PDF User Manual

  1. Home
  2. Manuals
  3. GE PACSystems RX3i IC695ACC403 Quick Start Manual

GE PACSystems RX3i IC695ACC403 Quick Start Manual

GFK-3000A

Made by: GE
Type: Quick Start Guide
Category: Controller
Pages: 17
Size: 0.51 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

GE 

For Public Disclosure 

Automation & Controls 
Programmable Control Products 

 

PACSystems* RX3i 
Rackless Energy Pack 
IC695ACC403 
Quick Start Guide 

 

GFK-3000A 

 

July 2018 

 

 


background image

 

GFK-3000A 

IC695ACC403 Quick Start Guide 

ii 

Contents 

 
1

 

Overview .............................................................................. 1

 

2

 

Hardware Installation ................................................... 2

 

2.1

 

Mounting the Energy Pack on a DIN Rail .. 2

 

2.2

 

Panel-Mounting the Energy Pack ................ 3

 

3

 

Cable Connections ......................................................... 4

 

3.1

 

Connect Input Power to Energy Pack ........ 5

 

3.2

 

Connecting the Energy Pack to the 

Controller ............................................................................ 6

 

4

 

Grounding ........................................................................... 7

 

5

 

Initial Power-up ................................................................ 8

 

6

 

LED and Status Indications ........................................ 9

 

6.1

 

LED Indications: Special Cases ................... 10

 

6.2

 

Energy Pack Status Bit Operation ............ 10

 

7

 

Replacing the CapPack Module ............................ 11

 

8

 

Firmware Updates ....................................................... 12

 

8.1

 

LED Indications for Firmware Updates ... 12

 

9

 

Additional Information .............................................. 13

 

 


background image

 

July 2018 

GFK-3000A 

 

1

 

Overview 

An Energy Pack is used in conjunction with a Controller 
to preserve user memory in the Controller during power 
fluctuations or outages. 
If system power is lost, the Energy Pack maintains power 
long enough for a Controller to write its user memory 
contents to non-volatile memory. When system power is 
restored, the user memory is restored if the Controller is 
configured to power up from RAM. 

 

Figure 1: Interconnect Wiring Diagram 

 


background image

 

GFK-3000A 

IC695ACC403 Quick Start Guide 

Ordering Information 

IC695ACC403 

Energy Pack.

 

Includes base, 

CapPack module and Energy Pack 
to Controller cable.

 

IC695ACC413 

Replacement CapPack module. 

IC695CBL003 

Replacement 0.6m (24

) Energy 

Pack to Controller cable. 

2

 

Hardware Installation 

The Energy Pack can be mounted on a standard EN50022 
DIN rail or an equipment panel. It is designed to be 
mounted adjacent to the Controller and connected to the 
Controller using the provided cable (IC695CBL003). 

  

Heat dissipation:

 When mounting the Energy Pack, 

allow a minimum clearance of 25.4mm (1 inch) on all four 
sides of the unit (right, left, top and the bottom). 

2.1

 

Mounting the Energy Pack on a DIN Rail 

The Energy Pack snaps easily onto the DIN rail. No tools 
are required. 

1)

 

Incline Energy Pack so that top edge of plastic 
recess (Figure 2) engages top of DIN rail 

2)

 

Swivel the Energy Pack so that bottom spring-
loaded plastic clip engages bottom of DIN rail. 

3)

 

Listen for click as plastic clip springs back, 
securing the Energy Pack onto the DIN rail. 

 


background image

 

July 2018 

GFK-3000A 

 

Figure 2: Snap Mount to DIN Rail 

2.2

 

Panel-Mounting the Energy Pack 

Recommended fasteners: 

Four M4-0.7 machine screws with minimum length 
of 25mm (or 8-32, 

1” min. length) and nuts.

 

 

CAUTION 

Over tightening the mounting screws could 
crack the plastic housing. 

