background image

THREE-PHASE
GRID-TIED OLAR INVERTER
QUICK INSTALLATION GUIDE

AS-IC01-2 SERIES

THANK YOU FOR CHOOSING AEG

Follow these instructions to successfully install your 
AEG solar inverter of the series AS-IC01-2:

AS-IC01-2 three-phase grid-tied solar inverter, 2 MPPT:
AS-IC01-4000-2/5000-2/6000-2/8000-2/10000-2

    

  CONTENTS 

1. Safety Recommendations
2. Product unpacking and inspection
3. Before installation
4. Mechanical installation
5.. Electrical installation
6. Operation
7. More information / Contacts

   1. SAFETY RECOMMENDATIONS 

General safety recommendations

• 

Only qualified electricians are allowed to install the 

inverter.

•  Make sure the installation site is not accessible to 

children or non-authorized personnel.

•  Remove metal accessories such as rings or bracelets 

before installation and electrical connection to avoid 
electric shock.

Product safety recommendations

•  Do not put and install the inverter on or close to 

combustible materials. 

•  Install the inverter far from devices with strong 

electromagnetic interference. 

•  To avoid product damage, ensure the inverter input 

voltage does not exceed the maximum input voltage.

•  Ensure a stable installation and a reliable electrical 

connection, as well as proper grounding of the inverter; 
improper connection or no grounding may cause the 
inverter to stop functioning.

•  To avoid irreparable damage, ensure that the positive 

and negative poles of solar modules are not grounded. 

!

   2. PRODUCT UNPACKING AND INSPECTION

2.1 Product inspection

Double-check the order information and the product na-
meplate to ensure the products are of the ordered type 

and that the package is not damaged. Should you find 

any problems, contact your supplier as soon as possible.

In the packaging of your AEG inverter you will find:

Model 
AS-IC01-xxx-2

4000-2
5000-2
6000-2
8000-2
10000-2

Inverter

1

Installation bracket

1

Quick installation guide

1

Communication connector

1

Expansion bolts

4 (M6*60)

DC connector

1

AC connector

1

Table 1: Three-phase inverter packing list

2.2 Product look

Front and side view of AEG AS-IC01-2 three-phase grid-
tied solar inverter

    

3. BEFORE INSTALLATION

Before installing your AEG grid-tied solar inverter, please 
take in consideration the following aspects:

3.1 Installation place

Select the installation place considering that:
1- The environment temperature should be between 
-25°C and 60 °C.
2- The insatllation surface should be perpendicular to the 

horizontal line. Please refer to figure 2 here below.

Figure 1: Installation space (mm)

Figure 2: Installation position

3.2 Cable specifications

Select connection cables according to the below table: 

Model 

DC side

AC side

Cross-section Mini cross-section

AS-
IC01-4000-2/
5000-2/
6000-2/
8000-2/
10000-2

4 mm

 

(12 AWG)

4 mm

(12 AWG)

 

Table 2: Cable specifications

1

2

3

4

   
    4. MECHANICAL INSTALLATION

We take as reference a typical installation environment, 
such as a concrete wall.

Figure 3: Installation brackets, AS-IC01-2 4000 to 10000

Model 

Installation hole

A x B

AS-
IR01-4000-2/
5000-2/
6000-2/
8000-2/
10000-2

260 mm x 45 mm

 

Table 3: Size of installation bracket

Follow these steps to install your AEG inverter:

1- Define the installation hole with aid of the installation 
bracket, and use the expansion bolts to fix the installation 

brackets to the designed location on the wall.

2-Lift the inverter to suspend it to the installation 
brackets and fasten with M8 hex socket cap screws.

3- Fasten the M5 screws and fasten the inverter to the 

bracket. Make sure the inverter is fastened firmly to the 

bracket.

Figure 4: Installation brackets, AS-IC01-2 4000 to 10000

   5 . ELECTRICAL INSTALLATION

Follow the next step to carry out the electrical wiring of 
your AEG inverter:

1- Before connecting the three-phase AC grid cable to 
the inverter, take lightning and short circuit protection 
measures in accordance with the local electrical safety 
codes.

2- As shown in Figure 6 below, connect and fasten L1, L2, 
L3, N (optional) and PE conductors of the three-phase 
common grid to the AC terminal, and then connect the 
terminal to the inverter´s AC port.

3- Fix and connect the DC output cables of the PV 
module with the matching DC connectors, and then 
connect the connectors to the inverter´s DC port.

