Full Text Searchable PDF User Manual
Page1
AIR CONDITIONING
PORTA TEMP 240/320DX
CAUTION
PLEASE READ THIS LEAFLET CAREFULLY
1. DO NOT APPLY MAINS WATER PRESSURE TO THIS UNIT. WHERE
APPROPRIATE, ACCESS TO THE FILLING POINT FOR THE WATER
CIRCULATING SYSTEM IS REACHED BY THE REMOVAL OF THE FILLER
ACCESS PLATE IN THE ROOM UNIT BACK PANEL.
2. WHEN REMOVING THE UNIT FROM AN INSTALLATION DISCONNECT WATER
QUICK COUPLINGS IN THE ROOM UNIT FIRST.
INTERNAL ACCESS SHOULD BE RESTRICTED TO CALOREX TRAINED STAFF
ONLY.
SD259755 ISS 4
Page 2
BLANK PAGE
Page3
DO NOT LET HEAT EXCHANGER HANG
FROM ITS FLEXIBLE LINE
SUPPORT HEAT EXCHANGER
WEIGHT USING HOOKS
AND CHAINS PROVIDED
OR STAND ON FIRM
GROUND.
DROPS OF CONDENSATE
MAY APPEAR HERE
Fig 1
PAC240 SHOWN
EXTERNAL HEAT EXCHANGER (HEX).
The heat exchanger must stand external to the area
being cooled and, preferably, in the outside atmosphere.
It can stand freely on a flat surface or, in the case of the
PAC.240 may be hung in the upright position from a
sindow sill, balcony etc, see Fig 1. USE THE CHAINS
PROVIDED TO SUPPORT THE HEAT EXCHANGER.
IT WOULD BE HIGHLY DANGEROUS TO SUPPORT
THE HEAT EXCHANGER BY MEANS OF THE
FLEXIBLE LINES ALONE.
CONDENSATE.
In operation, the room unit is constantly condensing water
vapour out of the atmosphere (reducing relative
humidity). This water has to be drained away. An
automatic condensate pump is fitted inside all room
units. The flexible hose outlet from the condensate pump
runs to the outside, inside the flexible sheath , the
condensate is deposited in the base of the heat
exchanger, considerable re-evaporation of this water
takes place on the warm air stream passing through and
around the heat exchanger, but please remember that
there will also be a degree of dripping through the base
of the heat exchanger.
HAVE GREAT REGARD FOR THIS CHARACTERISTIC
WHEN POSITIONING THE EXTERNAL HEAT
EXCHANGER.
The flexible water pipes should be routed so as to avoid
any possibility of kinking or unnecessary restrictions to
the flow of water inside. Also, remember that plastic
and rubber becomes much more flexible when warm
and, as a result, much more susceptible to distortion.
5) MACHINE LINK-UP.
Ensure the mains supply lead to the room unit is
disconnected. A 5m (extendable to 30m) line set to
connect water between the room unit and the external
heat exchanger will have been supplied. The water pipe
connections are by means of “quick connect couplers”.
These are simple “push-on” connectors which, when
disconnected (after pulling back sprung loaded locking
ring), re-seal the water system on either side. The
complete system will have been filled with the necessary
amount of water/antifreeze prior to its arrival on site. A
condensate drain pipe coupler 6mm clear polythene
(push fit), should also be connected. Having made the
couplings, the system is operational immediately.
WARNING !
This unit MUST be transported and operated in the upright
position at all times.
1) COMMISSIONING INSTRUCTIONS
As standard, these units are supplied with a NEMA power
plug attached to the power supply cord. They require a 208/
230volt 1 phase 60Hz supply with the following appropriately
protected current rating:-
PAC.240 20 AMPS
PAC.320 30 AMPS
The size of any extension cable that may be used is as
follows and must be rated above the fuse size also allowing
for voltage drop and be suitable for the environment:
PAC.240
14AWG up to 30 feet
12AWG over 30 feet
PAC.320
10AWG up to 30 feet
8AWG over 30 feet
If the cable is on a "cable drum" then ensure that it is
completely unwound; serious complications will occur
otherwise.
2) SYSTEM DESCRIPTION.