 


background image

 

GFK-3000A 

IC695ACC403 Quick Start Guide 

3

 

Cable Connections 

 

Figure 3: Input Power and Output Power

/Control Connections 

 


background image

 

July 2018 

GFK-3000A 

3.1

 

Connect Input Power to Energy Pack 

IMPORTANT 

Before connecting input power, see complete 
installation instructions in the 

PACSystems 

Controllers: Battery and Energy Pack Manual,

 

GFK-2741E or later. 

You will need: 

 

A 24Vdc, 72W SELV power supply  

 

A power cord with 18 AWG (0.82mm

2

) copper wires  

 

An 18 AWG (0.82mm

2

) copper wire for frame ground 

 

An input power terminal block 

 provided 

(Weidmuller part number 1748010000) 

 

A small flat-head screwdriver (such as a 1.4mm 

jeweler’s screwdriver)

 

1. 

Using the power cord, connect the power supply 
output to the 

Energy Pack’s 

input power terminal 

block. 
To insert the wires in the power terminal block 
connector, you may need to use the small 
screwdriver to release the spring clamp on the 
terminal block. 
Recommended wire stripping length is 
7mm (0.28 in). 

 


background image

 

GFK-3000A 

IC695ACC403 Quick Start Guide 

 

Figure 4: Energy Pack Input Power Mating 

Connector (bottom view) 

2. 

Insert the plug into the 

Energy Pack’s

 Input 

Power connector and securely tighten the 
attaching screws.  

3.2

 

Connecting the Energy Pack to the 
Controller  

With power to the system turned off, use the 
supplied cable (IC695CBL003) to connect the 
output of the Energy Pack (green connector) to 
the 24Vdc input on the Controller (3-pin green 
connector) and to the serial communication link 
(using the 5-pin green connector). Refer to 
Figure 5. 

 


background image

 

July 2018 

GFK-3000A 

 

4

 

Grounding 

Proper grounding of this device is essential. All ground 
wires must be as short as possible and terminated at the 
same grounding point. 

 

Figure 5: Frame Ground Connection 

 


background image

 

GFK-3000A 

IC695ACC403 Quick Start Guide 

5

 

Initial Power-up 

When 24Vdc power is first applied to the Energy Pack, 
the power-up process goes through the following steps: 

1. 

The IN LED turns on green. 

2. 

The Energy Pack performs a self-diagnostic 
test. If this test passes, output power to the 
Controller is turned on and the OUT LED turns 
on green. 

3. 

Charging of the CapPack begins and the STAT 
LED blinks green. 

4. 

When charging of the CapPack is complete, the 
STAT LED turns on solid green and the Energy 
Pack signals to the controller that it can start 
run-time operation. The Controller will not start 
running its application until the Energy Pack 
signals that it is fully charged. 

 

 

       Figure 6: LEDs on CAP Pack 

 


background image

 

July 2018 

GFK-3000A 

6

 

LED and Status Indications 

The LEDs on the Energy Pack indicate its status.   

LED 

LEDState 

Energy Pack Status 

IN 

Green, 

solid

 

Input power is applied and within the 
specified range. 

Red, 

solid

  

Input power is outside the specified 
range. 

Off  

Input power is not applied. 

STAT 

Green, 

blinking

 

CapPack Charging in progress. No 
faults. 

Green, 

solid

 

CapPack is fully charged and no faults. 

Amber, 

blinking 

CapPack is nearing end-of-life. The 
CapPack must be replaced soon. 
Backup is still guaranteed. 

Red, 

blinking

 

Internal fault:   Cycle power to the 
Energy Pack.    If this does not clear the 
fault, contact Technical Support and 
replace the Energy Pack.  

Red, 

solid

 

CapPack has reached end-of-life. 
Replace the CapPack. Backup is 

not

 

guaranteed. 

Off  

No power applied. 

OUT 

Green, 

solid

  

Output power is within the specified 
range. 

Red, 

solid

 

Output power is present but outside 
spec. 

Off  

Output power is not present.  

