DELTA Temperature Controller
DTB Series
User Manual
1
http://www.delta.com.tw/industrialautomation/
B Series Temperature Controller
User Manual
Thank you very much for purchasing DELTA B Series. Please read this instruction sheet before using
your B series to ensure proper operation and please keep this instruction sheet handy for quick
reference.
1
Precaution
DANGER!
Caution! Electric Shock!
1.
Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2.
Make sure power is disconnected while checking the unit inside.
3.
The symbol
indicates that this Delta B Series Temperature Controller is protected throughout by DOUBLE
INSULATION or REINFORCED INSULATION (equivalent to Class II of IEC 536).
WARNING!
This controller is an open-type temperature controller. Make sure to evaluate any dangerous
application in which a serious human injury or serious property damage may occur.
1.
Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm (6.0mm for
DTB 4824), hole diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Screw size for DTB4824:
M3 x 4.5 (With 6.0 x 6.0 square washer). Recommended tightening torque: 0.4 N.m (4kgf.cm). Applicable wire:
Solid/twisted wire of 2 mm
2
, 12AWG to 24AWG. Please be sure to tighten them properly.
2.
Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3.
Never modify or disassemble the controller.
4.
Do not connect anything to the “No used” terminals.
5.
Make sure all wires are connected to the correct polarity of terminals.
6.
Do not install and/or use the controller in places subject to:
•
Dust or corrosive gases and liquid.
•
High humidity and high radiation.
•
Vibration and shock.
•
High voltage and high frequency
7.
Must turn power off when wiring and changing a temperature sensor.
8.
Be sure to use compensating wires that match the thermocouple types when extending or connecting the
thermocouple wires.
9.
Please use wires with resistance when extending or connecting a platinum resistance thermometer (RTD).
10.
Please keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller
and please route power wires as far as possible from load wires to prevent interference and induced noise.
11.
This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity,
dripping water, corrosive materials, airborne dust and electric shock or vibration.
12.
Please make sure power cables and signals from instruments are all installed properly before energizing the
controller, otherwise serious damage may occur.
13.
Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an
electric shock.
14.
Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any
internal circuit within this period.
15.
Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
16.
This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install
the protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse
2
type: Time-lag fuse
17.
Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcurrent
protection device(s) must be added to ensure compliance with all relevant electrical standards and codes. (Rated
250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-use
installation.
2
Display, LED and Pushbuttons
PV Display
SV Display
AT
OUT1/OUT2
Function key
Temperature unit LED
Down key
Up
: to display the process value or parameter type.
: to display the set point, parameter operation read value,
manipulated variable or set value of the parameter.
: flashes
when
the
Auto-tuning
operation
is
ON.
: Output LED ights when the output is ON.
:
. Press this key to select the desired function mode and
confirm a setting value.
C, F :
.
ALM1 ~ ALM3 : Alarm output LED, lights when ALM1/ALM2/ALM3 is ON.
:
. Press this key to decrease values displayed on the SV
display. Hold down this key to speed up the decrements.
:
O
Auto-tuning LED,
, l
:
. Press this key to set parameters within function mode.
C : Celsius F : Fahrenheit
. Press this key to increase values displayed on the SV display.
Hold down this key to speed up the incremental action.
Mode key
key
O
O
O
3
Ordering Information
DTB
1 2 3 4 5 6
7
DTB Series
DTB : Delta B Series Temperature Controller
1 2 3 4
Panel Size (W×H)
4824 : 1/32 DIN W48
×
H24mm
4848 : 1/16 DIN W48
×
H48mm
4896 : 1/8 DIN W48
×
H96mm
9696 : 1/4 DIN W96
×
H96mm
5
1st Output Group Selection
R: Relay output, SPDT (SPST: 1/16 DIN and 1/32 DIN size), 250VAC, 5A
V: Voltage pulse output, 14V +10
﹪
~ -20
﹪
(Max. 40mA)
C: DC current output , 4 ~ 20m A
L: Linear voltage output, 0~5V, 0~10Vdc
6
2nd Output Group Selection
R: Relay output, SPDT (SPST: 1/16 DIN and 1/32 DIN size), 250VAC, 5A
V: Voltage pulse output, 14V +10
﹪
~ -20
﹪
(Max. 40mA)
7
EVENT Inputs / CT function
(Optional)
None : No EVENT input , No CT (Current transformer)
E: EVENT input is provided, No CT (Current transformer)
T: CT (Current transformer) is provided, No EVENT input
V: Valve control.
Note 1 :
DTB4824 series: no optional function provided and no extra alarm output supported, but user can set
2nd output as alarm mode.
