supported. 

 

Fig. 1 RS485 Serial network 

 

1.1.1 

Interface Cable Pin Arrangement 

 

Fig. 2 Cable Pin configuration 

 

+

-

+

-

RS 232-485 

converter

Description 

RJ45 Pin No. 

Cable Pin configuration 

TX/RX -

 

6

 

TX/RX    +

 

3

 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

N100_Inverter RS485 Interface Manual(English).doc

 2 

1.1.2 

Interface Cable Pin Arrangement 

 

Fig. 3 PC(or PLC) ~ Inverter Wiring Diagram 

PC(or PLC) ~ Inverter Wiring Diagram 

PC

PLC

RS232

RS485

RS232 

To RS485

Converter

Note 
 

If the PLCs have a RS485 communication port, don

t use the 

converter (RS232 to RS485 converter) between the PLCs 
and inverter. 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

1.1.3 

RS485 Communication specification 

 

Item 

Specification 

Notes 

Communication 
interface 

RS485 

 

Communication methods  Half duplex communication methods 

 

Transmission speed 
(Baud Rate) 

9600[BPS] 

 

Start methods 

Response for the external read, write 
command 

The inverter operates only as 
slave. 

Transmission code 

Binary code 

 

Data bit 

8[bit] 

 

Parity 

No parity/even/odd 

 

Stop bit 

1[bit] 

 

Connect form 

1:N (N=Maximum 32) 

 

Main function 

Fleming/CRC/CMD/MAXREQ/Parameter

 

Table 1 RS485 Communication specification 

 

1.1.4 

RS485 Communication setting in Inverter 

The following setting are required to operate RS485 communication 

 

Function 

code 

Set item 

Initial data 

Data 

Description 

b17 

Communication Number 

Inverter Address No. 1 

(Address : 1 ~ 32) 

A01 

Frequency commanding 

(Multi-speed 
commanding method) 

0 : Keypad potentiometer 

1 : Control terminal input 

2 : Standard operator 

3 : Remote operator   
      (Communication) 

A02 

RUN commanding 

0 : Standard operator 

1 : Control terminal input 

2 : Remote operator 
      (Communication) 

Table 2 RS485 Communication setting 

 

N100_Inverter RS485 Interface Manual(English).doc

 3 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

1.1.5 

Communication order 

The  flow  of  the  communication  protocol  between  an  external  control  device  and  an 
inverter is shown below in the time diagram. 

 

 

 

Fig. 4 Communication order 

Devices 

External control 

Frame 2 

(setting with operator) 

Waiting time 

Frame 1 

Inverter 

 

Frame start : 

Frame start is recognized by signal line data transmitted.   

Frame completion:  Frame  completion  is  recognized  by  no  data  during  correspond  4, 

5-character time. 

Frame 1:  Transmit from external controller to inverter.   

Frame 2:  Indication reflects from inverter to external controller. 

Frame 2 in inverter displays as the signal that inverter receiving Frame 1 
and recognizes a suitable frame and responds, and don

t output actively. 

 

1.2 

Communication protocol 

ModBus protocol that applies Query-Response Cycle method is used in the communication. 

The communication network is controlled by the master equipment, and it is operated by 
the  method  that  the  slave  equipment  reply  from  the  transmission  request  of  the  master 
equipment. ModBUS communication frame type and form is as follows. 

N100_Inverter RS485 Interface Manual(English).doc

 4 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

1.2.1 

Inverter read frame 

It requires 1~8 parameters of Inverter. 

 

(1)  External controller transmit frame 

 

Communication 

number 

Command 

parameter 

Parameter 

count 

CRC Hi 

CRC Lo 

 

Clause 

Description 

Data size 

Specifications 

Communication 
number 

Inverter communication 
number 

1 byte 

1~32 

Command 

Frame type 

1 byte 

0x03 

Parameter 

Parameter 

2 byte 

1st byte : Group 

2nd byte : index (Note1) 

Parameter 
number 

Request parameter 

Number 

2 byte 

1st byte : 0x00 

2nd byte : N(0x01~0x08) 

CRC Hi 

1 byte 

Higher 8bit of 16 bit CRC 

CRC Lo 

1 byte 

Lower 8bit of 16 bit CRC 

Table 3 External controller transmit frame 

 