The system comprises a room unit cooling section, an
external heat exchanger and the two are inter-connected
by means of flow and return water pipes and an electrical
supply to the heat exchanger fan.The room unit is fitted
with an automatic condensate disposal pump which
discharges the condensate via a small plastic pipe
into
the base of the external heat exchanger
and all
interconnecting pipes and electrics are enclosed in a flexible
plastic sheath. In addition, both ends of each pipe are fitted
with "quick connect" couplings that open on coupling but
reseal to become water tight on disconnect.
3) AIRFLOW
The angled outlets at the top of the room unit are fitted with
air grilles that allow the angle of air outlet to be adjusted
vertically and horizontally and, in conjunction with the fan
speed control switch, the air velocity and direction can be
carefully set up to obtain maximum coverage of the area
being cooled without causing drafts. Care should be taken
to avoid outlet air being obstructed as this will cause the air
to "eddy" around the unit resulting in recirculation and short/
inaccurate cycling of the machine. Ideally, cold air should
be directed to create a "blanket" all across the ceiling area
allowing natural convection to drop the air over the whole
area at very low velocity.
4) SITING
Ideally, the room unit should be positioned equidistant along
the shortest wall in the room
blowing down the length of
the room. If there is more than one unit in the same area,
then they would normally be positioned side by side, and
equidistant along the long wall, all pointing in the same
direction. Sometimes it may be necessary to position units
around the perimeter of an area but, in this case, great
care should be taken to avoid one unit blowing cold air
straight into another which will adversely affect the machine
operation. Good and correct air flow is, perhaps, the single
most important aspect of satisfactorily applying portable
air conditioners. If in doubt seek the advice of your supplier.
Page 4
6) ROOM UNIT WATER LEVELS
.
The water system in the room unit will be to the correct
level when delivered. However if for some reason the level
has fallen, antifreeze (33%) and water will have to be added.
The header tank filler and level indication is located to the
rear of the room unit and can be accessed by removing the
two screws holding the security plate over the filler tank
cap, see Fig 2. Ensure the machine is running in cooling
mode before removing the header tank cap, and as with all
pressure caps, remove slowly. It is recommended that a
mixture, by volume, of one part antifreeze to two parts water
is utilised, this will prevent freezing down to an external
temperature of -30°C/-5ºF. The approximate total volume
the systems, room unit with external heat exchanger and
lines is as follows:-
DO NOT APPLY MAINS WATER PRESSURE TO THE
SYSTEM.
Fig 2
10
C
34
C
1
2
3
4
5
6
7
8
THERMOSTAT
KNOB
MAINS LIGHT
(RED)
MODE
SWITCH
FAN ONLY
POSITION
COOLING
POSITION
FAN SPEED
SWITCH
FAN SPEED
HIGH
FAN SPEED
LOW
COOLING LIGHT
(GREEN)
ATTENTION LIGHT
(AMBER)
HIGH
PRESSURE
RE-SET
LOW
PRESSURE
RE-SET
DEFROST
LIGHT (WHITE)
OFF
POSITION
7) OPERATING INSTRUCTIONS.
The Control Panel on the room unit is illustrated below,
see Fig 3.
a) Revolve thermostat knob fully CLOCKWISE to the
number "8" position.
b) Plug in the room unit mains cable, and switch on
electricity, red mains light will illuminate.
c) Select "Fan Only" with the mode switch. The fan will
start.
d) Select "Fan Speed", with the fan speed switch, high or
low depending on air velocity required.
e) Select "Cooling" with the mode switch, and revolve the
thermostat knob fully ANTI-CLOCKWISE to the number
"1" position. If fitted the external heat exchanger fan and
the water pump in the room unit will start. After a delay of
10mins the green "Cooling" light will illuminate and the
machine will proceed to cool the air.
f) Monitor the room temperature and when it has reduced
to the desired level, very slowly revolve the thermostat knob
back, clockwise, until the green "Cooling" light goes out.
The room unit will now control the room temperature cooling
automatically at this setting.
Fig 3
LINESET LENGTH Total Volume
Units
16FT
2.65
U.S Gallons
21FT
3.07
U.S Gallons
32FT
3.25
U.S Gallons
48FT
3.85
U.S Gallons
64FT
4.45
U.S Gallons
80FT
5.05
U.S Gallons
Page5
8) ROUTINE MAINTENANCE
The air filter must be kept clean, never allow to become
choked with dust or dirt. If allowed to do so, the performance
of the unit will become impaired, resulting in loss of air flow,
freezing up of the evaporator coil and possible component
damage.