Note 2 :
DTB4848 series: only one alarm output when optional function supported, but user can set 2nd output as
2nd alarm output.
Note 3: “Valve control” with feedback selection is only available for DTB9696RRV.
3
4
Specifications
5
Temperature Sensor Type and Temperature Range
Input Temperature Sensor
Type
Register Value
LED Display
Temperature Range
0~50mV Analog Input
17
-999 ~ 9999
4~20mA Analog Input
16
-999 ~ 9999
0~20mA Analog Input
15
-999 ~ 9999
0V~10V Analog Input
14
-999 ~ 9999
0V~5V Analog Input
13
-999 ~ 9999
Platinum Resistance (Pt100)
12
-200 ~ 600
o
C
Platinum Resistance (JPt100)
11
-20 ~ 400
o
C
Thermocouple TXK type
10
-200 ~ 800
o
C
Thermocouple U type
9
-200 ~ 500
o
C
Thermocouple L type
8
-200 ~ 850
o
C
Thermocouple B type
7
100 ~ 1800
o
C
Thermocouple S type
6
0 ~ 1700
o
C
Thermocouple R type
5
0 ~ 1700
o
C
Thermocouple N type
4
-200 ~ 1300
o
C
Input Voltage
100 to 240VAC 50/60Hz
Operation Voltage
Range
85% to 110% of rated voltage
Power Consumption
5VA max.
Memory Protection
EEPROM 4K bit (non-volatile memory (number of writes: 100,000)
Display Method
2 line x 4 character 7-segment LED display Process value(PV): Red color, Set point(SV):
Green color
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
3-wire Platinum RTD: Pt100, JPt100
Sensor Type
Analog input: 0~5V, 0~10V, 0~ 20 m A, 4~20 m A, 0~50mV
Control Mode
PID, ON/OFF, Manual or PID program control (Ramp/Soak control)
Relay output: SPDT (SPST: 1/16 DIN and 1/32 DIN size), Max. load 250VAC, 5A resistive load
Voltage pulse output: DC 14V, Max. output current 40mA
Current output: DC 4 ~ 20m A output (Load resistance: Max. 600
Ω
)
Control Output
Linear voltage output: 0~5V, 0~10V
Display Accuracy
0 or 1 digit to the right of the decimal point (selectable)
Sampling Rate
Analog input: 150 msec/ per scan Thermocouple or Platinum RTD: 400 msec/per scan
RS-485 Communication MODBUS ASCII / RTU communication protocol
Vibration Resistance
10 to 55Hz, 10m/s
2
for 10min, each in X, Y and Z directions
Shock Resistance
Max. 300m/ s
2
, 3 times in each 3 axes, 6 directions
Ambient Temperature
0
o
C to +50
o
C
Storage Temperature
-20
o
C to +65
o
C
Altitude
2000m or less
Relative Humidity
35% to 80% (non-condensing)
4
Thermocouple E type
3
0 ~ 600
o
C
Thermocouple T type
2
-200 ~ 400
o
C
Thermocouple J type
1
-100 ~ 1200
o
C
Thermocouple K type
0
-200 ~ 1300
o
C
Note 1 : An external 250
Ω
precision resistor should be connected when the current input is selected as the input
temperature sensor type..
Note 2 :
(Operation mode) must be set if user wish to specify decimal point position. Except for the
thermocouple B, S, R type, the decimal point positions of all the other thermocouple type input sensors can
be set.
The default range of analog input is -999 ~ 9999. For example, when a 0~20mA analog input is selected as the
input temperature sensor type, -999 indicates 0mA and 9999 indicates 20mA. If change the input range to 0 ~
2000, then 0 indicates 0mA and 2000 indicates 20mA. One display scale is equal to 0.01mA.
6
Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, controller
gets into the operation mode. Press the
key to switch to regulation mode. If the
key is pressed for
more than 3 seconds, controller will switch to the initial setting mode. Pressing the
key while in the
regulation mode or initial setting mode, forces the controller to return to the operation mode.
PV/SV: Sets the temperature set point and displays the temperature process value. Use
keys to set the
temperature set point.
Setting method: While in any function mode, press the
key to select the desired function and use the
keys to change settings. Press
key to save the changes.
The next flow chart shows how to switch for settings and internal functions:
Regulation Mode
Operation Mode
Initial Setting Mode
Press key less than 3 sec
Press key
Press key more than 3 sec
Press key
Regulation Mode
Operation Mode
Initial Setting Mode
Auto-tuning
(Set in PID control and RUN mode)
Press
Use key to
set temperature set point
Press
Set input type
Press
4 groups PID modes (n=0~3). When n=4,
PID control is auto regulated.