Figure 5: Electrical wiring of the inverter

Figure 6: Connection of the AC to the inverter

DOCUMENT REVISION: PL201803 EN V.1-18

   
    6. OPERATION

6.1 Pre-operation inspection

Before starting inverter operations, please make sure to:

1- Check that the voltage of the components is in the 
allowed input voltage range of the inverter.
2- Check that the voltage of the AC grid is regular.
3- Check that the inverter is well grounded.
4- Ensure that all the switches are positioned on „OFF“
5- Ensure that all electrical safety precautions are clearly 

identifiable at the installation site.

6- Make sure that the WiFi stick (if used) is well 
connected.

6.2 Commissioning

To start the inverter:
1- Switch on the integrated DC switch.
2- Should you wish to change the default country, 
currency and time settings (Netherlands, EUR, GMT+1) 
of the inverter, you can use the External Display or the 
WiFi Stick (local monitoring mode via the app AEG 
InverterControl). 

In this case Install the WiFi Stick and the App as 
described in chapter 3 and 4.1 (page 6) of this guide, 
then connect your phone with the wireless network „AEG 
WiFi“ (generated by the WiFi Stick). Launch the App and 
select: Local Monitoring > click on your WiFi Stick picture 
> More > Parameter > change the individual parameters)

3- Switch on the breakers at the AC side
4- Check the LED indicators and the information 
displayed on the LCD screen / on the external display:

Run  Alarm  Fault

The green indicator blinks, the 

other  indicators  are  off:  the 

inverter is on and is in self-
inspection mode

Run  Alarm  Fault

The green indicator is on, the other 

indicators  are  off:  the  inverter  is 

in power generation mode after 
self-inspection. The inverter was 
successfully commissioned

Run  Alarm  Fault

Run  Alarm  Fault

„Alarm“ or „Fault“ indicators are on 
or blinking: the inverter is on, but 
faults are occurring

For the complete list of errors and warnings, see the 
extended version of the installation manual at 
www.aeg-industrialsolar.de/aeg-inverter-service

6.3 Accessories (Complements) and wiring

Complements to the inverter are :
-the External Display (optional)
-the WiF Sticki

   

Figure 8: Complements to the inverter

6.4 Regular maintenance

To carry out maintenance, inspection or troubleshooting 
operations on the inverter, stop the device as follows:

1- Switch off the breakers at the AC side.
2- Switch off the integrated (inverter´s) DC switch

3- Contact your local distributor or the AEG Inverter 
Service.

  

 7.  MORE INFORMATION / CONTACTS

You can download the extended version of the AEG grid-
tied three-phase solar inverter and the related Warranty 
Conditions at www.aeg-industrialsolar.de/aeg-inverter-
service. 

Solar Solutions GmbH
Schneckenhofstrasse 19
60596 Frankfurt am Main
Germany
service@aeg-industrialsolar.de

Last updated: March 2018 
AEG is a registered trademark used under license from Electrolux AB (publ).

 


background image

AEG WIFI STICK 
REMOTE MONITORING 
QUICK SETUP GUIDE

THANK YOU FOR CHOOSING AEG

Follow these instructions to successfully monitor the 
performances of you AEG grid-tied solar inverter with 
the AEG WiFi Stick. This guide is meant to provide 
a reference for setting up the AEG WiFi Stick in 
Remote Monitoring modus with the aid of the AEG 
InverterControl App.

The AEG WiFi Stick is a communication module enabling 
the transmission of relevant performance data from 
your AEG inverter to the monitoring software (AEG 
InverterControl App and AEG InverterControl Monitoring 
Webportal) 

    

  CONTENTS 

1. Safety Recommendations
2. Product unpacking and inspection
3. Mechanical installation

4. Configuration

5. Monitoring your plant
6. Troubleshooting

                           

1. SAFETY RECOMMENDATIONS 

General safety recommendations

• 

Only qualified electricians are allowed to install the 

AEG WiFi Stick.

•  Make sure the installation site is not accessible to 

children or non-authorized personnel.

•  Remove metal accessories such as rings or bracelets 

before installation and electrical connection to avoid 
electric shock.

Product safety recommendations

•  Do not store, place or install the AEG WiFi Stick on or 

close to combustible materials.

•  Ensure reliable connection between the AEG WiFi 

Stick and the inverter. 

   
     2. PRODUCT UNPACKING AND INSPECTION

2.1 Product unpacking

Double-check the order information and the product 
nameplate to ensure the products are of the ordered

type and that the package is not damaged. Should you 

find any problems, contact your supplier immediately.

IMPORTANT: Please keep the package of the 

AEG WiFi Stick. On the box you will find relevant 

information such as the Serial Number and the 
Product Key which are needed to complete the 

configuration process. 