(2)  Inverter response frame 

 

Communication 

number 

Order 

Byte 

number 

Data1 

………

 

Data N 

CRC Hi 

CRC Lo

 

Clause 

Description 

Data size 

Specifications 

Communication 
number 

Inverter communication 
number 

1 byte 

1~32 

Command 

Frame type 

1 byte 

0x03 

Request Byte 

Data byte number 

1 byte 

Request parameter number ⅹ 2 

Data 1 

Parameter 1 

2 byte 

Parameter value 

Data N 

Parameter N 

2 byte 

Nth parameter value 

CRC Hi 

1 byte 

Higher 8bit of 16bit CRC 

CRC Lo 

1 byte 

Lower 8bit of 16bit CRC 

Table 4 Inverter response frame 

  Frame size = 5byte (Communication number + Command + Request Byte + CRC H + 

CRC L) + Request parameter number 

ⅹ 

2byte (Data1 + Data2 + 

.. + 

Data N) 

 

N100_Inverter RS485 Interface Manual(English).doc

 5 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

1.2.2 

Request frame for setting parameter 

Setting 1 parameter and command (note3) of Inverter 

 

(1)  External transmit frame 

 

Communication 

number 

Order 

Parameter 

Data 

CRC Hi 

CRC Lo 

 

Clause 

Description 

Data size 

Specifications 

Communication 
number 

Inverter communication 
number 

1 byte 

1~32 

Order 

Frame type 

1 byte 

0x06 

Parameter 

Parameter 

2 byte 

1st byte : Group 

2nd byte : index (Note1) 

Data 

Data 

2 byte 

Setting value (Note2) 

CRC Hi 

1 byte 

Higher 8bit of 16bit CRC 

CRC Lo 

1 byte 

Lower 8bit of 16bit CRC 

Table 5 External transmit frame 

 

(2)  Inverter response frame 

 

Communication 

number 

Order 

Parameter 

Data 

CRC Hi 

CRC Lo 

 

Clause 

Description 

Data size 

Specifications 

Communication 
number 

Inverter communication 
number 

1 byte 

1~32 

Order 

Frame type 

1 byte 

0x06 

Parameter 

Parameter 

2 byte 

1st byte : Group 

2nd byte : index (Note1) 

Data 

Data 

2 byte 

Setting value is response 
(note 4) 

CRC Hi 

1 byte 

Higher 8bit of 16bit CRC 

CRC Lo 

1 byte 

Lower 8bit of 16bit CRC 

Table 6 Inverter response frame 

N100_Inverter RS485 Interface Manual(English).doc

 6 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

(3)  Parameter setting [Note 1] 

 

Basic parameter 

1st byte : Each group is setting. 

 

Group 

1

st

 byte 

Group 

1

st

 byte 

0x01 

0x05 

0x02 

0x06 

0x03 

0x07 

0x04 

Table 7 Basic parameters (1

st

 byte) 

 

2

nd

 byte : Parameter number setting 

Ex) The case of A60 parameter reading or writing 

1

st

 byte : 0x03 

2

nd

 byte : 0x3C 

 

 

Trip information 

Trip  information  is  4  parameters.  (output  frequency,  output  current,  DC  link 
voltage at trip occurs) 

 

 

Trip 

information

Previous 

first trip 

Previous 

second trip

Previous 
third trip 

Trip count

1st byte 

0x01 

0x01 

0x01 

0x01 

0x01 

2nd byte 

0x0D 

0x11 

0x15 

0x19 

0x1D 

Table 8 Trip information List (1

st

 byte, 

2

nd

 byte)

 

 

 

Trip information items 

Trip data 

Trip contents 

Trip data

Trip contents 

Over current trip 

Electric thermal trip 

Over voltage trip 

Outside trip 

Under voltage trip 

EEROM trouble 

Arm short trip 

10 

Communication trouble 

Reserved 

11 

USP trip 

Inverter over heat trip 

12 

GF trip 

Table 9 Trip information items 

 

N100_Inverter RS485 Interface Manual(English).doc

 7 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

(4)  Data value setting [Note 2] 

Data value is transmitted except decimal point. 