Press
Press
Control setting RUN or STOP
Set temperature unit
do not display when analog input
Press
PD control offset
setting
(When PID control is ON and Ti=0,
set the value of PdoF.
Press
Start pattern setting (PID
program control and
Time setting.
Press
Set upper-limit of
temperature range
Press
Heating hystereisis setting
(Set in ON/OFF control mode)
Press
Decimal point position selection
(except for B, S, R type, all the
other types can be set)
Press
Set lower-limit of
temperature range
Press
Cooling hystereisis setting
(Set in ON/OFF control mode)
Press
Upper-limit alarm 1
(This parameter is available only when
ALA1 function enables)
Press
Select control mode
(See "Pattern and set Editing
selection" for detail)
Press
5
or
Heating/Cooling
control cycle setting
(Set in PID control mode)
Press
Lower-limit alarm 1
(This parameter is available only when
ALA1 function enables)
Press
Select heating/cooling control
or dual loop output control
Press
Control cycle setting
of 2nd output group
(Set in PID control and Dual Loop
output control mode)
Press
Upper-limit alarm 2
(This parameter is available only when
ALA2 function enables)
Press
Alarm 1 mode setting
Press
P value of 2nd output group =
x
(P value of 1st output group)
P value of 1st & 2nd output group
during dual loop output control
Press
Lower-limit alarm 2
(This parameter is available only when
ALA2 function enables)
Press
Press
Alarm 2 mode setting
Press
Dead Band (Set in Dual Loop
output control mode)
Upper-limit alarm 3
(This parameter is available only when
ALA3 function enables)
Press
Press
Alarm 3 mode setting
Press
Switch setting for feedback
signal of valve. (Display when
valve control is ON)
Lower-limit alarm 3
(This parameter is available only when
ALA3 function enables)
Press
Set system alarm
Press
Press
Automatically regulate
feedback value.
Press
(Display when valve control is ON)
Setting lock mode
Press
Communication write function
enable/disable
Press
Time setting for valve from
full close to full open. (Display when
valve control is ON)
Press
Display and adjust output value
of 1st output group
(Display in PID control mode and manual
RUN mode)
Press
ASCII, RTU communication
format selection
Press
Press
Valve Dead Band setting.
Press
(Display when valve control is ON)
Display and adjust output value
of 2nd output group
(Display in dual loop PID control mode and
manual RUN mode)
Press
Communication address
setting
Press
Upper-limit regulation of
valve output with feedback to
controller. (Display when valve
signal feedback function is ON)
Press
In case of using an external CT,
the controller displays the current
value being measured by CT, if
the control output is ON
Press
to return to set target temperature
Communication baud
rate setting
Press
Lower-limit regulation of
valve output with feedback to
controller. (Display when valve
signal feedback function is ON)
Press
Valve output with feedback.
(Display when valve feedback
function is ON)
Press
Data length setting
Press
Press
Regulate temperature
deviation value
DA value feedback of valve.
(Display when valve feedback
function is ON)
Press
Back to target temperature
Parity bit setting
Press
(The setting display when analog output)
Press
Regulate upper-limit of analog
output value
Stop bit setting
Press to return input type setting
Press
Regulate lower-limit of analog
output value
(The setting display when analog output)
to return to auto-tuning mode
6
※
1 Scale = 2.8uA = 1.3mV for tuning output value
PID mode selection: any one of 4 groups PID modes (n=0~3) can be selected. When n=4, program will
automatically select 1 group PID that is most useful for target temperature.
Select n=0~4 to
decide PID mode.
0~3 groups PID
Press
PID setting: n=0.Press
PID setting: n=3.Press
Proportion band setting: n=0.
Press
Proportion band setting: n=3.
Press
Ti setting: n=0. Press
Ti setting: n=3. Press
Td setting: n=0.Press
Td setting: n=3.Press
Integral deviation setting: n=0.
AT setting.
Press
back to PID deviation setting
Integral deviation setting: n=3.
AT setting.
Press
back to PID deviation setting
Pattern and step editing selection: edit
in
parameter. The following display is the example operation of pattern
No. 0.
select OFF
Press
Select desired editing pattern
number
select number
Edit temperature of step No. 0
of pattern No. 0
Press
Select actual step No. when
program control is executing
Press
Exit p
attern and step editing selection
Switch to and continue setting
Edit time of step No. 0 of
pattern No. 0, unit is hh.mm
Press
Set additional execution cycle
number(0 to 99)
Press
Set step No. 07 in order
Press
Edit temperature of step No. 7
of pattern No. 0
Set link pattern, OFF indicates
the program end
Press to return pattern No. editing
mode
Press to set actual step No.