2.2 Product inspection 

Product look 

Figure 1: AEG WiFi Stick look

    3. MECHANICAL INSTALLATION

The AEG WiFi Stick should be fastened to the installed 
AEG solar inverter following the steps below:

1- Complete the installation of your AEG inverter in the 
selected place. 
2- Connect the DC input and switch on the inverter 

without the AC grid (AC disconnect / switch off) 

3- Fasten up the WiFi Stick to the RS485 port of your 
AEG inverter.
4- Wait until the hotspot „AEG WiFi“ can be found.  Check 
the available wireless networks from your mobile or PC to 
understand if the hotspot was successfully set up.

5- Now you can proceed to configuring the WiFi Stick.

RS485

RS485

Figure 2: AEG WiFi Stick connected to an AEG inverter

    

4. CONFIGURATION

Before starting with the Remote Monitoring configuration 
of the AEG WiFi Stick, you fist need to register a Remote 

Monitoring Account via the AEG InverterControl App.

4.1 The AEG InverterControl App

The AEG InverterControl App for iOS 
and Android is available in the App 
Store and Google Play respectively.

4.2 Registering an account via the App

1

Download the AEG InverterControl App from 
the App Store / Google Play

2

Launch the App and select 
„Remote Monitoring“

3

You will be prompted to 
the Login and Registration 
page. Click on the „Regis-
ter“ button.

4

Fill in the data. Please make 
sure that you choose a 
User Name without special 
characters / blank spaces. 

Press „Register“ to confirm.

5

Return to the main 
interface of the app. Select 
„Remote Monitoring“

5

6

7

8

DOCUMENT REVISION: PL201803 EN V.1-18

!

6

Login with the Remote 
Monitoring Account you 
just created.

7

Click „+“ to add a new plant.

8

Fill in the required data and 

confirm with „OK“.

9

Now add the WiFi Stick: 
select your plant and click 
on „>“

10

Click on „Device Info“

11

On the Collector page, click 
on „+“ to add a WiFi Stick.

 

12

Input the name of the WiFi 
Stick (you can choose one 
arbitrarily) along with the 
Serial Number and Product 

Key that you will find on the 

WiFi Stick packaging (and/
or on the product itself).

The Serial Number (1) is 
written under the bar code. 
The Product Key (2)  is the 
6-digit number.

Press „OK“ to save the 
settings and proceed.

13

Refresh the App and you 

will find the newly added 

WiFi Stick. 

 

If you have more inverters in your plant, please repeat 
steps 10 to 13 to add the extra WiFi Sticks to the plant.

You can now proceed to configure the AEG WiFi Stick 

for Remote Monitoring via the App following the below 
procedure..

4.3 Configuring the WiFi Stick for Remote Monitoring

1

Enable the WiFi on your 
mobile device (phone, ta-
blet) and connect it to the 
hotspot „AEG WiFi“.

2

Launch the AEG Inver-
terControl App and select 
„WiFi settings“.

3

Click the „Search“ (lens) 

icon to find the WiFi Stick. 

Alternatively, click the „+“ 

icon and confirm the IP 

address.

1

2

4

Click on the WiFi Stick 

when the App finds it.

5

Select the parameters as 
indicated here below: 

Net Mo

de: select WIFI-STA

SSID

: Select your WiFi router

Password

: input the 

password of your WiFi router

Network Mode

: select 

„Client“

Apply the settings by clicking 
the „Save“ button (top right). 
The hotspot of the AEG WiFi 
Stick will now disappear.

6

Wait for approximately 
15 minutes to allow for 
synchronization. 

7

Launch again the 
AEG InverterControl App.
Select „Remote Monitoring“.

8

Login with your credentials.

9

You have now successfully 
installed your WiFi 
Stick and you can start 
monitoring your inverter.

 

    

5. MONITORING YOUR INVERTER

1

Launch the AEG Inverter-
Control App, select „Remo-
te Monitoring“ and login 
with your credentials.

2

Select your plant and click 
on the „>“ icon.

3

Access the general 
interface of your plant. By 
clicking on the monitoring 
options you can access 

the different reports and 

monitoring parameters

 

   6. TROUBLESHOOTING AND FURTHER INFO

Should you need to check that the connection between 
your WiFi Stick and the router is working correctly, 
connect your mobile device with the wireless network 
of your router and select „WiFi Settings“ in the AEG 

InverterControl App. If you cannot find the WiFi Stick or 

if the settings are not correct, reset the WiFi Stick and set 

the parameters again (see 4.3 „Configuring the WiFi Stick 

for Remote Monitoring“, steps 1 to 5). 

If you need to reset the WiFi Stick, press and hold the 
reset button for 5 seconds. 

For further configuration possibilities for your AEG WiFi 

Stick see www.aeg-industrialsolar.de/aeg-inverter-service.

You can download the extended version of the 
AEG WiFi Stick Installation Guide online at 
www.aeg-industrialsolar.de/aeg-inverter-service