 

Ex1) Output frequency 

Parameter value 

Communication data 

Converted hexadecimal value 

60.00Hz 

6000 

1st byte : 0x17 

2nd byte : 0x70 

 

Ex 2) acceleration/deceleration time 

Parameter value 

Communication data 

Converted hexadecimal value 

10.0sec 

100 

1st byte : 0x00 

2nd byte : 0x64 

 

(5)  Special parameter [Note 3] 

A  special  parameter  is  used  to  operating  and  commanding  a  frequency  value  for  the 
basic parameter. 

 

Run command Parameter 

1st byte : 0x00 

2nd byte : 0x02 

Setting data 

1st byte 

Bit7 

Bit6 

Bit5 

Bit4 

Bit3 

Bit2 

Bit1 

Bit0 

Reserved 

2

nd

 byte 

Bit7 

Bit6 

Bit5 

Bit4 

Bit3 

Bit2 

Bit1 

Bit0 

Reserved 

RST 

REV 

FWD 

 

Data value on RUN command 

1

st

 Byte 

2

nd

 Byte 

                        Byte & Bit 

Command 

7

6

5

4

3

2

1

0

7

6  5  4  3  2

1

0

Forward RUN (0x01) 

0

0

0

0

0

0

0

0

0

0  0  0  0  0

0

1

Reverse RUN (0x02) 

0

0

0

0

0

0

0

0

0

0  0  0  0  0

1

0

STOP (0x00) 

0

0

0

0

0

0

0

0

0

0  0  0  0  0

0

0

 

N100_Inverter RS485 Interface Manual(English).doc

 8 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

 

Frequency command Parameter 

1st byte : 0x00 

2nd byte : 0x04 

Setting data 

Output frequency

100 

Ex)  The case of output frequency command is 60 Hz 

Data 6000 transmit 
1st byte : 0x17 
2nd byte : 0x70 

 

(6)  Response data in Prameter setting 

Note)  Response frame when you send a command for setting a parameter 

When the data cannot be stored due to the attempt to store data while the unit 
is  running,  the  setting  data  will  not  be  stored  and  the  original  data  will  be 
responded. 

 

(7)  16bit CRC generation 

The step of CRC-16 generation is as follows: 

z

 

All of 16-bit register is 1. 0xffff 

z

 

The exclusive OR of 16-bit register and 8-bit register. 

z

 

Shift right side 1bit a 16-bit register 

z

 

If the result of step 3 is 1, exclusive OR 16-bit register and 0xa001. 

z

 

Execute 8 times step 3 and step 4. 

z

 

Execute step 2~6 until data completion 

z

 

Exchange the step 6 result of higher 8bit and lower 8bit. 

N100_Inverter RS485 Interface Manual(English).doc

 9 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

N100_Inverter RS485 Interface Manual(English).doc

 10 

 

Ex) The case of d001 output frequency reading. 

Byte1 

Byte2 

Byte3 

Byte4 

Byte5 

Byte6 

Communication 

number 

Command 

Parameter 

Parameter number 

0x01 

0x03 

0x01 

0x01 

0x00 

0x01 

 

The sequence of addition Byte(0x01) 

16Bit Register

 

 

MSB

 

 

 

Flag

 

(Exclusive OR) 

1111 

1111 

1111 

1111 

 

01 

0000 

0001 

 

 

 

 

1111 

1111 

1111 

1110 

 

Shift1 

0111 

1111 

1111 

1111 

 

Shift2 

0011 

1111 

1111 

1111 

Polynomial 

1010 

0000 

0000 

0001 

 

 

1001 

1111 

1111 

1110 

 

Shift3 

0100 

1111 

1111 

1111 

 

Shift4 

0010 

0111 

1111 

1111 

Polynomial 

1010 

0000 

0000 

0001 

 

 

1000 

0111 

1111 

1110 

 

Shift5 

0100 

0011 

1111 

1111 

 

Shift6 

0010 

0001 

1111 

1111 

Polynomial 

1010 

0000 

0000 

0001 

 

 

1000 

0001 

1111 

1110 

 

Shift7 

0100 

0000 

1111 

1111 

 

Shift8 

0010 

0000 

0111 

1111 

Polynomial 

1010 

0000 

0000 

0001 

 

 

1000 

0000 

0111 

1110 

 

Byte1~6 

CRC of operation 

results 

0x01 

0x03 
0x01 
0x01 
0x00 
0x01 

0x807e 

0x2140 
0x30e1 
0x8831 
0xd449 
0x36d4 

 

It exchanges higher 8bit of the final result 0x36d4. 