 


background image

 

GFK-3000A 

IC695ACC403 Quick Start Guide 

10 

6.1

 

LED Indications: Special Cases 

All LEDs blinking in unison:

    See   

Firmware 

Updates, page 12. 

 

6.2

 

Energy Pack Status Bit Operation 

As shown in the table below, a CPU application program 
can automatically monitor the status of the attached 
Energy Pack via %S0014 (PLC_BAT) and %SA0011 
(LOW_BAT). For more details, refer to the chapter on 
Diagnostics in PACSystems RX7i and RX3i CPU 

Programmer’s Reference Manual, GFK

-2950.  

 

PLC_BAT 
(%S0014)  

LOW_BAT 
(%SA0011)  

Energy Pack Status  

Energy Pack connected and 
operational (may be 
charging)  

Energy Pack not connected 
or has failed  

Energy Pack is nearing its 
end-of-life and should be 
replaced.  

 

 


background image

 

11 

July 2018 

GFK-3000A 

7

 

Replacing the CapPack Module 

The CapPack can be removed and replaced while 
power is applied to the Energy Pack (hot swapped.)  

 

CAUTION 

When hot swapping CapPacks, do not 
cycle power until the new CapPack is fully 
charged and operational. Cycling power 
before the STAT LED on the CapPack is solid 
green can result in Controller memory not 
being preserved. 

Do not hot remove/insert the CapPack during 
the firmware update process. 

1. 

Loosen the four screws on the CapPack and 
carefully pull the CapPack off the base. 

2. 

Install the new CapPack on the base, first 
engaging the module-to-base connectors 
and then pressing the CapPack into place. 

 

CAUTION 

Over tightening the mounting screws could 
crack the plastic housing. 

3. 

Use the four screws provided to secure the 
CapPack to the base. 

4. 

When the CapPack is first inserted, the STAT 
LED blinks green while the CapPack is 
charging. Do not remove power to the 
Energy Pack while the CapPack is charging 

 


background image

 

GFK-3000A 

IC695ACC403 Quick Start Guide 

12 

because this could result in Controller 
memory not being preserved. 
The Energy Pack LEDs and the Controller 
status bits indicate when charging is 
complete and the Energy Pack is ready to 
support backup.  

5. 

To remove a Failed Battery fault and clear 
the battery status bits, clear the Controller 
fault table. 
For details on status bit operation, refer to 
the 

PACSystems RX7i and RX3i CPU 

Reference Manual

, GFK-2222 (rev. Y or later). 

 

8

 

Firmware Updates 

The firmware for the Energy Pack is automatically 
updated by the Controller. At power-up, the 
Controller checks the version of Energy Pack firmware 
to verify compatibility with the Controller firmware. If 
an update is needed, the Controller performs it 
automatically. 

8.1

 

LED Indications for Firmware Updates 

Firmware Update 
Mode  

All three LEDs blink 

green

 

Failed to Load 
Firmware  

All three LEDs blink 

red

 

 


background image

 

13 

July 2018 

GFK-3000A 

9

 

Additional Information 

PACSystems RX7i and RX3i CPU Reference Manual,

 

GFK-2222Y or later 

PACSystems Controllers: Battery and Energy Pack 
Manual,

 GFK-2741E or later 

PACSystems RX3i / Series 90-30 Installation and 
Maintenance Requirements

, GFK-2975 

 
For user manuals, product updates and other 
information go to the Support website, 

www.geautomation.com

 

and refer to 

Controllers and IO

RX3i Rackless Controllers. 

 
 

 


background image

 

 

 
 

GE  
Contact Information 

Americas: 1-800-433-2682 or  
 

1-434-978-5100 

Global regional phone numbers are available 
on our  
web site  

www.geautomation.com 

©2016-2018 General Electric Company.

 

All Rights Reserved 
*Trademark of General Electric Company 
and/or its subsidiaries. 
All other trademarks are property of their 
respective holders.

 

GFK-3000A 

 

 

 

 
 
 
 
 
 
 
 

 

 


background image