Edit time of step No. 7 of
pattern No. 0, unit is hh.mm
7
Dual Loop Output Control (Heating / Cooling Control)
OFF
PV
Set point
ON
Heating
Dead band
Heating hysteresis
Figure 1. Output
during dual loop output control
operation of ON/OFF control
Cooling hysteresis
Cooling
Temperature control can be achieved either by heating or cooling. In DTB
series, heating and cooling can be operated simultaneously (Dual Loop
output control) to perform temperature control. When Dual Loop output
control are used, two control outputs must be connected to the heating and
cooling devices. Please refer to the following for the operation:
: This parameter is used to select heating or cooling action if
operate either heating or cooling function in this controller. When selecting
, 1st output group is heating (reverse) control, and when selecting
, 1st output group is cooling (forward) control. At this moment, 2nd
output group is regarded as an alarm output. If user select
or
,
it indicates that user can operate Dual Loop output control function in this
controller. When selecting
, 1st output group is heating (reverse)
control and 2nd output group is cooling (forward) control. When selecting
, 1st output group is cooling (forward) control and 2nd output group is
heating (reverse) control.
PV
0
Output
Dead band: dead
band width=positive
Set point
Heating
Cooling
Figure 2. PID
Dead Band is positive
control,
7
In DTB series, P (Proportional Band), I(Integral Time) and D(Derivative
Time) parameters are automatically set by using the Auto-tuning (AT)
function.
: This parameter is for the control mode that must be Dual Loop
output control with PID control method configured. The value of P, I and D of
1st output group can be set immediately. The P value of 2nd output group is
equal to (P value of 1st output group) x
and the value of I and D of
2nd output group are the same as the value of I and D of 1st output group.
: Dead Band, shown as the following figure 1, 2 and 3. This
parameter sets an area in which the heating and cooling control output is 0
centering around the set point in a Dual Loop output control mode.
:
Settings lock.
To avoid incorrect operation, two key lock functions
are provided.
: Lock 1 can lock all settings. All parameters and
temperature settings can be locked to disable changes.
: Lock 2
can lock settings except the SV (Set point) value. All parameters and
temperature settings can be locked with the exception of the SV value.
Press
and
key simultaneously, the “Lock” status can be
released.
PV
0
Output
Dead band: dead
band width=negative
Set point
Heating
Cooling
Figure 3. PID
Dead Band is negative
control,
8
Alarm
Outputs
There are up to three groups of alarm outputs and each group allows thirteen alarm types in the initial setting
mode. The alarm output is activated whenever the process temperature value (PV) is getting higher or lower than
the set point of alarm limit.
Set
Value
Alarm Type
Alarm Output Operation
0
Alarm function disabled
Output is OFF
1
Deviation upper- and lower-limit:
This alarm output operates when PV value is higher than the setting value
SV+(AL-H) or lower than the setting value SV-(AL-L).
ON
OFF
SV-(AL-L)
SV
SV+(AL-H)
2 Deviation
upper-limit:
This alarm output operates when PV value is higher than the setting value
SV+(AL-H).
ON
OFF
SV
SV+(AL-H)
3 Deviation
lower-limit:
This alarm output operates when PV value is lower than the setting value SV-(AL-L).
ON
OFF
SV
SV-(AL-L)
4
Reverse deviation upper- and lower-limit:
This alarm output operates when PV value is in the range of the setting value
SV+(AL-H) and the setting value SV-(AL-L).
ON
OFF
SV
SV-(AL-L)
SV+(AL-H)
5
Absolute value upper- and lower-limit:
This alarm output operates when PV value is higher than the setting value AL-H or
lower than the setting value AL-L.
ON
OFF
AL-L
AL-H
6
Absolute value upper-limit:
This alarm output operates when PV value is higher than the setting value AL-H.
ON
OFF
AL-H
7
Absolute value lower-limit:
This alarm output operates when PV value is lower than the setting value AL-L.
ON
OFF
AL-L
8
Deviation upper- and lower-limit with standby sequence:
This alarm output operates when PV value reaches set point (SV value) and the
value is higher than the setting value SV+(AL-H) or lower than the setting value
SV-(AL-L).
ON
OFF
SV
SV-(AL-L)
SV+(AL-H)
8
9
Deviation upper-limit with standby sequence:
This alarm output operates when PV value reaches set point (SV value) and the
reached value is higher than the setting value SV+(AL-H).
SV+(AL-H)
ON
OFF
SV
10 Deviation lower-limit with standby sequence:
This alarm output operates when PV value reaches the set point (SV value) and the
reached value is lower than the setting value SV-(AL-L).