ACCESSING THE FILTER
Lift open the return air grille on the front face of the unit,
Fig 4. On refitting the filter ensure that it is correctly
positioned covering the whole rear face of the grille. The
filter (see Fig. 4) can be washed in warm, soapy water,
rinsed and shaken dry before replacement. Frequency of
cleaning depends upon application and can only be
determined by the user. However, you should never allow
more than two months to elapse between cleaning. The
probable life of the filter will be about one year and spares
are available from the supplier of the unit itself. Failure to
have filter fitted during operation will cause serious damage.
FIG 4.
The refrigeration circuit inside the room unit is fitted with a
HIGH and a LOW pressure sensing switch. They are both
manually re-settable. A pencil or screwdriver with gentle
pressure on the knob behind is all that is required to re-set.
Necessary access is provided through the control console.
HOWEVER, DO NOT ATTEMPT TO RE-SET WITHOUT
FIRST DISCOVERING WHY THE TRIP
OCCURRED IN THE FIRST PLACE
LIFT AND REMOVE AIR FILTER
UNSCREW RETAINERS AND OPEN PANEL TO REMOVE FILTERS
9) MACHINE NOT WORKING?
ONLY A COMPETENT ELECTRICIAN SHOULD
ATTEMPT TO RECTIFY ELECTRICAL SUPPLY
PROBLEMS. DO NOT REMOVE ANY PANELS FROM
THE MACHINE.
Problem
- No air flow from room unit.
Diagnosis
-Red "MAINS" light off.
Cure
- Turn on electricity and/or check mains supply
fuse.
Problem
- No air flow from room unit.
Diagnosis
- Red "MAINS" light on, White "DEFROST"
light on.
Cure
- Machine in defrost mode, do not adjust anything,
machine will revert to normal run after 10 mins.
Problem
- Insufficient air flow from room unit.
Diagnosis
- Blocked air filter.
Cure
- Clean filter
Problem
- No cooling.
Diagnosis
- Green "COOLING" light off.
Cure
- Revolve thermostat knob fully anti-clockwise to
"1". Wait 10 minutes for time delay on start-up
Problem
- No cooling.
Diagnosis
- Amber "ATTENTION" light illuminated.
High pressure trip.
Cure
- Press "+" button to re-set and check for :-
Lack of water flow ... kinked hoses? Shortage of
water ... top up.
External heat exchanger unit mounted in very high
temperature? Water frozen? Add glycol (33%).
External heat exchanger coil blocked with dirt ... clean.
Problem
- No Cooling.
Diagnosis
- Amber "ATTENTION" light illuminated.
Low pressure trip.
Cure
- Press, "-" button to re-set and check for :-
No air flow, blocked filter?
Evaporator blocked with ice. Very low external
temperature?
Problem
- No Cooling.
Diagnosis
- Amber "ATTENTION" light illuminated.
Low pressure trip.
Cure
- Condensate pump not reducing water level.
Kink in Condensate tube between room unit and heat
exchanger? Leak inside room unit. Sump filter inside
room unit blocked. Condensate tube frozen.
Page 6
21
22
HE
X
WA
T
E
R
PU
M
P
7
4
9
6
B
A
6
3
5
2
1
4
HEX UNIT
MV
AI
R
ST
AT
1 4
HP
L
P
FS
1
FS
2
A2
A1
5
3
1
6
4
2
FL
MC
C1
C3
S
R
C
AU
X
N/
C
D
6
min
s
1
2
4
3
DL
6
5
4
C2
MV
CL
S2
FT
B
Y
RL
S1
SUMP HEATER
F1
F2
COOL
FAN ONLY
LOW
HIGH
IN
N
CO
M
NC
IN
L
OU
T
NO
PUMP
CONTROLLER
TIME
MP
DELAY
L1
L2
K 1
DO NOT SCALE PRINT
10 FLOAT SWITCH COAXIAL LEADS REMOVED
3 SUPPRESSORS ADDED TO RELAYS No2 & 3
4 W/R & W WIRES TO FLOAT SWITCHES WERE BLACK
5 CONTACTOR CHANGED
SUPPRESSORS DELETED
FLOAT SWICHES
COAX LEAD ADDED
6 2 off RELAYS DELETED & PUMP CONTROLLER ADDED
7 PUMP CONTROLLER CLARIFIED ON CIRCUIT DIAGRAM
8 FLOAT SWITCH FS1 TURNED AROUND 180 deg
9
PLUG LEAD COLOURS ADDED.