 0xd436 

Byte7 : CRC higher 8Bit = 0xd4 

Byte8 : CRC lower 8Bit = 0x36 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

2.  Example of Transmit/Receive Data frame 

2.1 

Read Request & Response Data 

2.1.1 

A prior condition 

(1)  Communication number  : 

(Inverter address 1) 

(2) Command 

03  (Read 

request) 

(3) Parameter 

count 

(Parameter 

Q’ty) 

 

2.1.2 

Example 1 – Output frequency Monitoring (Function code : D01) 

(1) Transmit 

Data 

Transmit (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Parameter 

Count 

CRC 16 

Hi          Lo 

010301010001D436 

01 03 01 01 00 01 D4 36 

 

(2)  Response Data (In case of D01 = 0.00Hz) 

Response (7Byte) 

Com.

Num.

Com-

mand

Byte 

Q’ty 

Data 

CRC 16 

Hi          Lo 

0103020000B844 01  03  02  00 

00 B8 44 

Data Description 

0x16

3

 + 0x16

2

 + 0x16

1

 + 0x16

0

 = 0(Communication Data) 

Î

 divide by 100 

Î

 0.00Hz (Parameter value)

 

 

(3)  Response Data (In case of D01 = 60.00Hz) 

Response (7Byte) 

Com.

Num.

Com-

mand

Byte 

Q’ty 

Data 

CRC 16 

Hi          Lo 

0103021770B650 01  03  02  17 

70 B6 50 

Data Description 

1x16

3

 + 7x16

2

 + 7x16

1

 + 0x16

0

 = 6000(Communication Data)

Î

 divide by 100 

Î

 60.00Hz (Parameter value)

 

 

N100_Inverter RS485 Interface Manual(English).doc

 11 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

2.1.3 

Example 2 – Output frequency (Function code : F01) 

(1) Transmit 

Data 

Transmit (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Parameter 

Count 

CRC 16 

Hi          Lo 

010302010001D472 

01 03 02 01 00 01 D4 72 

 

(2)  Response Data (In case of F01 = 60.0Hz) 

Response (7Byte) 

Com.

Num.

Com-

mand

Byte 

Q’ty 

Data 

CRC 16 

Hi          Lo 

0103021770B650 01  03  02  17 

70 B6 50 

Data Description 

1x16

3

 + 7x16

2

 + 7x16

1

 + 0x16

0

 = 6000(Communication Data)

Î

 divide by 100 

Î

 60.00Hz (Parameter value)

 

 

(3)  Response Data (In case of F01 = 50.00Hz) 

Response (7Byte) 

Com.

Num.

Com-

mand

Byte 

Q’ty 

Data 

CRC 16 

Hi          Lo 

0103021388B512 01  03  02  13 

88 B5 12 

Data Description 

1x16

3

 + 3x16

2

 + 8x16

1

 + 8x16

0

 = 5000(Communication Data)

Î

 divide by 100 

Î

 50.00Hz (Parameter value)

 

 

2.1.4 

Example 3 – Acceleration time (Function code : F02) 

(1) Transmit 

Data 

Transmit (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Parameter 

Count 

CRC 16 

Hi          Lo 

010302010001D472 

01 03 02 02 00 01 24 72 

 

(2)  Response Data (In case of F02 = 10.0sec) 

Response (7Byte) 

Com.

Num.

Com-

mand

Byte 

Q’ty 

Data 

CRC 16 

Hi          Lo 

0103020064B9AF 01  03  02  00 

64 B9 AF 

Data Description 

0x16

3

 + 0x16

2

 + 6x16

1

 + 4x16

0

 = 100(Communication Data) 

Î

 divide by 10 

Î

 10.0sec (Parameter value)

 

 

N100_Inverter RS485 Interface Manual(English).doc

 12 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

2.2 

Setting Request & Response Data 

2.2.1 

A prior condition 

(1)  Communication number  : 

01 

(Inverter address 1) 

(2) Command 

06  (Setting 

request) 

 

2.2.2 

Output frequency setting (Function code : F01) 

Please refer to 

Clause 2.3 Frequency command on page 13

 

2.2.3 

Example 4 – Acceleration time 1 setting (F02) 