SV-(AL-L)
ON
OFF
SV
11 Hysteresis upper-limit alarm output:
This alarm output operates if PV value is higher than the setting value SV+(AL-H).
This alarm output is OFF when PV value is lower than the setting value SV+(AL-L).
ON
OFF
AL-L AL-H
12 Hysteresis lower-limit alarm output:
This alarm output operates if PV value is lower than the setting value SV-(AL-H).
This alarm output is OFF when PV value is higher than the setting value SV-(AL-L).
ON
OFF
AL-H AL-L
13 CT alarm output:
This alarm operates when the current measured by transformer (CT) is lower than
AL-L or higher than AL-H (This alarm output is available only for the controller with
current transformer).
ON
OFF
AL-L
SV
AL-H
14 When program control is end status, alarm output is ON.
15 When RAMP UP status happens to PID program control, alarm output is ON.
16 When RAMP DOWN status happens to PID program control, alarm output is ON.
17 When SOAK status happens to PID program control, alarm output is ON.
18 When RUN status happens to PID program control, alarm output is ON.
Note: AL-H and AL-L include AL1H, AL2H, AL3H and AL1L, AL2L, AL3L
9
Current Transformer (CT) Function
The Current Transformer (CT) function is used with the alarm output. When using a current transformer (CT) with
the controller, change the corresponding alarm output mode to mode 13 (alarm output set value is 13), then turn
to operation mode and set the current lower-limit and current upper-limit. You can set current alarm range
between 0.5A ~ 30A, display resolution is 0.1A and measure accuracy is +/- 0.5A.
10
EVENT Inputs Function
5
There are two optional event inputs (contact inputs) supported (EVENT1and EVENT2) in DTB series.
EVENT1:
RUN/STOP operation can be executed by RUN/STOP parameters (Operation Mode) or via the
communication. User also can control RUN/STOP operation by EVENT 1 in DTB series. The control
output is ON if the circuit of EVENT 1 is open when the controller is operating. Otherwise, the
controller will stop output if the circuit of EVENT 1 is short or when the system parameter of the
controller is set to STOP mode.
EVENT2:
DTB series allows user can switch two temperature setting value by changing the status (open/short) of
EVENT 2. Each temperature setting value has independent control parameters.
11
PID Program Control (Ramp/Soak Program Control)
Description of Function and Parameters Setting:
PID program control by 8 patterns (Pattern No. 0~7) is supported in DTB series. Each pattern contains 8 steps
(step No. 0 ~ 7), one Link Pattern parameter, one Cycle parameter and one Actual Step parameter.
Start Pattern
:
is in operation mode and it is used to set the Start Pattern of PID program control (This
parameter appear in
mode only).
Steps :
Include set point X and execution time T, these two parameters setting. The set point (SV) should reach
temperature X after the period of execution time T. If the set point is the same as the result of the previous
setting, then it is called Soak program control. If not, then it is called Ramp program control. Therefore,
PID program control is also called Ramp/Soak program control. The default of step No. 0 in this controller
is Soak program control. The controller will control the temperature (PV) to reach the set point X and then
keep the temperature at set point X. The period of execution time is time T which provided by step No. 0.
Link Pattern Parameter :
For example, when set
to 2, it indicates that pattern No. 2 will execute next after
9
the execution of pattern No. 0. If set to
, it indicates the program will stop after executing the current
pattern and the temperature will keep at the set point of the last step.
Cycle Parameter :
Additional execution cycle number. For example, when set
to 2, it indicates that pattern
No. 4 should execute twice in addition. Include origin one time execution, total execute three times.
Actual Step Parameter :
Execution step number per pattern (can set to 0 ~ 7). For example, when set
to
2, it indicates that pattern No 7 will not execute other steps than step 0 to step2.
Execution :
When
is set to
, the program will start to execute in order from the step 0 of start
pattern. When
is set to
, the program will stop and the control output is disabled. When
is set to
, the program will stop and the temperature at that time will be controlled at the set
point before program stop. Select
again, then the program will restart and execute from step 0 of
start pattern. When
is set to
, the program will hold and the temperature at that time will be
controlled at the set point before program hold. Select
again, then the program will follow the step
before hold and start to execute through the rest of the time.
Display :
During PID program control, the SV default display is P-XX, P indicates the current execution pattern
and XX indicates the current execution step. Press
to change the display item. After select
,
press
key, and then the temperature set point of the current execution step will display on SV
display.After select
, press
key, and then the residual time of the current execution step will
display on SV display.
12
PID Control
One group can be selected from any one of 4 groups PID parameters (P, I, D, IOF) for PID control. After AT, PID
value and temperature setting will be stored in the selected one group.
~
:
PIDn, n=0~4 from which
0~3 correspond to each PID parameter.