11 GREY FLOAT SWITCH LEADS WERE BLACK.
ISS
DRAWING CHANGE
12 TERMINAL BLOCK ADDED FOR WATER PUMP
97
R
c
U.C.C.
CALOREX HEAT PUMPS LTD
MATERIAL
FINISH
1024 CJW 08:02:01
GSM 3:6:97
GSM 23:6:97
952 GSM 23:1:98
961 GSM 4:6:98
961 GSM 3:12:98
JAC
1004
1050 CJW 29:06:04
C/N
APPD
DATE
1084 CJW 15:04:05
C
L
H
C
L
H
LP SWITCH
HP SWITCH
TERM BLOCK
EARTH STUD
FAN CAP
COMP RUN CAP
HARD START CAP
COMPRESSOR
SUMP HEATER
BASE EARTH
B 1,5
BR 1,5
B 0
,5
B
0,
5
B 0
,5
BR 0,5
B 0,5
GR/B 0,5
O
/B
K
0,
5
GR
/B
0
,5
R
/B
L 0,
5
R 1,5
BL
1
,5
BL 1,5
P 1,5
P 1,5
G
/Y
1,
5
PLUG
MAINS LEAD
FAULT
G/Y 1,5
BLACK FLYING LEADS
V
0,
5
V
0,
5
G/Y 1,0
BL
U
E
BRO
W
N
BL
AC
K
YE
LL
O
W
G
R
EEN
G
/Y
0,
5
B
0,
5
W
0,
5
B
L 0,
5
W 0,5
FAN MOTOR
CA
P
TB
SOCKET
G/Y 1,5
G/Y 1,5
G/Y 1,0
G/Y 1,0
G/Y 1,0
G/Y 1,0
BR 0,5
S
R
C
E
L
N
LAMP
C3
C1
C2
FL
MC
TERMINAL BOX
G/Y (G USA)
BR (BL USA)
B (W USA)
GSM 3:8:98
08:02:01
SOCKET TO HEX UNIT
B 0,5
BR 0,5
B 0,5
E
L
N
G/R GREEN/RED
GRUN/ROT
VERT/ROUGE
BL
B
BR
GR
O
P
R
W
G/Y GREEN/YELLOW
WHITE
RED
PINK
ORANGE
GREY
BROWN
BLUE
BLACK SCHWARZ
BLAU
BRAUN
GRAU
ORANGE
ROSA
ROT
WEIB
GRUN/GELB
NOIR
BLEU
MARRON
GRIS
ORANGE
ROSE
ROUGE
BLANC
VERT/JAUNE
V VIOLET
VIOLETT VIOLETTE
G GREEN
GRUN
VERT
HEX
UNI
T
O/BK 0,5
P 0,5
GR/B 0,5
R
/B
L 0,
5
Page7
1
---
GSM 9:4:97
NTS
B
FT
S1
HP
LP
D
K
MC
MV
C1
C2
Y
AT
CONTACTOR
DEFROST THERMOSTAT
FAN MODE SWITCH
LOW PRESSURE SWITCH
DELAY TIMER
RELAY
COMPRESSOR MOTOR
FAN MOTOR
COMPRESSOR CAPACITOR
FAN CAPACITOR
SOLENOID VALVE
AIR THERMOSTAT
HIGH PRESSURE SWITCH
SCHALTSCHUTZ
VEREISUNGSSCHUTZTHERMOSTAT
GEBLASESCHALTER
HOCHDRUCKSCHALTER
NIEDERDRUCKSCHALTER
VERZOGERUNGSRELAIS
RELAIS
KOMPRESSORMOTOR
VENTILATORMOTOR
KONDENSATOR KOMPRESSOR
KONDENSATOR VENTILATOR
MAGNETVENTIL
LUFTTHERMOSTAT
CONTACTEUR
THERMOSTAT DE DEGIVRAGE
SELECTEUR DE MODE DU VENTILATEUR
REINITIALISATION DEFAUT HAUTE PRESSION
REINITIALISATION DEFAUT BASSE PRESSION
TEMPORISATEUR
RELAIS
COMPRESSEUR
MOTEUR DU VENTILATEUR
CONDENSATEUR DU COMPRESSEUR
CONDENSATEUR DU VENTILATEUR
VANNE ELECTROMAGNETIQUE
THERMOSTAT AIR
MP
CONDENSATE PUMP
KONDENSATPUMPE
POMPE A CONDENSAT
FL
FAULT LAMP
LAMPE 'FEHLER'
VOYANT PANNE