(1)  Transmit Data    (In case of 10sec) 

Transmit (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

0106020200642859 

01 06 02 02 00 

64 28 59 

Data Description 

0x16

3

 + 0x16

2

 + 6x16

1

 + 4x16

0

 = 100 (Communication Data) 

Î

 divide by 10 

Î

 10.0sec (Parameter value)

 

 

(2) Response 

Data 

Response (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

0106020200642859

 

01 06 02 02 00 

64 28 59 

 

2.2.4 

Example 5 – Deceleration time 1 setting (F03) 

(1)  Transmit Data    (In case of 30sec) 

Transmit (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

01060203012C783F 

01 06 02 03 01 

2C 78 3F 

Data Description 

0x16

3

 + 1x16

2

 + 2x16

1

 + 12x16

0

 = 300 (Communication Data) 

Î

 divide by 10 

Î

 30.0sec (Parameter value)

 

 

(2) Response 

Data 

Response (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

01060203012C783F 

01 06 02 03 01 

2C 78 3F 

 

N100_Inverter RS485 Interface Manual(English).doc

 13 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

2.3 

Frequency Command 

 

2.3.1 

A prior condition 

(1)  Communication number  : 

01 

(Inverter address 1) 

(2) Command 

06  (Setting 

request) 

(3) Parameter 

0004 

 

2.3.2 

Example 6 – Frequency Command (In case of 60Hz) 

(1)  Transmit Data    (In case of 60.00Hz) 

Transmit (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

010600041770C61F 

01 06 00 04 17 

70 C6 1F 

Data Description 

1x16

3

 + 7x16

2

 + 7x16

1

 + 0x16

0

 = 6000 (Communication Data) 

Î

 divide by 100 

Î

 60.00Hz (Parameter value)

 

 

(2) Response 

Data 

Response (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

010600041770C61F 

01 06 00 04 17 

70 C6 1F 

 

2.3.3 

Example 7 – Frequency Command (In case of 50Hz) 

(1)  Transmit Data    (In case of 50.00Hz) 

Transmit (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

010600041388C55D 

01 06 00 04 13 88 C5 5D 

Data Description 

1x16

3

 + 3x16

2

 + 8x16

1

 + 8x16

0

 = 5000 (Communication Data) 

Î

 divide by 100 

Î

 50.00Hz (Parameter value)

 

 

(2) Response 

Data 

Response (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

010600041388C55D 

01 06 00 04 13 

88 C5 5D 

 

N100_Inverter RS485 Interface Manual(English).doc

 14 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

 

2.4 

RUN command parameter 

2.4.1 

A prior condition 

(1)  Communication number  : 

(Inverter address 1) 

(2) Command 

06  (Setting 

request) 

(3) Parameter 

0002 

 

2.4.2 

Example 8 – FWD(Forward) RUN Command 

(1) Transmit 

Data  

Transmit (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

010600020001E9CA 01  06  00  02  00 

01 E9 CA 

Data Description 

0001 : FWD,   0002 : REV,   0000 : STOP 

 

(2) Response 

Data 

Response (7Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

010600020001E9CA 

01 06 00 02 00 

01 E9 CA 

 

2.4.3 

Example 9 – REV(Reverse) RUN Command 

(1) Transmit 

Data  

Transmit (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

010600020002A9CB 01  06  00  02  00 

02 A9 CB 

Data Description 

0001 : FWD,   0002 : REV,   0000 : STOP 

 

(2) Response 

Data 

Response (7Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

010600020002A9CB 

01 06 00 02 00 

02 A9 CB 

 

N100_Inverter RS485 Interface Manual(English).doc

 15 

 


background image

N100

plus

 Inverter RS485 Interface Instruction Manual

 

N100_Inverter RS485 Interface Manual(English).doc

 16 

 

2.4.4 

Example 10 – STOP Command 

(1) Transmit 

Data  

Transmit (8Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

010600020000280A 

01 06 00 02 00 

00 28 0A 

Data Description 

0001 : FWD,   0002 : REV,   0000 : STOP 

 

(2) Response 

Data 

Response (7Byte) 

Com.

Num.

Com-

mand

Parameter 

Data 

CRC 16 

Hi          Lo 

010600020000280A

 

01 06 00 02 00 

00 28 0A