: n=4, auto PID parameter. Program will automatically select a most
useful PID parameter based on current temperature setting. Displayed SV values correspond to
~
~
:
Temperature setting corresponded to the selected PID parameter via user-defined or AT.
Valve Control:
When use valve control as output control, there are 2 Relay outputs for motor forward/reverse control, one (output
1) for valve open the other (output 2) for valve close. The output volume is controlled by valve open/close and it
can be set with feedback function enabled or disabled. When feedback is disabled, output 1 will keep output while
valve fully opens and output 2 will keep output while valve fully closes. But if feedback is enabled, please follow the
parameter setting for valve control as follows:
: Time for valve from full close to full open.
: Dead Band setting of valve. The value of current valve output minus previous one must be greater than
Dead Band value; otherwise, valve will remain OFF.
: Signal feedback setting, ON for enabling feedback and OFF for disabling feedback.
When
set to ” 1”, it means signal feedback function is activated and will come up selections as follows:
a.
: Upper/Lower limit of valve feedback by auto-tuning.
must set to
for showing up this
selection.
b.
: D/A value when value fully opens. Set
to be ”1” for auto setting or ”0” for manual setting.
c.
: D/A value when value fully closes. Set
to be ”1” for auto setting or “0” for manual setting.
Note: If feedback function setting is with problem, program will see the setting as feedback disabled.
10
13
RS-485 Communication
1. Supporting transmission speed: 2400, 4800, 9600, 19200, 38400bps
2. Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2
3. Communication protocol: Modbus (ASCII or RTU)
4. Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register.
02H to read the bits data (Max. 16 bits). 05H to write 1 (one) bit into register.
5. Address and Content of Data Register:
Address Content
Explanation
Measuring unit is 0.1, updated one time in 0.4 second
The following reading value display indicates error occurs:
8002H : Initial process (Temperature value is not got yet)
8003H : Temperature sensor is not connected
1000H Process value (PV)
8004H : Temperature sensor input error
8006H : Cannot get temperature value, ADC input error
1000H
Process value (PV)
8007H : Memory read/write error
1001H Set point (SV)
Unit is 0.1,
o
C or
o
F
1002H Upper-limit of temperature
range
The data content should not be higher than the temperature range
1003H Lower-limit of temperature
range
The data content should not be lower than the temperature range
1004H
Input temperature sensor type
Please refer to the contents of the “Temperature Sensor Type and
Temperature Range” for detail
1005H Control method
0: PID, 1: ON/OFF, 2: manual tuning, 3: PID grogram control
1006H Heating/Cooling control
selection
0: Heating, 1: Cooling, 2: Heating/Cooling, 3: Cooling/Heating
1007H 1st group of Heating/Cooling
control cycle
0~99, 0:0.5 sec
1008H 2nd group of Heating/Cooling
control cycle
0~99, 0:0.5 sec
1009H PB Proportional band
0.1 ~ 999.9
100AH Ti Integral time
0~9999
100BH Td Derivative time
0~9999
100CH Integration default
0~100%, unit is 0.1%
100DH Proportional control offset
error value, when Ti = 0
0~100%, unit is 0.1%
100EH The setting of COEF when
Dual Loop output control are
used
0.01 ~ 99.99
100FH The setting of Dead band
when Dual Loop output control
are used
-999 ~ 9999
1010H Hysteresis setting value of the
1st output group
0 ~ 9999
1011H Hysteresis setting value of the
2nd output group
0 ~ 9999
1012H Output value read and write of
Output 1
Unit is 0.1%, write operation is valid under manual tuning mode only.
1013H Output value read and write of
Output 2
Unit is 0.1%, write operation is valid under manual tuning mode only.