DL
DEFROST LAMP
LAMPE 'ENTEISEN'
VOYANT DEGIVRAGE
CL
CHILL LAMP
LAMPE 'KUHLEN'
VOYANT REFROIDISSEMENT
RL
MAINS (OR RUN) LAMP
LAMPE 'STROM EIN' ODER 'LAUF'
VOYANT SECTEUR (FONCTIONNEMENT)
S2
FAN SPEED SWITCH
SCHALTER VENTILATORGESCHWINDIGKEIT
COMMUTATEUR VITESSE VENTILATEUR
F1 CONTROL
FUSE
KONTROLLSICHERUNG
FUSIBLE
PRINCIPAL
F2
CONDENSATE FUSE
KONDENSATSICHERUNG
FUSIBLE CONDENSAT
C3
HARD START CAPACITOR
HARTSTARTKONDENSATOR
CONDENSATEUR DEMARRAGE DIRECT
FS1
FLOAT SWITCH HIGH LEVEL
SCHWIMMERSCHALTER HOHER STAND
INTERRUPTEUR A FLOTTEUR NIVEAU HAUT
FS2
FLOAT SWITCH LOW LEVEL
SCHWIMMERSCHALTER NIEDRIGER STAND
INTERRUPTEUR A FLOTTEUR NIVEAU BAS
C4 SUPPRESSOR
SUPPRESSEUR
ENTSTORUNGSELEMENT
D355550
WIRING DIAGRAM
PAC240/HEX240
TOLERANCE UNLESS SPECIFIED
HOLES TO BS 4500 E12
INSPECTION LEVEL
DIMS
SHT No.
CONT'
DRAWN
DRG No.
APPROVED
DATE
SCALE
TITLE
AIR STAT
4
5
6
1
2
3
3 POSN SWITCH
A B
7
4
9
6
5
3
1
6
4
2
21
DELAY TIMER
1 4
2 3
DEFROST STAT
FAN MOTOR
SOLENOID VALVE
CONDENSATE
FLOAT SWITCH
HIGH LEVEL
FLOAT SWITCH
LOW LEVEL
MAINS
DEFROST
CHILL
BR 1
,5
B
1.
5
B 0,5
B 0,5
CONTACTOR B
AUX
A1
22
BR
B 0,5
R/
B
R
0
,5
W
0,
5
BL/W 0,5
RELAY No 1
W/
B
L 0
,5
P 0,5
P 0
,5
P 0,5
O
/B
L 0,
5
O 0,5
O 0,5
GR/B 0,5
W
/R
0,
5
W/
R
0
,5
B 0
,5
G
/R
0,
5
R 0,5
R
W
0,
5
GR 0,5
GR
0
,5
BR 0,5
B
R
0,
5
B
R
1,
0
R
/B
0,
5
R/B 0,5
R/BL 0,5
BLUE FLYING LEAD
BLACK FLYING LEAD
WHITE
BROWN
BR 0,5
RED NOT USED
R 1
,5
BL
1
,5
FLYING LEAD
FLYING LEAD
SUMP
GREY
GREY
GREY
GREY
R/B
R
0
,5
BR 0
,5
W/
B
L 0
,5
B
0,
5
BR 1
,5
B
1,
5
W/R 0,5
B 0,5
W/R 0,5
G/Y 1,0
G/Y 1,0
B 0,5
B
0,
5
W
/R
0,
5
W
0,
5
O 0,5
BR
0
,5
B 0,5
BR
G/Y 1,0
PUMP
W/R 0,5
W 0,5
G/
R
0
,5
G
/R
0,
5
B
0,
5
B
R
0,
5
BR 0
,5
FAN ONLY
COOL
1
4
W/BL LINK
GR 0,5
B 0,5
N/C
AT
S1
CL DL RL
D
FT
MV
MP
Y
FS1
FS2
NOTE ORIENTATION OF SWITCHES
B 0
,5
A2
W
0,
5
1,5
0,5
0,5
B 0
,5
8 COM
7 N/C
6 N/O
5 FAULT SIGNAL
4 OUT
3 SIGNAL IN
2 L
1 N
B 0
,5
B 0
,5
PUMP CONTROLLER
4
5
6
1
2
3
2 POSN SWITCH
FAN SPEED
S2
CONTROL FUSE 7A
CONDENSATE FUSE 1A
BR 1,5
BR 0,5
BR 0,5
BR 0,5
BR 0,5
G/R 0,5
F1
F2
LAB
E
L D
355
551
D355550
IS
SU
E 1
2
FLYING LEADS
IF IN DOUBT ASK
DRG No.