1014H Upper-limit regulation of
analog linear output
1 Unit = 2.8uA(Current Output) = 1.3mV(Linear Voltage Output)
1015H Lower-limit regulation of
analog linear output
1 Unit = 2.8uA(Current Output) = 1.3mV(Linear Voltage Output)
11
1016H Temperature regulation value -999~+999, unit: 0.1
1017H Analog decimal setting
0 ~ 3
1018H Time for valve from full open
to full close
0.1~999.9
1019H Dead Band setting of valve
0~100%; unit: 0.1%
101AH Upper-limit of feedback
signal set by valve
0~1024
101BH Lower-limit of feedback
signal set by valve
0~1024
101CH PID parameter selection
0~4
101DH SV value corresponded to
PID value
Only valid within available range, unit: 0.1 scale
1020H Alarm 1 type
Please refer to the contents of the “Alarm Outputs” for detail
1021H Alarm 2 type
Please refer to the contents of the “Alarm Outputs” for detail
1022H Alarm 3 type
Please refer to the contents of the “Alarm Outputs” for detail
1023H System alarm setting
0 : None (default), 1~3 : Set Alarm 1 to Alarm 3
1024H Upper-limit alarm 1
Please refer to the contents of the “Alarm Outputs” for detail
1025H Lower-limit alarm 1
Please refer to the contents of the “Alarm Outputs” for detail
1026H Upper-limit alarm 2
Please refer to the contents of the “Alarm Outputs” for detail
1027H Lower-limit alarm 2
Please refer to the contents of the “Alarm Outputs” for detail
1028H Upper-limit alarm 3
Please refer to the contents of the “Alarm Outputs” for detail
1029H Lower-limit alarm 3
Please refer to the contents of the “Alarm Outputs” for detail
102AH Read LED status
b0 : Alm3, b1: Alm2, b2: F, b3:
℃
, b4: Alm1, b5: OUT2, b6: OUT1, b7: AT
102BH Read pushbutton status
b0 : Set, b1 : Select, b2 : Up, b3 : Down. 0 is to push
102CH Setting lock status
0 : Normal, 1 : All setting lock, 11 : Lock others than SV value
102DH CT read value
Unit: 0.1A
102FH Software version
V1.00 indicates 0x100
1030H Start pattern number
0 ~ 7
1040H~
1047H
Actual step number setting
inside the correspond pattern
0 ~ 7 = N, indicate that this pattern is executed from step 0 to step N
1050H~
1057H
Cycle number for repeating
the execution of the
correspond pattern
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
1060H~
1067H
Link pattern number setting of
the correspond pattern
0 ~ 8, 8 indicates the program end. 0~7 indicates the next execution pattern
number after executing the current pattern
2000H~
203FH
Pattern 0~7 temperature set
point setting
Pattern 0 temperature is set to
2000H~2007H
-999 ~ 9999
2080H~
20BFH
Pattern 0~7 execution time
setting
Pattern 0 time is set to
2080H~2087H
Time 0 ~ 900 (1 minute per scale)
6. Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data = FF00H for bit set,
0000H for bit clear)
0810H
Communication write-in
selection
Communication write in disabled: 0 (default), Communication write in
enabled: 1
0811H
Temperature unit display
selection
o
C / linear input (default) : 1 ,
o
F : 0
0812H
Decimal point position
selection
Except for the thermocouple B, S, R type, all the other thermocouple type
are valid. (0 or 1)
0813H AT setting
OFF: 0 (default), ON : 1
0814H Control RUN/STOP setting
0 : STOP, 1 : RUN (default)
0815H
STOP setting for PID
program control
0: RUN (default), 1: STOP
12
0816H
Temporarily STOP for PID
program control
0: RUN (default), 1: Temporarily STOP
0817H Valve feedback setting status 0: w/o feedback (default), 1: feedback function
0818H
Auto-tuning valve feedback
status
0: Stop AT (default), 1: Start AT
7. Communication Transmission Format : Command Code: 02: read N bits, 05: write 1 bits, 03: read N words, 06:
write 1 words
14
Panel Cutout and Terminals Identification
Panel Cutout (
dimensions are in millimeter and
Terminals Identification
DTB4824
65.0 min.
(2.56)
4
0
.0
m
in
.
(1
.5
8
)
44.8
(1.76)
2
2
.0
(0
.8
7
)
+0.6
-0
+0.02
-0
+
0
.6
-0 +
0
.0
2
-0
mm
(in)
DTB4824
1
4
3
2
5
6
AC 100~240V
50/60 Hz 5VA
Tc
+
-
RTD
OUT 1
DATA-
DATA+
RS-485
7
9
8
10
11
12
V
!
+
+
-
-
OUT 2/
ALM
V
+
-
IN
+
-
L
N
DTB4848
65.0 min.
(2.56)
4
5
.0
(1
.7
7
)
45.0
(1.77)
6
0
.0
m
in
.
(2
.3
6
)
+0.6
-0
+0.02
-0
+
0
.6
-0 +
0
.0
2
-0
mm
(in)
DTB4848
(EVENT & CT selection)
DTB4848
(NO EVENT & CT)
1
4
3
2
5
Tc
+
-
RTD
7
6
9
8
10
14V
DC
DATA-
DATA+
RS-485
11
14
15
13
12
AC 100~240V
50/60 Hz
5VA
3A
250Vac
ALM 2
ALM 1
COM
3A
250Vac
NO
OUT1
14V
or
4~20mA
or
0~10V
DC
+
-
COM
NO
COM
+
-
IN
OUT2/
ALM3
+
-
L
N
DTB4896
DTB4896/DTB9696
NO
COM
NC
5A
250Vac
1
4
3
2
5
7
6
9
8
10
11
14
15
13
12
16
19
20
18
17
AC 100~240V
50/60 Hz
5VA
OUTPUT1
14V
DC
4~20mA
0~10V
NO
COM
NC
5A
250Vac
OUTPUT2/ALM3
14V
DC
ALM2
COM
or
or
Tc
+
RTD
DATA+
DATA-
RS-485
SG
Ev1
Ev2
CT
ALM1
COM
IN
+
+
-
+
- -
-
L
N
13
DTB9696
DTB9696RRV
15
External Dimensions
Dimensions are in millimeter (inch)
DTB4824
DTB4848
48.0 mm
(1.89 in)
2
4
.0
m
m
(0
.9
4
in
)
3.4 mm
(0.13 in)
99.8 mm
(3.93 in)
2
1
.8
5
m
m
(0
.8
6
in
)
44.75 mm
(1.76 in)
2
2
.0
m
m
(0
.8
7
in
)
44.8 mm
(1.76 in)
48.0 mm
(1.89 in)
4
8
.0
m
m
(1
.8
9
in
)
9.5 mm
(0.37 in)
80.0 mm
(3.15 in)
4
4
.7
5
m
m
(1
.7
6
in
)
45.0 mm
(1.77 in)
+0.6
0
4
5
.0
m
m
(1
.7
7
in
)
+
0
.6
0
+0.02
0
+
0
.0
2
0
DTB4896
DTB9696
48.0 mm
(1.89 in)
12.8 mm
(0.50 in)
79.2 mm(3.12 in)
91.0
mm(3.58
in
)
95
.7
m
m
(3.
7
7
in)
98.2
mm(3.
8
7 i
n
)
44.0 mm
(1.73 in)
44.5 mm
(1.75 in)
+0.6
0
91
.5
m
m
(3
.6
0
i
n
)
+0
.6
0
+0.02
+0
.0
2
0
0
96.0 mm
(3.78 in)
96.
0 mm
(3
.7
8 in
)
98.
0 mm
(3
.8
6 i
n
)
15.8 mm
(0.62 in)
79.2 mm
(3.12 in)
90
.8
m
m
(3
.5
7 i
n
)
91.0 mm
(3.58 in)
+0.6
0
91
.0
mm
(3
.5
8 in
)
+0
.6
0
+0.02
0
+0
.0
2
0
14
16
Mounting
Mounting Method
Mounting Bracket Installation
CT Wiring Method (if CT function is
Step 1 : Insert the controller through the panel cutout.
Step 2 : Insert the mounting bracket into the mounting groove
at the top and bottom of the controller
Step 3 : Push the mounting bracket forward until the bracket
stops at panel wall.
Step 4 : Insert and tighten screws on bracket to secure the
controller in place. (The screw torque should be
0.8kgf-cm to 1.5kgf-cm)
DTB4824 Mounting Method:
DTB4848/4896/9696 Mounting Method:
1
3
2
06
.8
m
m
M
ax
.
17
Error Acknowledge and Display
Communication error code response description:
Error status 102EH/4750H
PV read back 1000H/4700H
Error status
0001H N/A
PV
unstable
0002H 8002H
Re-initial
,
No temperature at this time
0003H
8003H
Input sensor did not connect
0004H
8004H
Input signal error
0005H
N/A
Over input range
0006H 8006H
ADC
fail
0007H
N/A
EEPROM read/write error
Display message:
Power ON
Normal display
PV
DTB series, Firmware V1.50
Present value
SV
Output VR type with Event option
Set value
Sensor didn’t connect
Input error
PV
No
Error
SV
Connect
Input
EEPROM error
Input over range
PV
Error
PV flash when over
SV
EEPROM
15
Contact Information:
ASIA
DELTA ELECTRONICS, INC.
TAOYUAN Plant/
31-1, SHIEN PAN ROAD,
KUEI SAN INDUSTRIAL ZONE
TAOYUAN 333, TAIWAN
TEL: 886-3-362-6301
FAX: 886-3-362-7267
NORTH/SOUTH AMERICA
DELTA PRODUCTS CORPORATION
Sales Office/
P.O. BOX 12173
5101 DAVIS DRIVE
RTP, NC 27709 U. S. A.
TEL: 1-919-767-3813
FAX: 1-919-767-3969
EUROPE
DELTRONICS (Netherlands) B.V.
Sales Office/
DE WITBOGT 15
NL-5652 AG EINDHOVEN
The NETHERLANDS
TEL: 31-40-259-2850
FAX: 31-40-259-2851