B 0
,5
R 1.0
BL 1.0
WATER PUMP
TERM BLOCK
IN TERM BOX
B 0,5
BR
1
.0
O/BK 0,5
GR/B 0,5
R/B 0,5
G/Y 1,0
G/Y 1,0
G/Y 1,0
BR 1,5
B 1,5
Page 8
RED FLYING LEAD
RED FLYING LEAD
R/
B
L 0,
5
BL 0,5
R/B 0,5
2 CHANGES TO SUIT EXISTING PAC22 LOOM
05:11:03
1A
1A
F4
F2
10A
INSIDE
VIEW
R/BL 0,5
97
L1
L2
1 AS DRAWN
19:01:02
BL
B
BR
GR
O
P
R
W
G/Y GREEN/YELLOW
WHITE
RED
PINK
ORANGE
GREY
BROWN
BLUE
BLACK SCHWARZ
BLAU
BRAUN
GRAU
ORANGE
ROSA
ROT
WEIB
GRUN/GELB
NOIR
BLEU
MARRON
GRIS
ORANGE
ROSE
ROUGE
BLANC
VERT/JAUNE
V VIOLET
VIOLETT VIOLETTE
G GREEN
GRUN
VERT
TERM BLOCK
30A
EARTH/GROUND STUD
FAN CAP
COMP RUN CAP
HARD START CAP
SOCKET TO HEX UNIT
COMPRESSOR
SUMP HEATER
BASE EARTH
B 2,5
BR 2,5
B 0,
5
B 0,
5
B
0,
5
B 0,5
BR 0,5
B 0,5
BR 0,5
BL 0,5
R/
B
0
,5
R 2,5
BL
2
,5
BL 2,5
P 2,5
P 2,5
G/Y 2,5
PLUG
MAINS LEAD
G/Y 2,5
BLK FLYING
LEADS
B 0,5
G/Y 1,0
TERMINAL BLOCK
G/Y 2,5
G/Y 2,5
G/Y 1,0
G/Y 1,0
G/Y 1,0
G/Y 1,0
BR 0,5
S
R
C
GND
L1
L2
C3
C1
C2
GR/
B
0
,5
C
L
H
C
L
H
LP SWITCH
HP SWITCH
GR/B 0,5
O/
B
L 0
,5
FAULT
V 0
,5
V 0
,5
LAMP
FL
MC
G/Y (G USA)
BR (BL USA)
B (W USA)
HEX
WA
T
E
R
PU
M
P
7
4
9
6
B
A
6
3
5
2
1
4
HEX UNIT
MV
AI
R
ST
AT
1 4
HP L
P
FS
1
FS2
A2
A1
5
3
1
6
4
2
FL
MC
C1
C3
S R
C
AUX
N/
C
D
6
mi
ns
1
2
4
3
DL
6
5
C2
MV
CL
S2
FT
B
Y
RL
S1
SUMP HEATER
F1
10A
F3
COOL
FAN ONLY
LOW
HIGH
IN
N
COM
NC
IN
L
OU
T
NO
PUMP
CONTROLLER
TIME
MP
DELAY
K 1
FAN SPEED CAP
C4
ISS
C/N
APPD
DATE
R
c
U.C.C.
CALOREX HEAT PUMPS LTD
MATERIAL
FINISH
DO NOT SCALE PRINT
DRAWING CHANGE
Page9
F4
CONTROL FUSE 10A
B 0,5
1A
B 2,5
B 2,5
B 2,5
R/BL 0,5
B 0,5
B 0,5
GR
N(
G
R
N/
Y
E
L
)
BLK
D355552
LABEL D64355553
D355552
WIRING DIAGRAM
PAC320DX/HEX320D
ISSU
E 2
HEX UNIT
1
---
CJW 19:01:02
NTS
AIR STAT
4
5
6
1
2
3
3 POSN SWITCH
A B
7
4
9
6
5
3
1
6
4
2
21
DELAY TIMER
1 4
2 3
DEFROST STAT
FAN MOTOR
SOLENOID VALVE
CONDENSATE
FLOAT SWITCH
HIGH LEVEL
FLOAT SWITCH
LOW LEVEL
MAINS
DEFROST
CHILL
BR 2,
5
B
2.
5
BR 2,5
B 0,5
B 0,5
CONTACTOR B
AUX
A1
22
BR 0,5
BR
B 0,5
B 0,5
BR 0,5
R/BR 0,5
W
0,
5
BL/W 0,5
RELAY No 1
W
/BL
0,
5
P 0,5
P
0,
5
P 0,5
O/
B
L
0
,5
O 0,5
O 0,5
GR/B 0,5
W/
R
0
,5
W/
R
0
,5
B 0
,5
G/
R 0
,5
R 0,5
R
W 0
,5
GR 0,5
GR 0
,5
BR 0,5
BR
0
,5
B
R
1,
0
BLACK
BROWN
BR 0,5
BLUE
R 2
,5
BL
2,
5
FLYING LEAD
FLYING LEAD
SUMP
GREY
GREY
GREY
GREY
R/
B
R
0
,5
BR
0,
5
W
/BL
0,
5
B 0
,5
BR
2
,5
B 2
,5
W/R 0,5
B 0,5
W/R 0,5
G/Y 1,0
G/Y 1,0
B 0,5
B 0
,5
W/
R
0
,5
W
0,
5
O 0,5
BR
0,
5
B 0,5
BR
G/Y 1,0
PUMP
W/R 0,5
W 0,5
G/
R 0
,5
G
/R
0,
5
B 0
,5
BR
0
,5
B
R
0,
5
FAN ONLY
COOL
1
4
W/BL LINK
GR 0,5
B 0,5
WATER PUMP
BR 1,0
N/C
AT
S1
CL DL RL
D
FT
MV
MP
Y
FS1
FS2
NOTE ORIENTATION OF SWITCHES
B 0,
5
A2
W 0
,5
2,5
0,5
0,5
B 0,
5
8 COM
7 N/C
6 N/O
5 FAULT SIGNAL
4 OUT
3 SIGNAL IN
2 L
1 N
B 0
,5
B 0,
5
PUMP CONTROLLER
PUMP
FAN MOTOR
CA
PA
C
IT
O
R
CA
P
A
C
IT
O
R
BASE PLATE
EARTH
M
A
IN
S
SUPPL
Y
L1
L2
GND
WHT
BLK
GRN
GRN/YEL 1,50
BRN
BRN
WHT 1,00
PR
OT
EC
TO
R
MAINS
START
NO
NC
C
WATER STAT
BLK
R
E
D(
NO
T
U
S
E
D
)
WH
T
BL
K
WIRED TO RUN COUNTER CLOCKWISE
R
EVE
R
S
IN
G PLU
G
YEL(WHT)
BL
K
GR
N(
GR
N
/Y
E
L)
/WHT
BLK
A
T Z
S
E
F2
CONTROL FUSE 10A
CONDENSATE FUSE 1A
BR 0,5
BR 0,5
G/R 0,5
F1
F3
FLYING LEADS
BLK 1,00
WHT
YEL(WHT)
BLK
BLK
GRN
GRN (GRN/YEL)
GRN
G/Y
4
5
6
1
2
3
2 POSN SWITCH
FAN SPEED
S2
HIGH
LOW
TOLERANCE UNLESS SPECIFIED
HOLES TO BS 4500
E12
INSPECTION LEVEL
DIMS
SHT No.
CONT'
DRAWN
DRG No.
APPROVED
DATE
SCALE
IF IN DOUBT ASK
TITLE
DRG No.
Page 10
BLANK PAGE
Page11
BLANK PAGE
Page 12
BLANK PAGE